1
Power entry modules without line filter KEC
https://www.schurter.com /PG05
Connectors
IEC Appliance Inlet C14 with Fuseholder 1- or 2-pole and Voltage Selector
IEC connector C14 with fuse holder 1- or 2-pole
Screw-on mounting
from front side
Fuse drawer must be ordered separately (see
accessories).
IEC connector C14 with fuse holder 1- or 2-pole
with voltage selector
Snap-in mounting from front side
Fuse drawer must be ordered separately (see
accessories).
See below:
Approvals and Compliances
C14
70° C
Description
- Panel mount :
Screw-on version from front or rear side, snap-in version from front
side
- 3 Functions :
Appliance Inlet Protection class I , Fuseholder with interchangeable
fuse drawer for Fuse-links 5x20 mm or 6.3x32 mm 1- or 2-pole , with
or without voltage selector (step switch)
- Meets the requirements of IEC 60335-1 for appliances in unattended
use. This includes the enhanced requirements of glow wire tests acc.
to IEC 60695-2-12 and -13.
- Quick connect terminals 4.8 x 0.8 mm
Characteristics
- Available with or without internal connections
- The fuse drawer "Fingergrip" can be removed by hand
- Suitable for use in equipment according to IEC/UL 62368-1
Other versions on request
- Fuse drawer with other voltage values
- For protection class II
- Variant with notch for V-Lock mating Cordsets
References
Alternative: version with line filter KFC
Weblinks
pdf data sheet, html datasheet, General Product Information, Approvals,
Distributor-Stock-Check, Accessories, Detailed request for product
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC 10 A / 250 VAC; 50 Hz
Ratings UL/CSA 10 A / 250 VAC; 60 Hz
Dielectric Strength > 3 kVAC between L-N
> 4 kVAC between L/N-PE
(1 min/50 Hz)
Allowable Operation Tempe-
rature
-25 °C to 70 °C
IP-Protection from front side IP40 acc. to IEC 60529
Protection against electric
shock
Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Quick connect terminals 4.8 x 0.8 mm
Panel Thickness S Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 1.5/2/2.5 mm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance inlet/-outlet C14 acc. to IEC 60320-1,
UL 60320-1, CSA C22.2 no. 60320-1
(for cold conditions) pin-temperature 70
°C, 10 A, Protection Class I
Fuseholder 1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 or 6.3 x 32 mm
Rated Power Acceptance @
Ta 23 °C
5 x 20: 2.5 W (1 pole)/ 2 W (2-pole) per
pole
6.3 x 32: 3.15 W (1 pole)/ 2.5 W (2-pole)
per pole
Power Acceptance @ Ta >
23°C
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
Voltage Selector optional, step, 2-4 digits
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.