© 2006 TELEDYNE RELAYS (800) 284-7007 • www.teledynerelays.com S20DC100 Page 3
S20DC100\062006\Q1
NEW Series S20DC100
Output to 100A, 200 Vdc
DC Solid-State Relay
Please refer to the installation notice for
precautions about mounting the device on a heat sink.
Ambient Temperature (°C)
Power Dissipation (W)
Load Current (Arms)
110
100
90
80
70
60
50
40
30
20
10
0
266
220
178
141
108
79.2
55
35.2
19.8
8.8
2.2
0
0 3010 20 40 7050 60 80 11090 100
1.1°C/W 0.9°C/W 0.75°C/W 0.55°C/W 0.3°C/W 0.1°C/W0.3°C/W
8°C/W 4°C/W 2.4°C/W 2.2°C/W 2.1°C/W 1.95°C/W 1.5°C/W 1.3°C/W 1.2°C/W
POWER DISSIPATION AND LOAD CURRENT LIMIT VS. TEMPERATURE
Figure 8
GENERAL SPECIFICATIONS
(+25°C ambient temperature unless otherwise specified)
ENVIRONMENTAL SPECIFICATIONS
Min Max Units
Operating Temperature –40 +90 °C
Storage Temperature –40 +100 °C
Input-Output Isolation 4000 Vrms
Insulation Resistance 1 GΩ
Insulation Capacitance <8 pF
Junction Temperature 175 °C
CONNECTIONS
Power Control
Screwdriver Phillips NR2 Phillips NR1
Tightening Torque 1.8 N.m 0.8 N.m
Insulated crimp terminals
(Round Tabs, Eyelet Type) M5 M3
MISCELLANEOUS
Display Green LED (ON)
Housing UL94V0
Mounting 2 screws (M4x12mm)
Noise Level No audible noise
NOTES
1. For additional/custom options, contact factory.
Figure 9
PROTECTIVE COVER AVAILABLE
Add -14 to part number
GENERAL
Standards IEC60947-1
Protection Level IP00
Protection Against Direct Touch None
CE Marking Yes
E.M.C. EMISSION
Radiated & Conducted Disturbances NFEN55011