Basic-type Digital Temperature Controller E5CN/E5CN-U (48 x 48 mm) CSM_E5CN_E5CN-U_DS_E_5_7 New 48 x 48-mm Basic Temperature Controller with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. * Indication Accuracy Thermocouple input: 0.3% of PV (previous models: 0.5%) Pt input: 0.2% of PV (previous models: 0.5%) Analog input: 0.2% FS (previous models: 0.5%) * New E5CN-U Models (Plug-in Models) with analog inputs and current outputs. * A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/ manual, RUN/STOP, and alarms) and the PV or SV. * Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. 48 x 48-mm E5CN 48 x 48-mm E5CN-U For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Refer to Safety Precautions for E5@N/E5@N-H. Refer to Operation for E5@N/E5@N-H for operating procedures. Main I/O Functions Event Inputs * None * Two Sensor Inputs * Universal thermocouple/Pt inputs (Models with temperature inputs) * Analog current/voltage inputs (Models with analog inputs) Indication Accuracy * Thermocouple input: 0.3% of PV * Pt input: 0.2% of PV * Analog input: 0.2% FS Sampling Period * 250 ms E5CN 2-level Display: PV and SV Control Output 2 * None * Voltage output (for driving SSR) Auxiliary Outputs * None * One * Two 4-digit Display * Auto/manual switching * Temperature Controller status display * Simple program function * Control output ON/OFF count alarm * PV change rate alarm * Models also available with RS-485 communications Control Output 1 * Relay output * Voltage output (for driving SSR) * Current output * Long-life relay output (hybrid) This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) 1 E5CN/E5CN-U Lineup 1 control output 0 or 2 auxiliary outputs Temperature input 2 control outputs 2 auxiliary outputs 1 control output 0 or 2 auxiliary outputs Terminal block Analog input E5CN 2 control outputs 2 auxiliary outputs Temperature input 1 control output 0, 1, or 2 auxiliary outputs Analog input 1 control output 0, 1, or 2 auxiliary outputs Basic Type Plug-in Note: Models with one control output and one or two auxiliary outputs and models with two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers Option Units E5CN-@@M@@-@-500 E53-CN@@@ 1 2 3 4 5 1 6 7 1. Control Output 1 R: Relay output Q: Voltage output (for driving SSR) C: Current output Y: Long-life relay output (hybrid) *1 2. Auxiliary Outputs *2 Blank: None 2: Two outputs 3. Option M: Option Unit can be mounted. 4. Input Type T: Universal thermocouple/platinum resistance thermometer L: Analog current/voltage input 5. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 6. Case Color Blank: Black W: Silver 2 3 4 1. Applicable Controller CN: E5CN or E5CN-H 2. Function 1 Blank: None Q: Control output 2 (voltage for driving SSR) P: Power supply for sensor 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) B: Two event inputs 03: RS-485 communications H03: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + RS-485 communications HB: Heater burnout/SSR failure/Heater overcurrent detection (CT1) + Two event inputs HH03: Heater burnout/SSR failure/Heater overcurrent detection (CT2) + RS-485 communications 4. Version N2: Applicable only to models released after January 2008 7. Terminal Cover -500: With terminal cover Note: 1. Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@). 2. Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details. *1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for switching the circuit. For details, check the conditions in Ratings. *2. Auxiliary outputs are contact outputs that can be used to output alarms or results of logic operations. 2 E5CN/E5CN-U Ordering Information Controllers with Terminal Blocks Size Case color Power supply voltage Input type Auxiliary outputs None 100 to 240 VAC 24 VAC/VDC Black Thermocouple or Resistance thermometer Thermocouple or Resistance thermometer 2 None 2 None 1/16 DIN 48 x 48 x 78 (W x H x D) 100 to 240 VAC Analog (current/voltage) 2 24 VAC/VDC Analog (current/voltage) 2 None 100 to 240 VAC Silver Thermocouple or Resistance thermometer 24 VAC/VDC 2 Control output 1 Relay output E5CN-RMT-500 Voltage output (for driving SSR) E5CN-QMT-500 Current output E5CN-CMT-500 Relay output E5CN-R2MT-500 Voltage output (for driving SSR) E5CN-Q2MT-500 Current output E5CN-C2MT-500 Long-life relay output (hybrid) E5CN-Y2MT-500 Relay output E5CN-RMTD-500 Voltage output (for driving SSR) E5CN-QMTD-500 Current output E5CN-CMTD-500 Relay output E5CN-R2MTD-500 Voltage output (for driving SSR) E5CN-Q2MTD-500 Current output E5CN-C2MTD-500 Relay output E5CN-RML-500 Voltage output (for driving SSR) E5CN-QML-500 Current output E5CN-CML-500 Relay output E5CN-R2ML-500 Voltage output (for driving SSR) E5CN-Q2ML-500 Current output E5CN-C2ML-500 Long-life relay output (hybrid) E5CN-Y2ML-500 Relay output E5CN-R2MLD-500 Voltage output (for driving SSR) E5CN-Q2MLD-500 Current output E5CN-C2MLD-500 Relay output E5CN-RMT-W-500 Voltage output (for driving SSR) E5CN-QMT-W-500 Current output E5CN-CMT-W-500 Relay output E5CN-R2MT-W-500 Voltage output (for driving SSR) E5CN-Q2MT-W-500 Current output E5CN-C2MT-W-500 Long-life relay output (hybrid) E5CN-Y2MT-W-500 E5CN-R2MTD-W-500 Relay output Voltage output (for driving SSR) 2 Model Current output E5CN-Q2MTD-W-500 E5CN-C2MTD-W-500 Note: Models with analog inputs do not have temperature unit indicators. Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions. Model (See Note 2.) Functions Communications RS-485 3-phase heater burnout/SSR failure/ Heater overcurrent detection Heater burnout/SSR failure/Heater overcurrent detection E53-CNHH03N2 Event inputs Communications RS-485 E53-CNHBN2 Control output 2 (Voltage for driving SSR) Event inputs Heater burnout/SSR failure/Heater overcurrent detection Communications RS-485 Communications RS-485 Heater burnout/SSR failure/Heater overcurrent detection E53-CNQ03N2 External power supply for ES1B E53-CNPBN2 External power supply for ES1B E53-CNPHN2 External power supply for ES1B E53-CNP03N2 E53-CNH03N2 Communications RS-485 E53-CN03N2 Event inputs E53-CNBN2 Heater burnout/SSR failure/Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHN2 3-phase heater burnout/SSR failure/ Heater overcurrent detection Control output 2 (Voltage for driving SSR) E53-CNQHHN2 Control output 2 (Voltage for driving SSR) E53-CNQBN2 Event inputs Note: 1. Option Units cannot be used for plug-in models. These Option Units are applicable only to models released after January 2008. 2. If models with heater burnout detection are used together with the E5CN-C@ Temperature Controller and control output 1 (current output) is assigned to the heating control output, heater burnout detection will be disabled. 3 E5CN/E5CN-U Model Number Structure Model Number Legend (Plug-in-type Controllers) E5CN-@@@U 1 2 3 4 3. Input Type T: Universal thermocouple/platinum resistance thermometer L: Analog Input 4. Plug-in type U: Plug-in type 1. Output Type R: Relay output Q: Voltage output (for driving SSR) C: Current output 2. Number of Alarms Blank: No alarm 1: One alarm 2: Two alarms Ordering Information Plug-in-type Controllers Size Case color Power supply voltage Input type Auxiliary outputs Control output 1 Relay output None Thermocouple or resistance thermometer 100 to 240 VAC 1 2 1 1/16 DIN Analog (current/voltage) Black 2 None 24 VAC/VDC Thermocouple or resistance thermometer 1 2 Model E5CN-RTU Voltage output (for driving SSR) E5CN-QTU Current output E5CN-CTU Relay output E5CN-R1TU Voltage output (for driving SSR) E5CN-Q1TU Current output E5CN-C1TU Relay output E5CN-R2TU Voltage output (for driving SSR) E5CN-Q2TU Current output E5CN-C2TU Relay output E5CN-R1LU Voltage output (for driving SSR) E5CN-Q1LU Current output E5CN-C1LU Relay output E5CN-R2LU Voltage output (for driving SSR) E5CN-Q2LU Current output E5CN-C2LU Relay output E5CN-RTDU Voltage output (for driving SSR) E5CN-QTDU Current output E5CN-CTDU Relay output E5CN-R1TDU Voltage output (for driving SSR) E5CN-Q1TDU Current output E5CN-C1TDU Relay output E5CN-R2TDU Voltage output (for driving SSR) E5CN-Q2TDU Current output E5CN-C2TDU Note: Models with analog inputs do not have temperature unit indicators. 4 E5CN/E5CN-U Accessories (Order Separately) Adapter USB-Serial Conversion Cable Model Connectable models E58-CIFQ1 Terminal Cover Connectable models Model Terminal block models Y92F-45 Note: Use this Adapter when the panel has been previously prepared for the E5B@. Model DIN Track Mounting Adapter Terminal block models E53-COV17 Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Model Y92F-52 Sockets (for Plug-in Models) Model Y92S-29 Note: The Waterproof Packing is included with the Controller only for models with terminal blocks. Current Transformers (CTs) Hole diameter Model 5.8 dia. E54-CT1 12.0 dia. E54-CT3 Type Model Front-connecting Socket P2CF-11 Front-connecting Socket with Finger Protection P2CF-11-E Back-connecting Socket P3GA-11 Terminal Cover for Back-connecting socket with Finger Protection Y92A-48G Front cover Type Model Hard Front Cover Y92A-48B Soft Front Cover Y92A-48D CX-Thermo Support Software Model EST2-2C-MV4 5 E5CN/E5CN-U Specifications Ratings Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption E5CN 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA) E5CN-U 100 to 240 VAC: 6 VA (max.) 24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W) Sensor input Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C Voltage input: 0 to 50 mV Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB.) Control method ON/OFF control or 2-PID control (with auto-tuning) E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA E5CN-U SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Voltage output (for driving SSR) E5CN E5CN-U Output voltage: 12 VDC 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit Current output E5CN 4 to 20 mA DC/0 to 20 mA DC, load: 600 max., resolution: approx. 10,000 Long-life relay output E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max. (250 VAC, 60 Hz) Relay output Control outputs Auxiliary outputs Event inputs Number of outputs 1 or 2 max. (Depends on the model.) Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA Number of inputs 2 External contact input specifications Contact input: ON: 1 k max., OFF: 100 k min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact External power supply for ES1B 12 VDC 10%, 20 mA, short-circuit protection circuit provided Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators (7-segment display also possible) Character height: PV: 11 mm, SV: 6.5 mm Multi SP Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial communications. Bank switching Not supported Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection (including SSR failure and heater overcurrent detection), 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment Ambient operating temperature -10 to 55C (with no condensation or icing), for 3-year warranty: -10 to 50C Ambient operating humidity 25% to 85% Storage temperature -25 to 65C (with no condensation or icing) 6 E5CN/E5CN-U Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal Inputs) Input Type Platinum resistance thermometer Name Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PL II 10 to 70C 60 to 120 C 115 to 165 C 140 to 260 C Analog input 0 to 50 mV 2300 2300 1800 1800 1700 1700 1700 1600 1500 Temperature range (C) 1400 1300 1300 1300 1300 Usable in the following ranges by scaling: -1999 to 9999 or -199.9 to 999.9 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.0 400 400 400.0 400 400.0 260 300 200 100.0 100 0 Setting number 165 90 100 0.0 -100.0 -200.0 100.0 120 0.0 -20.0 -100 -20.0 -200 -199.9 0 1 -199.9 2 -200 3 4 -200 -199.9 -200 5 6 7 0 0 16 17 0 0 0 0 0 0 24 25 19 20 21 22 -100 8 9 10 11 -200 -199.9 -200 12 Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990 13 14 15 18 23 JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Models with Analog Inputs Input Type Input specification Current 4 to 20mA Voltage 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V Setting range Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 Setting number 0 1 2 3 4 Shaded settings are the default settings. 7 E5CN/E5CN-U Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function). Alarm output operation Set value 0 Alarm type Alarm function OFF 1 *1 Upper- and lower-limit 2 Upper-limit 3 Output OFF 5 *1 Upper- and lower-limit with standby sequence 6 Upper-limit with standby sequence 9 10 11 L ON OFF Absolute-value lower-limit with standby sequence ON OFF Set the downward deviation in the set point by setting the alarm value (X). *4 A standby sequence is added to the upper- and lower-limit alarm (1). *6 ON OFF X ON OFF SP X ON OFF 0 X ON OFF X SP Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). SP ON OFF Set the upward deviation in the set point by setting the alarm value (X). SP *3 X ON OFF X H SP ON OFF Absolute-value upper-limit with standby sequence H SP *5 Absolute-value lower-limit ON OFF SP ON OFF Absolute-value upper-limit ON OFF X L Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). *2 X ON OFF Lower-limit with standby sequence No alarm SP ON OFF Upper- and lower-limit range H SP ON OFF 4 *1 8 L ON OFF Lower-limit 7 Description of function When alarm value When alarm value X is positive X is negative ON OFF 0 X ON OFF 0 X ON OFF 0 X A standby sequence is added to the upper-limit alarm (2). *6 SP X A standby sequence is added to the lower-limit alarm (3). *6 SP X 0 The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point. 0 The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. 0 A standby sequence is added to the absolute-value upper-limit alarm (8). *6 0 A standby sequence is added to the absolute-value lower-limit alarm (9). *6 X X X 12 LBA (alarm 1 type only) --- *7 13 PV change rate alarm --- *8 *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as "L" and "H." *2. Set value: 1, Upper- and lower-limit alarm Case 2 Case 1 Case 3 (Always ON) H < 0, L < 0 L H SP H < 0, L > 0 H < L H SP L H H > 0, L < 0 H > L H SP L H < 0, L > 0 H L L SP SP H L H > 0, L < 0 H L *3. Set value: 4, Upper- and lower-limit range Case 1 *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the operation of the standby sequence. *7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the loop burnout alarm (LBA). *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) for information on the PV change rate alarm. Case 3 (Always OFF) Case 2 H < 0, L < 0 L H SP H < 0, L > 0 H < L SP L H H H > 0, L < 0 H > L H SP L L SP SP H L H < 0, L > 0 H L H > 0, L < 0 H L *4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above * Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. * Case 3: Always OFF 8 E5CN/E5CN-U Characteristics Indication accuracy Influence of temperature *2 Influence of voltage *2 Thermocouple: *1 Terminal block models (E5CN): (0.3% of indicated value or 1C, whichever is greater) 1 digit max. Plug-in models (E5CN-U): (1% of indicated value or 2C, whichever is greater) 1 digit max. Platinum resistance thermometer input: Terminal block models (E5CN) and plug-in models (E5CN-U): (0.2% of indicated value or 0.8C, whichever is greater) 1 digit max. Analog input: Terminal block models (E5CN) and plug-in models (E5CN-U): 0.2% FS 1 digit max. CT input: Terminal block models (E5CN): 5% FS 1 digit max. Thermocouple input (R, S, B, W, PL II): Terminal block models (E5CN): (1% of PV or 10C, whichever is greater) 1 digit max. Plug-in models (E5CN-U): (2% of PV or 10C, whichever is greater) 1 digit max. Other thermocouple input: *3 Terminal block models (E5CN): (1% of PV or 4C, whichever is greater) 1 digit max. Plug-in models (E5CN-U): (2% of PV or 4C, whichever is greater) 1 digit max. Platinum resistance thermometer input: Terminal block models (E5CN) and plug-in models (E5CN-U): (1% of PV or 2C, whichever is greater) 1 digit max. Analog input: Terminal block models (E5CN) and plug-in models (E5CN-U): (1%FS) 1 digit max. Input sampling period 250 ms Hysteresis Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4 Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS) Proportional band (P) Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4 Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 3999 s (in units of 1 s) Derivative time (D) 0 to 3999 s (in units of 1 s) *5 Control period 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Affect of signal source resistance Thermocouple: 0.1C/ max. (100 max.) Platinum resistance thermometer: 0.1C/ max. (10 max.) Insulation resistance 20 M min. (at 500 VDC) Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration resistance Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Shock resistance Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Destruction 300 m/s2, 3 times each in X, Y, and Z directions E5CN Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g E5CN-U Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g E5CN Front panel: IP66, Rear case: IP20, Terminals: IP00 Weight Degree of protection E5CN-U Front panel: IP50, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Setup Tool port Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN. *6 Standards EMC Approved standards *7 UL 61010-1, CSA C22.2 No. 1010-1, KOSHA certified (some models) *8 Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *9 EMI: EN 61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 *1. The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U and L thermocouples at any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800C range is 3C max. The indication accuracy of the R and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is 0.3 of PV or 3C, whichever is greater, 1 digit max. The indication accuracy of PL II thermocouples is 0.3 of PV or 2C, whichever is greater, 1 digit max. *2. Ambient temperature: -10C to 23C to 55C, Voltage range: -15% to 10% of rated voltage *3. K thermocouple at -100C max.: 10 max. *4. "EU" stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is C or F. *5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s). *6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time. *7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11 is not certified for UL listing. *8. Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html *9. Refer to information on maritime standards in Safety Precautions for E5@N/E5@N-H for compliance with Lloyd's Standards. 9 E5CN/E5CN-U USB-Serial Conversion Cable Current Transformer (Order Separately) Ratings Applicable OS Windows XP/Vista/7/8 Applicable software CX-Thermo version 4 or higher Dielectric strength Applicable models E5AN/E5EN/E5CN/E5CN-U/E5AN-H/ E5EN-H/E5CN-H/E5GN Vibration resistance 50 Hz, 98 m/s2 USB interface standard Conforms to USB Specification 1.1. 1,000 VAC for 1 min Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) Power supply Bus power (Supplied from USB host controller.) Power supply voltage 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55C (with no condensation or icing) Ambient operating humidity 10% to 80% Input current indication accuracy 5% FS 1 digit max. Storage temperature -20 to 60C (with no condensation or icing) Heater burnout alarm setting range *1 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms Storage humidity 10% to 80% Altitude 2,000 m max. SSR failure alarm setting range *2 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms Communications Specifications Transmission line RS-485: Multipoint connection method Communications RS-485 (two-wire, half duplex) Synchronization method Start-stop synchronization Protocol CompoWay/F, SYSWAY, or Modbus Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps Transmission code ASCII Data bit length * 7 or 8 bits Stop bit length * 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485 Retry function None Communications buffer 217 bytes Communications 0 to 99 ms response wait time Default: 20 ms * The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. Models with detection for single-phase heaters: One input Models with detection for single-phase or three-phase heaters: Two inputs CT input (for heater current detection) Maximum heater current 50 A AC Heater overcurrent 0.1 to 49.9 A (in units of 0.1 A) alarm setting range *3 Minimum detection ON time: 100 ms *1. For heater burnout alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2. For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3. For heater overcurrent alarms, the heater current will be measured when the control output is ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) Life (x 104 operations) Weight Approx. 100 g Note: A driver must be installed in the personal computer. Refer to installation information in the operation manual for the Conversion Cable. Heater Burnout Alarms, SSR Failure Alarms, and Heater Overcurrent Alarms 500 300 100 50 30 10 5 E5CN 250 VAC, 30 VDC (resistive load) cos = 1 3 1 0 1 2 3 4 5 6 Switching current (A) Note: Do not connect a DC load to a Controller with a Long-life Relay Output. 10 E5CN/E5CN-U External Connections * A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current.) * Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose. E5CN Controllers Control output 1 Long-life relay output 250 VAC, 3 A (resistive load) Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Current output 0 to 20 mA DC 4 to 20 mA DC Load: 600 max. The E5@N-@@@T@ is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Auxiliary outputs (relay outputs) 250 VAC, 3 A (resistive load) Auxiliary outputs (relay outputs) Control output 1 Control output 2 Voltage output (for driving SSR) 12 VDC, 21 mA DO NOT USE mA Auxiliary output 2 Auxiliary output 1 A DO NOT USE B V Analog input A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. Input power supply B DO NOT USE * 100 to 240 VAC * 24 VAC/VDC (no polarity) TC/Pt universal input Option Units E53-CNHH03N2 Communications (RS-485) and CT2 B(+) E53-CNHBN2 Event inputs and CT 11 11 B(+) 12 12 RS-485 RS-485 A(-) 13 CT2 E53-CNQ03N2 Communications (RS-485) and Control Output 2 EV1 13 EV2 14 CT1 14 15 Control output 2 + - E53-CN03N2 Communications (RS-485) E53-CNH03N2 Communications (RS-485) and CT B(+) B(+) 11 RS-485 A(-) DO NOT USE 12 13 14 15 E53-CNBN2 Event inputs 11 13 14 CT1 15 A(-) - 13 DO NOT USE - 15 E53-CNQHN2 Control Output 2 and CT + 12 14 15 EV1 EV2 DO NOT USE DO NOT USE 11 12 - 12 13 DO NOT USE 13 14 14 12 A(-) DO NOT USE 13 11 12 13 + 14 External 12 VDC, power supply 20 mA 14 CT1 - + 15 E53-CNQBN2 Event Inputs and Control Output 2 E53-CNQHHN2 Control Output 2 and CT2 11 11 Control output 2 - 12 EV1 13 CT2 EV2 + 14 CT1 CT1 15 B(+) RS-485 15 Control output 2 13 DO NOT USE DO NOT USE DO NOT USE EV2 + 12 14 12 VDC, External power supply 20 mA 11 RS-485 12 EV1 E53-CNP03N2 Communications (RS-485) and External Power Supply E53-CNPHN2 External Power Supply and CT External + 11 12 VDC, power supply 20 mA 11 11 DO NOT USE CT1 15 A(-) E53-CNPBN2 Event Inputs and External Power Supply 13 14 Control output 2 15 15 12 - 15 E5CN-U The E5@N-@@@T@ is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Control output 1 Relay output (three terminals used) SPDT, 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Current output 4 to 20 mA DC 0 to 20 mA DC Load: 600 W max. Auxiliary output 250 VAC, 3 A (resistive load) (Relay outputs) Control output 1 DO NOT USE mA DO NOT USE A Auxiliary output 1 Auxiliary output 2 (Control output (cooling side)) An input error is sent to the output to which the alarm 1 function is assigned. B V DO NOT USE Analog input B TC/Pt universal input Input power supply * 100 to 240 VAC * 24 VAC/VDC (no polarity) Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately. 11 E5CN/E5CN-U Isolation/Insulation Block Diagrams E5CN E5CN-U Input/Q output (OUT1) Input/CT input/Q output (OUT1, 2) C output Communications/event inputs Power supply External power supply Power supply R output C output Y output Auxiliary output 1, 2 R output Y output : Reinforced insulation : Functional insulation Auxiliary output 1, 2 : Reinforced insulation : Functional insulation Nomenclature E5CN E5CN-U Temperature unit The front panel is the same for the E5CN and E5CN-U. No.1 display Operation indicators No. 2 display Up Key Level Key Mode Key Down Key Dimensions (Unit: mm) E5CN Terminal Models 91 6 48 x 48 Panel Cutout Mounted Separately Group Mounted (48 x number of units - 2.5) 78 +1.0 0 1.5 +0.6 0 45 44.8 x 44.8 48.8 58 Group mounting does not allow waterproofing. 60 min. +0.6 0 45 Waterproof Mounting Adapter Packing (Accessory) (Accessory) Terminal Cover (E53-COV17) (Accessory) +0.6 0 45 Note: The terminal block cannot be removed. E5CN-U Plug-in Models 6 48 x 48 (84.7) 70.5 * Recommended panel thickness is 1 to 5 mm. * Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) * To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. * When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Panel Cutout Mounted Separately Group Mounted 14.2 (48 x number of units - 2.5) +1.0 0 +0.6 0 45 44.8 x 44.8 58 60 min. +0.6 45 0 Mounting Adapter (Accessory) 45 +0.6 0 * Recommended panel thickness is 1 to 5 mm. * Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) * When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. 12 E5CN/E5CN-U Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 (2,100) LED indicator (SD) 250 USB connector (type A plug) LED indicator (RD) Terminal Cover Waterproof Packing E53-COV17 Y92S-29 (for DIN 48 x 48) Note: The E53-COV10 cannot be used. 48 48.8 22 1,765 Serial connector Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. 9.1 13 E5CN/E5CN-U Current Transformers E54-CT1 21 15 E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) 2.8 5.8 dia. Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 4002 Winding resistance: 182 7.5 3 Output voltage (Eo) V (r.m.s.) 25 10.5 40 Two, 3.5 dia. 10 30 100 V 50 Hz 10 Distortion factor 10% 1 k 1 3% 1% 100 mV 100 10 E54-CT3 RL = 10 1 2.36 dia. 30 12 dia. 100 V 9 10 1 10 100 mA 1 Two, M3 (depth: 4) E54-CT3 Accessory Connection Example Armature Plug Lead 18 * Plug E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Output voltage (Eo) V (r.m.s.) 30 Approx. 3 dia. 100 1,000 A Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for the Temperature Controller is 50 A.) Number of windings: 4002 Winding resistance: 80.8 15 * Armature 10 Thru-current (Io) A (r.m.s.) 40 x 40 100 V 50 Hz Distortion factor 10% 3% 1% 10 1 k 500 1 100 mV 100 50 10 RL = 10 1 100 V Approx. 6 dia. (22) 10 1 10 100 mA 1 10 100 1,000 A Thru-current (Io) A (r.m.s.) 14 E5CN/E5CN-U Adapter Y92F-45 Note: 1. Note: 1. Use this Adapter when the panel has already been prepared for the E5B@. 2. The Adapter is available only in black. Fixture (Accessory) 76 4.7 69.6 to 77.6 72 x 72 67 x 67 87 Mounted to E5CN Panel (1 to 8 mm) 72 x 72 48 x 48 2.2 4.7 77.3 (to back of E5CN) DIN Track Mounting Adapter Y92F-52 Note: This Adapter cannot be used together with the Terminal Cover. Remove the Terminal Cover to use the Adapter. 61 3.5 38 50 Mounted to E5CN 48 100.5 15 E5CN/E5CN-U E5CN-U Wiring Socket Front-connecting Socket Eleven, M3.5 x 7.5 P2CF-11 sems screws 3 Terminal Layout/Internal Connections (Top View) 4.5 7.8 8 7 6 5 Mounting Holes 4 Two, 4.5 dia. mounting holes 35.4 70 max. Two, 4.5-dia. holes 4 9 3 10 11 1 2 400.2 Note: Can also be mounted to a DIN track. 50 max. 31.2 max. Note: A model with finger protection (P2CF-11-E) is also available. Back-connecting Socket P3GA-11 27 dia. 4 7 3 Terminal Layout/Internal Connections (Bottom View) 5 6 7 8 4 45 25.6 3 9 2 1 11 10 45 4.5 16.3 6.2 6 8.7 Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets. 2. A Protective Cover for finger protection (Y92A-48G) is also available. 16 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obligation hereunder shall be, at Omron's election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron's analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user's programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron's test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron's Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron's representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2014.4 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2014 All Right Reserved. Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Omron: E5CN-CML-500 AC100-240 E5CN-C2LU AC100-240 E5CN-RMTD-500 AC/DC24 E5CN-QTDU AC/DC24 E5CNQ2MT-W-500 AC100-240 E5CN-QMT-W-500 AC100-240 E5CN-R2MTD-W-500 AC/DC24 E5CN-CTDU AC/DC24 E5CN-C1LU AC100-240 E5CN-C2MTD-W-500 AC/DC24 E5CN-Q2LU AC100-240 E5CN-C2MT-W-500 AC100-240 E5CN-Y2MT-500 AC100-240 E5CN-Y2ML-500 AC100-240 E5CN-C2ML-500 AC100-240 E5CN-R2LU AC100-240 E5CN-C2TDU AC/DC24 E5CN-CTU AC100-240 E5CN-RTDU AC/DC24 E5CN-Q2TDU AC/DC24 E5CN-R2ML-500 AC100-240 E5CN-Q1TDU AC/DC24 E5CN-Q1LU AC100-240 E5CN-Y2MT-W-500 AC100-240 E5CN-C1TDU AC/DC24 E5CN-Y2ML-500 AC100-240-N5 E5CN-CMT-W-500 AC100-240 E5CN-QML-500 AC100-240 E5CN-R1LU AC100-240 E5CN-C2MTD-500 AC/DC24 E5CN-Q2MLD-500 AC/DC24 E5CN-CMTD-500 AC/DC24 E5CN-C2TU AC100-240 E5CN-R2MLD-500 AC/DC24 E5CN-C1TU AC100-240 E5CN-RML-500 AC100-240 E5CN-Q2MTD-W-500 AC/DC24 E5CN-R1TDU AC/DC24