Time-Delay Fuses SC
Class G – 600 Volt, 12- 20 Amps
480 Volt, 25 - 60 Amps
A
(Length)
.41"
(10.41mm
)
Catalog Numbers
SC-⁄Ω SC-6 SC-25
SC-1 SC-7 SC-30
SC-1⁄Ω SC-8 SC-35
SC-2 SC-9 SC-40
SC-2⁄Ω SC-10 SC-45
SC-3 SC-12 SC-50
SC-4 SC-15 SC-60
SC-5 SC-20
Dimensional Data
Catalog Symbol: SC
Current-Limiting
Ampere Rating: Ω™ to 60A (fast-acting),
7 to 60A (time-delay)
Voltage Ratings:
SC ⁄Ω™ to 20 600Vac, 170Vdc
SC 25 to 60 480Vac, 300Vdc
Interrupting Rating: 100,000A RMS Sym. AC, 10,000A dc
Agency Information:
UL Listed, Std. 248-5, Class G, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.5, Class 1422-01, File 53787
Carton Quantity and Weight
Catalog Carton Weight†
Number Qty. Lbs. Kg.
Ω™–15 4 0.060 0.0272
20 4 0.064 0.029
25–30 2 0.040 0.018
35–60 2 0.075 0.0340
†Weight per carton.
Fuse (Amps) A
SC-⁄Ω™ to 15 1.31
SC-20 1.41
SC-25 to 30 1.62
SC-35 to 60 2.25
General Information:
Compact branch-circuit units with high interrupting rating
and current-limitation.
With 600V rating, they can be used in 120/208, 120/240
and 277/480V circuits.
Length variations relative to case size make the “rejec-
tion” type fuses.
In general, SC fuses are about ⁄Ω£ the size of the 600V
NEC fuse type.
SC fuses with ampere ratings above 6A have a
degree of overload time-delay which permits them to
pass temporary overloads. At 200% load, they have a
minimum opening time of 12 seconds.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to
Data Sheet:
8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Recommended fuseblocks/fuseholders for
Class G fuses
See Data Sheets listed below
• Open fuseblocks - 1106
• In-line fuseholders - 1123, 1124
0104 SB04105 Page 1 of 3 Data Sheet 1024
© 2011 Cooper Bussmann
www.cooperbussmann.com
Peak Let-Through Curves
B60
30
20
15
AMPERE
RATING
A
10,000
1,000
100
100
1,000
10,000
100,000
INSTANTANEOUS PEAK LET-THROUGH
CURRENT IN AMPS
RMS SYMMETRICAL CURRENTS IN AMPERES
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS)
0104 SB04105 Page 2 of 3 Data Sheet 1024
© 2011 Cooper Bussmann
www.cooperbussmann.com
CURRENT IN AMPERES
TIME IN SECONDS
100
10
1
.1
.01 10 100 1, 0 0 0
1
.7 2,000
1/2A
1-1/2A
2-1/2A
1A
2A
3A
5A 6A
8A
10A
12A
15A
20A
30A
60A
4A
300
Time-Current Characteristic Curves– Total Clearing
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of
this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product da ta and provide technical informa-
tion that will help the end user with design applica tions. Cooper Bussmann reser ves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice,
any technical informa tion contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applica tions.
0104 SB04105 Page 3 of 3 Data Sheet 1024
© 2011 Cooper Bussmann
www.cooperbussmann.com