1302 Dimensions are shown for
reference purposes only. Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
P&B
Catalog 1308242
Issued 3-03
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
CS series
Solid State Hybrid Voltage Sensor
Close differential
Choice of two types
– Fixed pick-up and knob adjustable drop-out
– Knob adjustable pick-up and drop-out
Internal 2 Form C (DPDT) output relay
File E22575
File LR15734
Wiring Diagrams – Bottom Views
(pins numbered clockwise from keyway)
Note 1 – As voltage increases, the
relay will pick-up at its selected
point and remain energized while
voltage is maintained at that level or
higher.
Note 2 – As voltage decreases, af-
ter pick-up, the relay will drop-out at
its selected point.
Note 3 – Minimum hysterisis, the
voltage differential between pick-up
and drop-out, is typically 2% of
pick-up.
Fixed Pick-up and Adjustable Pick-up
Adjustable Drop-out and Drop-out
AC
INPUT DC
INPUT -
+
Sensing Modes
The CS can be used as an over or undervoltage sensor, depending upon
whether the load is connected to the normally closed (NC) or normally open
(NO) contacts of the sensors output relay.
Overvoltage sensor The NC contacts are used. The relay remains de-
energized until an overvoltage is sensed.
Undervoltage sensor The NO contacts are used. The relay remains en-
ergized until the voltage decreases to the preset level, where the sensor
de-energizes the relay.
Adjustable Voltage Sensor Operation
HYSTERISIS
2 VOLTS
RELAY
ENERGIZED
RELAY
DE-ENERGIZED
VOLTAGE
NOTE 1 NOTE 2
Outline Dimensions
Ordering Information –
Distributors are more likely to stock boldface items.
Fixed Pick-Up and Adjustable Drop-Out
Part Number Pick-Up Drop-Out Range Maximum
(Volts) (Volts) Voltage
CSJ-38-71010 105 90-103 140VAC (50/60 Hz.)
CSL-38-31010 22 16-21 32VDC
Adjustable Pick-Up and Adjustable Drop-Out
Part Number Pick-Up Range Drop-Out Range* Maximum
(Volts) (Volts) Voltage
CSJ-38-70010 92-140 90-138 150VAC (50/60 Hz.)
CSL-38-30010 20-30 18-28 32VDC
CSL-38-40010 40-58 38-56 60VDC
CSL-38-60010 92-140 90-138 150VDC
* Actual maximum drop-out voltage is the selected pick-up voltage less the hysterisis
voltage.
Engineering Data
Power Requirement: Typically less than 3VA or 3W.
Duty Cycle: Continuous.
Repeatability: ±1%, max.
Response Time: 10-25 ms, typ.
Internal Relay Contact Arrangement: 2 Form C (DPDT).
Internal Relay Contact Rating: 10A @ 28VDC , res., or 120VAC, 80% p.f.
Reverse Polarity Protection: On DC types.
Temperature Range: -10°C to +55°C.
Temperature Coefficient: 0.2%/°C, max.
Enclosure: Plastic dust cover.
Mounting: 8-pin octal style plug. Fits either 27E122 or 27E891 (snap-on)
screw terminal sockets.
Weight: 8 oz. (227g) approximately.
.600 MAX.
(15.24)
2.937 MAX.
(76.60) .560
(14.22)
2.406 MAX.
(61.11)
1.781 MAX.
(42.24)
.875
(22.23)
1.187
(30.15)
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.