Extract from the online catalog MINI-PS-100-240AC/24DC/C2LPS Order No.: 2866336 http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866336 DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 100 W, NEC Class 2 approval. Product notes WEEE/RoHS-compliant since: 17/01/2008 Commercial data EAN 4 017918 975043 Pack 1 Customs tariff 85044081 Country of Origin CN Catalog page information Page 597 (IF-2011) Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation at http:// www.download.phoenixcontact.com. The General Terms and Conditions of Use apply to Internet downloads. Technical data Input data Nominal input voltage 100 V AC ... 240 V AC AC input voltage range 85 V AC ... 264 V AC DC input voltage range 90 V DC ... 350 V DC AC frequency range 45 Hz ... 65 Hz PHOENIX CONTACT Ltd http://www.phoenixcontact.co.uk Page 1 / 6 20-Jan-2012 MINI-PS-100-240AC/24DC/C2LPS Order No.: 2866336 http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866336 DC frequency range 0 Hz Current consumption Approx. 1.3 A (120 V AC) 0.8 A (230 V AC) Approx. 1.3 A (90 V DC) Approx. 0.4 A (350 V DC) Inrush surge current < 15 A (typical) Power failure bypass > 20 ms (120 V AC) > 100 ms (230 V AC) Input fuse 3.15 A (slow-blow, internal) Permissible backup fuse B6 B10 B16 Output data Nominal output voltage 24 V DC 1% Setting range of the output voltage 22.5 V DC ... 26 V DC (> 24 V constant capacity) Output current 3.8 A (-25 C ... 60 C) Derating 60 C ... 70 C (2.5%/K) Connection in parallel Yes, for redundancy and increased capacity Connection in series Yes Residual ripple < 40 mVPP (20 MHz) Peak switching voltages idling < 100 mVPP (20 MHz) Maximum power dissipation idling 2.5 W Power loss nominal load max. 12 W General data Width 67.5 mm Height 99 mm Depth 107 mm Net weight 0.4 kg Operating voltage display Green LED Efficiency > 88 % (for 230 V AC and nominal values) Insulation voltage input/output 3 kV (routine test) 3 kV (type test) Degree of protection IP20 Protection class II (in an enclosed control cabinet) PHOENIX CONTACT Ltd http://www.phoenixcontact.co.uk Page 2 / 6 20-Jan-2012 MINI-PS-100-240AC/24DC/C2LPS Order No.: 2866336 http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866336 MTBF (IEC 61709, SN 29500) > 500000 h Ambient temperature (operation) -25 C ... 70 C (> 60 C derating) Ambient temperature (storage/transport) -40 C ... 85 C Max. permissible relative humidity (operation) 95 % (at 25 C, no condensation) Mounting position horizontal DIN rail NS 35, EN 60715 Assembly instructions Can be aligned: Horizontally 0 mm, vertically 50 mm Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC Noise emission EN 50081-2 Noise immunity EN 61000-6-2:2005 Low Voltage Directive Conformance with LV directive 2006/95/EC Standard - Safety of transformers EN 61558-2-17 Standard - Electrical safety EN 60950-1/VDE 0805 (SELV) Standard - Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV) Standard - Safe isolation DIN VDE 0100-410 DIN VDE 0106-1010 Standard - Limitation of mains harmonic currents EN 61000-3-2 Standard - Equipment safety GS (tested safety) UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950 UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D NEC Class 2 as per UL 1310 Surge voltage category III Connection data, input Connection method Pluggable screw connection Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 2.5 mm Conductor cross section stranded min. 0.2 mm Conductor cross section stranded max. 2.5 mm Conductor cross section AWG/kcmil min. 24 Conductor cross section AWG/kcmil max 12 Stripping length 7 mm Screw thread M3 PHOENIX CONTACT Ltd http://www.phoenixcontact.co.uk Page 3 / 6 20-Jan-2012 MINI-PS-100-240AC/24DC/C2LPS Order No.: 2866336 http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866336 Connection data, output Connection method Pluggable screw connection Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 2.5 mm Conductor cross section stranded min. 0.2 mm Conductor cross section stranded max. 2.5 mm Conductor cross section AWG/kcmil min. 24 Conductor cross section AWG/kcmil max 12 Stripping length 7 mm Signaling Output name DC OK active Output description UOUT > 21.5 V: High signal Maximum switching voltage 24 V Output voltage + 24 V (signal) Continuous load current 20 mA Status display "DC OK" LED green Note on status display UOUT > 21.5 V: LED lights up Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 2.5 mm Conductor cross section stranded min. 0.2 mm Conductor cross section stranded max. 2.5 mm Conductor cross section AWG/kcmil min. 24 Conductor cross section AWG/kcmil max 12 Tightening torque, min 0.5 Nm Tightening torque max 0.6 Nm Screw thread M3 Certificates Certification CUL, CUL Listed, UL, UL Listed Certification Ex: CUL-EX LIS, UL-EX LIS PHOENIX CONTACT Ltd http://www.phoenixcontact.co.uk Page 4 / 6 20-Jan-2012 MINI-PS-100-240AC/24DC/C2LPS Order No.: 2866336 http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866336 Drawings Block diagram Diagram Output characteristic curve PHOENIX CONTACT Ltd http://www.phoenixcontact.co.uk Page 5 / 6 20-Jan-2012 MINI-PS-100-240AC/24DC/C2LPS Order No.: 2866336 http://eshop.phoenixcontact.co.uk/phoenix/treeViewClick.do?UID=2866336 Address PHOENIX CONTACT Ltd Halesfield 13 Telford / Shropshire / TF7 4PG,England Phone 01952 681 700 Fax 01952 681 799 http://www.phoenixcontact.co.uk Phoenix Contact Ltd. Technical modifications reserved; PHOENIX CONTACT Ltd http://www.phoenixcontact.co.uk Page 6 / 6 20-Jan-2012