Power Supplies 3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
137
SCP-X Extreme Environment Series
The SCP-X is a rugged power supply designed for use in
extreme environments. The metal case reduces costs by
eliminating separate enclosures. Quick change connectors
simplify connectivity for distributed I/O devices on industrial
machinery. This model provides 24 Vdc output with limited
power to meet Class 2 requirements. Two models are
currently offered based on application.
Control Power (-CP) Applications
The SCP100S24X-CP is designed for Control Power
applications where a grounded power supply output is
required (Figure 2). The output power is limited to approx
96 total watts.
• Inputconnector:3-pole,malereceptacleexternally
threaded with 7/8”-16 UN mounting thread.
• Outputconnector:4-pole,femalereceptacleinternally
threaded with 7/8”-16 UN mounting thread.
DeviceNetTM (-DVN) Applications
The SCP100S24X-DVN is designed for DeviceNetTM
application where an isolated output from ground is required
(Figure 2).
• Inputconnector:3-pole,malereceptacleexternally
threaded with 7/8”-16 UN mounting thread.
• Outputconnector:4-pole,femalereceptacleinternally
threaded with 7/8”-16 UN mounting thread.
Features
• IP66/67Versatile/NEMA4XRated
• 24Vdc,115/230Vac,3.8ANominalCurrent
• Listedpowersupplyforstandaloneapplications
• Canbemountedinanyorientationwithoutlimitation
• Universalinput
• Highambienttemperatureupto60oC without derating
• DCOKGreenLED
• Worldwideapprovals
• Fiveyearlimitedwarranty
Certifications and Compliances
• Listed,Ind.ControlEquipment,E61379,ITE,
E137632
-UL508,CSAC22.2No.107.1
- UL60950-1/CSAC22.2No.60950-1,2ndEdition
 -LowVoltageDirective
- IEC/EN60950-1,2ndEdition
•RoHSCompliant
Related Products
• SDNSeries
Selection Table
Recommended Electrical Connections 1
E61379
E137632
Catalog Number Input 3-PIN Connections Output 4-PIN Connections
SCP 100S24X-CP DanielWoodhead
P/N103000A01FXX0 2
TurckRSM46*M
*lengthinmeters
SCP 100S24X-DVN
Catalog Number Output Current Output Voltage Output Power
SCP 100S24X-CP
3.8A 24 Vdc 95W
SCP 100S24X-DVN
1. Connections to be provided by the user.
2. XX is the length of the cordset in foot.
Power Supplies
3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
138
Electrical ConnectionsSCP100S24X-CP and SCP100S24X-DVN Mechanical Diagrams
Top View Side View
Bottom View
Notes:
1. Vdc connections are internally bonded to ground
2. V- is isolated from ground. V- is a separately derived source so it is
permissible to bond to ground if required in the application.
Figure 2
Power Supplies 3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
139
SCP-X Specifications
1. Inputcurrentratingsarespeciedwithlowinput,lineconditions,worstcase
efciencyvaluesandpowerfactor.
2.PowerFactorCorrectionat50/60Hzonly.
Input
Nominal Voltage Anyvoltagefrom100to240VacInput
-AC Range 85-264VacUniversalInput
-DC Range 100-353Vdc
Nominal Current 11.6A/0.7A
-Inrush current max. Typ.<25A
Power Factor Correction 20.95
Frequency 50/60/400Hz
Output
Power Back Immunity 35V
Overvoltage Protection 25-25.5Vdc,autorecovery
Nominal Voltage 24 Vdc
Tolerance <+/-2%overall(combinationline,load,timeandtemperaturerelatedchanges)
- Line Regulation <0.5%
- Load Regulation <0.5%
- Time & Temp. Drift < 1%
Ripple 3<50mVpp
Total Nominal Current 3.8A
Holdup Time >25ms(Fullload,100VacInput@Tamb=+25oC)to95%outputvoltage
General
Emissions EN61000-6-3,EN61204-3,EN55022ClassB,EN61000-3-2,EN61000-3-3
Immunity EN61000-6-2,EN61204-3,EN55024,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8,IEC61000-4-11
Temperature Storage: -40oto+85oC,Operation: -40o to +60oC full power with linear derating to half power from 60o to 70oC (Convection
cooling,noforcedairrequired).Operationupto100%loadpermissiblewithsidewaysorfrontsideupmountingorientation.
Humidity Upto100%RHwithcondensation
Altitude 2,000meters(6,600feet)
Vibration 1.0gravity(g)peak,10-500Hz(randomwave).
Passedrandomvibrationtestconditionsfor3axesfor60minutesdurationwhileenergizedandoperating.
Shock 4gravitypeak,22millisecondshalf-sinepulse,3timeson6faceswhileenergizedandoperating
Warranty 5YearLimitedWarranty
MTBF >500,000hoursaccordingtoTelecordia/BellcoreSR-332Issue1,(Vin120Vac,Tamb=40oC)
General Protection/Safety Protectedagainstcontinuousshort-circuit,continuousoverload,continuousopencircuit.ProtectionClass1(IEC536),
degreeofprotectionIP66/67versatile(IEC529).Safelowvoltage:SELV(acc.IEC60950)
Status Indicators - Visual DCOKLED
Installation
Fusing
-Input Internallyfused,fusesnotreplaceable
-Output ElectronicallycurrentlimitedtomeetClass2perUL1310
Mounting Chassismountedviabuiltinmountingtabs.Removalandreplacementoftheunitshallbepossiblefromfrontofpanel.
Connections Input:One3pinIP67moldedplug(minichange),internallythreaded.Output:Two4pinIP67moldedreceptacle(minichange),externallythreaded.
Case IP66/67versatileingressprotection;alsomeetsUL50Type4Xenclosure
Min. Required Free Space 1in.(25mm)allsides(permissibletomountinanyorientation)
H x W x D inches (mm) 4.73x6.52x1.80(120.0x166.0x46.0)
Weight - lbs (kg) 2.6 (1.16)
3.Ripple/noiseisstatedastypicalACvalueswhenmeasuredwitha20MHZ,
bandwidthscopeand50Ohmtermination.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Sola/Hevi-Duty:
SCP100S24X-CP