FNP1500/FNP1800
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD.00247_AB
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
LEDs: DC OK (green), AC OK (green); fan fail and overtemperature (amber)
Monitors alarm functions and sets parameters
Contact closure to logic ground ( internal pull-down resistor of 1 kΩ)
PS Remote Shutdown / Inhibit Pin
TTL compatible signal, inhibited when open contact, high or at TTL logic “1”.
Signal referenced to logic return (LRTN)
AC OK & DC OK & no overcurrent & no overtemperature & fans working
AC Fail / Power Down Warning
(I2C & OC)2
Provides a warning that the input power has failed at least 5 ms before the output falls
out of regulation (<90% Vo1 set).
Open collector signal with 20 mA pull-down capability, referenced to logic return (LRTN).
AC fail will go high or open during power fail condition and will go low when input is within the operating
range.
A Power Fail warning will turn off the green AC OK LED.
DC fail / Output Voltage Fault
(I2C & OC)2
Internal undervoltage and overvoltage supervision of
V
o1.
Open collector signal with 20 mA pull-down capability, referenced to logic return (LRTN).
DC fail will go high or open if
V
o1 is < 90% or > 110% of
V
o1 set, measured in front of the ORing FETs.
A green LED on the front panel indicates normal operation.
The LED will flash if in parallel operation
V
o1 is OK, but the unit is disabled.
Temperature Warning (I2C & OC)2
I2C critical temperature warning: Indicates that the operating temperature has reached [Tshut-down – 10K]
I2C & OC overtemperature warning: Indicates if the unit is in overtemperature shutdown.
Open collector signal with 20 mA pull-down capability, referenced to logic return (LRTN).
The OC-output will go low 100 ms before an overtemperature condition shuts down the unit.
An amber LED on the front panel indicates overtemperature or fan fail.
DC Voltage Monitoring (I2C)1
Monitors the voltage
V
o1 at the output connector.
Accuracy ± 0.45 V over setting range, temperature and load.
DC Current Monitoring (I2C)1
Monitors the output current
I
o1 : Accuracy ± 0.4A over the load range.
DC Voltage Trimming
(I2C or external resistor)1
Output voltage trimming
V
o1: ± 8 % of
V
o set
Setting accuracy over I2C: ± 50mV at Vo nom, ± 150 mV over setting range
Two fan speed levels automatically set depending on the internal temperature.
The fan speed can be set to full speed or automatic control.
Indicates if the fans are operating or have failed.
Overcurrent signal which can be used for synchronous startup of units in parallel or to recover from an
overload condition. (See application note).
1 Detailed I2C information is available from the model’s I2C Manual found on the Bel Power Solutions web site.
2 Provided over the I2C interface and as an open collector signal on the output connector (OC).
Relative Humidity, Non-Condensing
0 °C to 70 °C (after 15 min warm-up)
IEC/EN 60068-2-6
2-8 Hz
8-200 Hz
200-500 Hz
Calculated per Bellcore (SR-332, Issue 1):
GB 25 °C
GB 25 °C (FNP1500-12G)
Demonstrated