42
PM4H-A/S/M
Operation mode
PM4H-A
Note: Keep 0.1s or more for power off time.
Keep 0.05s or more for start, stop, reset input time.
Operation type Explanation Time chart
• If using a time-limit start when the power is turned on, and a reset when
the power is turned off, pins 2 to 6 (screw-tightening pins x and c)
should be shorted ahead of time.
• Turn the operation mode selector switch to the position.
If pins 2 to 6 (screw-tightening pins x and c) are shorted (the start input
is turned on) with the power supply on, the output will go on after the set
time has elapsed.
If the power supply is turned off, or pins 2 to 7 (screw-tightening pins x to
v) are shorted (the reset input is turned on), a reset is carried out.
Note) During time-limited operation, the time-limited operation is stopped
while the pins 2 to 5 (screw-tightening pins x to b) are being shorted
(the stop input is on). When the pins are released, time-limited operation
resumes.
• Turn the operation mode selector switch to the position.
When pins 2 to 6 (screw-tightening pins x and c) are shorted (the start
input is turned on) with the power supply on, the output goes on, and when
pins 2 to 6 (screw-tightening pins x and c) are released (the start input
is turned off), the time limit interval begins. After the set time has elapsed,
the output goes off. If start input is entered at any point during the time limit
interval, the time limit interval is reset.
Note) During time-limited operation, the time-limited operation is stopped
while the pins 2 to 5 (screw-tightening pins x to b) are being shorted
(the stop input is on). When the pins are released, time-limited operation
resumes.
• Turn the operation mode selector switch to the position.
When pins 2 to 6 (screw-tightening pins x and c) are shorted (the start
input is turned on) with the power supply on, the output goes on, and after
the set time has elapsed, it goes off.
Also, when pins 2 to 6 are released (the start input goes off), the output
goes on, and after the set time has elapsed, it goes off.
If the status of pins 2 to 6 (screw-tightening pins x and c) changes dur-
ing the time-limit interval (the start input goes from on to off, or from off to
on), the time-limit interval is restarted from the point at which the change
took place.
If the power supply is turned off, or pins 2 to 7 (screw-tightening pins x to
v) are shorted (the reset input is turned on), a reset is carried out.
Note) During time-limited operation, the time-limited operation is stopped while
the pins 2 to 5 (screw-tightening pins x to b) are being shorted (the stop
input is on). When the pins are released, time-limited operation resumes.
• If using a time-limit start when the power is turned on, and a reset when
the power is turned off, pins 2 to 6 (screw-tightening pins x and c)
should be shorted ahead of time.
• Turn the operation mode selector switch to the position.
When pins 2 to 6 (screw-tightening pins x and c) are shorted (the start
input is turned on) with the power supply on, the output goes on, and after
the set time has elapsed, it goes off. This process is subsequently repeated.
If the power supply is turned off, or pins 2 to 7 (screw-tightening pins x to
v) are shorted (the reset input is turned on), a reset is carried out.
Note) During time-limited operation, the time-limited operation is stopped
while the pins 2 to 5 (screw-tightening pins x to b) are being shorted
(the stop input is on). When the pins are released, time-limited operation
resumes.
• If using a time-limit start when the power is turned on, and a reset when
the power is turned off, pins 2 to 6 (screw-tightening pins x and c)
should be shorted ahead of time.
• Turn the operation mode selector switch to the position.
When pins 2 to 6 (screw-tightening pins x and c) are shorted (the start
input is turned on) with the power supply on, the limited time interval begins,
and the output goes on after the set time has elapsed. After the output has
gone on, it goes off when the set time has elapsed, and this process is sub-
sequently repeated.
If the power supply is turned off, or pins 2 to 7 (screw-tightening pins x to
v) are shorted (the reset input is turned on), a reset is carried out.
Note) During time-limited operation, the time-limited operation is stopped
while the pins 2 to 5 (screw-tightening pins x to b) are being shorted
(the stop input is on). When the pins are released, time-limited operation
resumes.
Pulse
ON-delay
ON
ON
Pulse
Flicker
FL
FL
Pulse
ON-flicker
FO
FO
Differential
ON/OFF-delay (1)
OF1
OF1
Signal
OFF-delay
SF
SF
Power supply
ON
OFF
Start
ON
OFF
ON ON
OFF
Reset
ON
OFF
Stop
ON
OFF
Time out (N.O. contact)
OP. LED
POWER LED
0–4
0–5
0–3
ON
Tt
1t2
ON
OFFOFF
Note: LED lighting or No LED lighting
Power supply
ON
OFF
Start
ON
OFF
ON
OFF
ON
OFF
OFF
Reset
ON
Stop
ON
OFF
Time out (N.O. contact)
OP. LED
POWER LED
0–4
0–5
0–3
ON
TT t
1tat2tb
ON
OFFOFF
Note: LED lighting or No LED lighting
Power supply
ON
OFF
Start
ON
OFF
ON
OFF
ON
OFF
OFF
Reset
ON
Stop
ON
OFF
Time out (N.O. contact)
OP. LED
POWER LED
0–4
0–5
0–3
ON
TT t
2Ttatbt1
OFFOFF
Power supply
ON
OFF
Start
ON
OFF
ON
OFF
ON
Reset
Stop
ON
OFF
Time out (N.O. contact)
OP. LED
POWER LED
0–4
0–5
0–3
ON ON
Tt
1t2tatb
OFF OFF
ON
OFF
Restart
OFF
Note: LED lighting or No LED lighting
Power supply
ON
OFF
Start
ON
OFF
ON
OFF
ON
OFF
ON
Reset
Stop
Time out (N.O. contact)
OP. LED
POWER LED
0–4
0–5
0–3
ON
Tt
bta
OFF
OFF
Note: LED lighting or No LED lighting
LED lighting LED flickering
T: Setting time t1, t2, ta, tb<T t1+t2=T
´
¶
´
¶
Analog