1000Vdc XL Style Photovoltaic Fuses
63 to 630 Amps, 01XL, 1XL, 2XL and 3L Body Sizes
1211 BU-SB111362 Page 1 of 5 Data Sheet 2156
01XL, 1XL, 2XL and 3L Sizes
Catalogue Symbols: 1000Vdc Bladed: PV-(amp rating)A(size)XL
1000Vdc Bolted: PV-(amp rating)A(size)XL-B
Description: A range of XL package fuse links specifically designed for
protecting and isolating photo voltaic array combiners and disconnects.
These fuse links are capable of interrupting low overcurrents associated with
faulted PV systems (reverse current, multi-array fault).
Part Number/Style Body Current Energy Integrals I2t (A2s) Watts Loss
Bladed Bolted Size Rating (Amps) Volts Pre-Arcing Total @ 1000V 0.8InIn
PV-63A-01XL PV-63A-01XL-B 63 350 2520 12 24
PV-80A-01XL PV-80A-01XL-B 80 660 4752 14 27
PV-100A-01XL PV-100A-01XL-B 01 100 1000Vdc 1350 9720 15 30
PV-125A-01XL PV-125A-01XL-B 125 1930 13,896 20 40
PV-160A-01XL PV-160A-01XL-B 160 3900 28,080 25 44
PV-200A-1XL PV-200A-1XL-B 1 200 1000Vdc 9400 27,260 31 60
PV-160A-2XL PV-160A-2XL-B 160 2780 21,000 25 44
PV-200A-2XL PV-200A-2XL-B 200 4152 31,000 29 62
PV-250A-2XL PV-250A-2XL-B 2 250 1000Vdc 7721 57,000 35 70
PV-315A-2XL PV-315A-2XL-B 315 17,600 130,000 40 75
PV-355A-2XL PV-355A-2XL-B 355 26000 192,000 42 68
PV-350A-3L PV-350A-3L-B 350 30,885 160,700 41 90
PV-400A-3L PV-400A-3L-B 3400 1000Vdc 44,000 230,000 63 100
PV-500A-3L PV-500A-3L-B 500 48,300 251,200 71 138
PV-630A-3L PV-630A-3L-B 630 100,000 520,000 92 180
Class of Operation: gPV and UL PV fuse links
Fuse Sizes: 01XL, 1XL, 2XL and 3L
Ratings:
Volts - 1000Vdc
Amps - 63 to 630A:
IR - 50kA @ 63 to 160A
- 33kA @ 200 to 315A
- 50kA @ 350 to 630A
Time Constant: 1-3ms
Agency Information: - IEC 60269-6
- RoHS compliant
- UL 2579 (pending)
- CCC (pending)
Recomended Fuse Holders
SD1XL-S (suitable for 01 and 1XL)
SD2XL-S (suitable for 2XL)
SD3L-S (suitable for 3L)
43
43
58,3
Adapter
150,3
164,3
10,4
20,0
127,8
187,6
6,0
43
43
21.3
40.4
Top indicator
127.8
193.8
124.6 128.6
20
7.9
5.8
59,2
59,2
74,49
Top indicator
10,5
154,8
167,8
25
128,5
191,3
6,0
59.2
20
47.9
59.2
Top indicator
204.5
128.5
123.3
119.3
26
14.38
5.80
1211 BU-SB111362 Page 2 of 5 Data Sheet 2156
1XL Blade Size 1XL Bolt Size
51
51
39.8
20
Top indicator
189.8
127.8
123.6
119.6
20
13.4
5.8 51
51
66,3
Adapter
6
146,3
160,3
10,4
20
127,8
183,6
2XL Blade Size 2XL Bolt Size
Dimensions - mm (not to scale)
3L Blade Size 3L Bolt Size
22.025
60
73.5
73.5
Top indicator
127.5204.9 118.3 122.3
32.3
18.7
6
73,5
73,5
88,8
Adapter
128,5
199,7 169,7
10,5
30
6,0
01XL Blade Size 01XL Bolt Size
1211 BU-SB111362 Page 3 of 5 Data Sheet 2156
100
1000
10000
160A
125A
100A
80A
63A
200A
0.01
0.1
1
10
100
00001000100101
Pre-arcing Time (s)
80A
63A
Time Current Curves for 01XL and 1XL
Available Current (Amps), DC-Time Constant 1-3ms
1211 BU-SB111362 Page 4 of 5 Data Sheet 2156
100
1000
10000
200A
315A
250A
355A
160A
0.01
0.1
1
10
100
00001000100101
Pre-arcing Time (s)
Time Current Curves for 2XL
Available Current (Amps), DC-Time Constant 1-3ms
© 2011 Cooper Bussmann
www.cooperbussmann.com
1211 BU-SB111362 Page 5 of 5 Data Sheet 2156
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
100
1000
10000
630A
400A
500A
350A
0.01
0.1
1
10
100
0000
1
0001
0
0101
Pre-arcing Time (s)
Time Current Curves for 3L
Available Current (Amps), DC-Time Constant 1-3ms