Data sheet Field bus components FBCon PA CG 8way The FBCon Fieldbus distributor is available in the industry and EEx (ia) version. They are used for coupling from 1 to 8 field devices or sensors. They are connected via spur lines. The connection to the spur line can be made with an M12 plug or directly via an EMC cable gland. Communication and device power feed are transferred by a common 2-wire line. The distributors offer the following features respective of the version: * Tension-clamp connection system * Overvoltage protection for the main line * Current limiter for each branch line * EMC cable gland * M12 plug-in connectors * External earthing contact * Interruption-free bus operation * Industrial version * Bus termination integrated (not EX) * ATEX explosion-proof version * Pressure-equalising element * Protection degrees IP65, IP66, IP67 * Stainless steel versions * PROFIBUS-PA compatible Weidmuller Interface GmbH & Co. KG Klingenbergstrae 16 D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com General ordering data Type Order No. Version GTIN (EAN) Qty. FBCon PA CG 8way 8564300000 Standard distributor, 8-way distributor, IP 66 4032248287635 1 pc(s). Creation date December 18, 2013 10:13:52 PM CET Catalogue status / We reserve the right to make technical changes. 1 Data sheet Field bus components FBCon PA CG 8way Weidmuller Interface GmbH & Co. KG Klingenbergstrae 16 D-32758 Detmold Germany Fon: +49 5231 14-0 Fax: +49 5231 14-292083 www.weidmueller.com Technical data Dimensions and weights Length Height 175 mm 58 mm Width Net weight 80 mm 944 g -40 C...+80 C -40 C...+80 C Ambient temperature -40 C...+80 C branch line CG Spur line with cable gland surface-mounted Colour Protection degree Version Grey IP 66 Aluminium enclosure EC000214 27-25-02-01 27-24-26-08 UNSPSC eClass 6.2 26-12-16-03 27-24-26-08 Temperatures Operating temperature Storage temperature Technical data Cable gland Connection type PE Type of mounting Classifications ETIM 3.0 eClass 5.1 eClass 7.1 Product information Descriptive text ordering data Descriptive text technical data CG = brass cable gland PCG = plastic cable gland FBcon products cannot be used in strongly saline environment. Approvals Approvals ROHS Conform Downloads Declaration of Conformity K328_01_10.pdf Creation date December 18, 2013 10:13:52 PM CET Catalogue status / We reserve the right to make technical changes. 2