MODEL NUMBERS AC CONTROL A1210 A1225 A1240 A2410 A2425 A2450 A2475 A2490
DC CONTROL D1210 D1225 D1240 D2410 D2425 D2450 D2475 D2490
OUTPUT SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms] 24-140 24-140 24-140 24-280 24-280 24-280 24-280 24-280
Max. Load Current [Arms] 10 25 40 10 25 50 75 90
Min. Load Current, [mArms] 40 40 40 40 40 40 40 40
Transient Overvoltage [Vpk] 400 400 400 600 600 600 600 600
Max. Surge Current, (16.6ms) [Apk] 120 250 625 120 250 625 1000 1200
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Thermal Resistance Junction to Case (RθJC
) [˚C/W] 1.48 1.02 0.63 1.48 1.02 0.63 0.31 0.28
Maximum I2 t for Fusing, (8.3 msec.) [A 2sec] 60 260 1620 60 260 1620 4150 6000
Max. Off-State Leakage Current @ Rated Voltage [mArms] 8 8 8 1010101010
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] 500 500 500 500 500 500 500 500
Max. Turn-On Time 1/2 Cycle (DC Control), 10.0 msec (AC Control)
Max. Turn-Off Time 1/2 Cycle (DC Control), 40.0 msec(AC Control)
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
INPUT SPECIFICATIONS DC CONTROL AC CONTROL AC CONTROL
(E SUFFIX)
Control Voltage Range 3-32 Vdc 90-280 Vrms (60Hz) 18-36 Vrms
Max. Reverse Voltage -32 Vdc --- ---
Max. Turn-On Voltage 3.0 Vdc 90 Vrms 18 Vrms
Min. Turn-Off Voltage 1.0 Vdc 10 Vrms 4.0 Vrms
Nominal Input Impedance 1500 Ohms 60K Ohms 9.0K Ohms
Typical Input Current 3.4mA @ 5 Vdc, 20mA @ 28Vdc 2mA @ 120 Vrms, 4mA @ 240 Vrms 3mA @ 24 Vrms
GENERAL NOTES
All parameters at 25˚ C unless otherwise specified.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
Heat sinking required, for derating curves see page 3.
Turn-on time for random turn-on versions is 0.02 msec (DC Control Models).
Zero Voltage and Random
Turn-On Switching
Panel Mount
600V Transient Capability
Internal Snubber
110 & 125A Models
Available
FastFax Document No. 151
SERIES1
Rev. 102104
PAGE 1 OF 3
Featuring state-of-the-art Surface
Mount Technology, these SPST-NO
relays deliver proven reliability in the
most demanding applications. Output
consists of an SCR AC switch and is
available in zero-cross, random turn-
on (phase controllable) and normally
closed (Form B) versions with either
AC or DC input (coil) control.
Manufactured in Crydoms ISO 9001
Certified facility for optimum product
performance and reliability.
© 2003 CRYDOM CORP, Specifications subject to change without notice.
Integrated Overvoltage
Protection by Automatic
Self Turn-On (Suffix P)
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com
WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
S
e
r
i
e
s
1
10
-
90
A
m
p
120
/
240
V
ac
-
A
C
O
U
T
P
U
T
Screw Torque Requirements:
6-32 Screws - 10 in. lbs.,
8-32 and 10-32 Screws - 20in. lbs.
(Screws dry without grease.)
Fastons:
Single pair (up to 25A)
Double pair* (up to 50A).
*Caution: User must connect to both pairs
FastFax Document No.151
SERIES1
Rev. 102104
PAGE 2 OF 3
AVAILABLE OPTIONS
-B Normally Closed (Form B)
Example: D2450-B, A2450-B
4D 400 Hz Operation
10-50 Amp Models Only
Zero Cross Switching Only
Example: 4D2450
E24 Vac Input (18-36 Vac)
Example: A2450E
-10 Random Turn-On (AC & DC Control)
Phase Controllable (DC Control)
Example: D2450-10
FFaston Terminals (Up to 50A Models)
Example: D1225F
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc 109Ohm
Max. Capacitance Input/Output 8 pF
Ambient Operating Temperature Range -40 to 80˚C
Ambient Storage Temperature Range -40 to 125˚C
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g)
Encapsulation: Thermally Conductive Epoxy
Terminals: Screws and Saddle Clamps Furnished, Unmounted
APPROVALS
UL E116949
CSA LR81689
VDE 10143 UG
(Not Applicable: -B and 4D)
Crydom Heat Sinks offer excellent
thermal management and are per-
fectly matched to the load current rat-
ings of Crydom panel mount relays.
Request Crydoms Heat Sink specifica-
tion sheet for all the details.
© 2003 CRYDOM CORP, Specifications subject to change without notice.
All dimensions are in inches (millimeters)
.90
(22.9)
FASTON
TERMINAL
.187 X .032
(2 PLCS.)
BASE PLATE
.125 (3.2)
FASTON TERMINAL
.250 X .032 (2 PLCS.)
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.87 REF.
(22.2)
OUTPUT
INPUT
1.00
(25.4)
1.80
(45.7)
.45
(11.4)
1.10
(27.9)
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
PInternal Overvoltage Protection.
Relay Will Self Trigger Between
450-600 Vpk. Not Suitable For Capacitive Loads.
Not Available with -B Option
Agencies Approval Pending.
Example: D2425P
GInput Status LED.
Agencies Approval Pending
Example: D2450G
Note: Control Voltage Range 4.5-32Vdc
for DC Control Models.
12
43
+
--
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.90
(22.9)
.45
(11.4)
1.10
(27.9)
8-32 TERMINAL
(2 PLACES )
1.00
(25.4) 6-32 TERMINAL
(2 PLACES)
1.80
(45.7)
12
OUTPUT
34 +--
INPUT
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE
.125 (3.2)
Ordering System: Combination of the
suffixes should be made in the following order:
EFPG-10.
Example: A2450EFPG-10
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com
WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
H Heat Transfer Pad (Attached)
Example: D2450H
S
e
r
i
e
s
1
10
-
90
A
m
p
120
/
240
V
ac
-
A
C
O
U
T
P
U
T
12
8
4
024 8106 20406080
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
110
115
120
Base Plate Temp [˚C]
10A
9˚C/W 5˚C/W
3˚C/W
7˚C/W
NO HEATSINK
30
20
10
25
15
5
0510 202515 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
95
120
Base Plate Temp [˚C]
25A
1˚C/W
100
110
3˚C/W
NO HEATSINK
60
40
20
010 20 40 5030 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
90
Base Plate Temp [˚C]
50A
2˚C/W
1˚C/W .5˚C/W
100
110
120
1.5˚C/W
NO HEATSINK
120
80
40
015 30 60 7545 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
100
110
120
Base Plate Temp [˚C]
75A
.5˚C/W
95
1˚C/W
120
80
40
020 40 80 060 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
Power Dissipation
100
110
120
Base Plate Temp [˚C]
90A
1˚C/W
.4˚C/W
.2˚C/W
90
.5˚C/W
2˚C/W
.3˚C/W
CURRENT DERATING CURVES
FastFax Document No.151
SERIES1
Rev. 102104
PAGE 3 OF 3
© 2003 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com
WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
S
e
r
i
e
s
1
10
-
90
A
m
p
120
/
240
V
ac
-
A
C
O
U
T
P
U
T