23-04-09 SB-SB09366 Form No.NH500V Page 1 of 9 Data Sheet 2142
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 2 to 1250 Amps, Sizes 000 to 4
Dimensions - mm
Standards/Approvals
lIEC 60269, VDE 0636, DIN 43620 Part 1 and 3
Description Asquare bodied range of industrial fuse
links for a wide variety of applications.
Packaging All fuse links are packed in 3’s, except
size 4 packed individually.
Technical Data
lSize: 000 to 4
lRated voltage: 500Vac/250Vdc
lAmps: 2 to 1250A
lRated breaking capacity: 120kA
lOperating frequency: 45-62Hz
lDesign - Steatite insulator
-Corrosion-resistant aluminium end plates
-Corrosion-resistant plated steel screws
lContact blade: Full contact silver plated brass blades
Environmental
l100% recyclable (including packaging)
lRoHS compliant
lCadmium and lead free for sizes 000 to 4
Features
lReliable dual indicator system
lAvailable with or without insulated metal gripping lugs
Catalogue Symbol
lWith metal gripping lugs: (amp)NHG(Size)B
lWith insulated metal gripping lugs: (amp)NHG(Size)BI
Operation Class: gG/gL
Fuse Holders
lFuse bases: SB*-D single-pole, TB*-D three-pole
lFuse rails - vertical: BFR
lFuse switch disconnectors vertical: BFD
lFuse switch disconnectors horizontal: BFH
*Select requiredsize of fuse base
Size a1a2(max) a3a4bc1c2de1(max) e2(max) e3(max) e4f (max)
000 78.5±1.5 54 45±1.5 49±1.5 15 35 10 2±0.5 41 21 16 6 8
00 78.5±1.5 54 45±1.5 49±1.5 15 35 11 2±0.5 48 30 25 6 15
0 125±2.5 68 62+3/-1.5 68+1.5/-3 15 35 11 2.5±0.5 48 30 25 6 15
01 135±2.5 75 62±2.5 68±2.5 15 40 112.5±0.5 48 30 25 6 15
1 135±2.5 75 62±2.5 68±2.5 20 40 112.5±0.5 53 52 25 6 15
02 150±2.5 75 62±2.5 68±2.5 20 48 112.5±0.5 53 52 25 6 15
2 150±2.5 75 62±2.5 68±2.5 25 48 11 2.5±0.5 61 60 25 6 15
03 150±2.5 75 62±2.5 68±2.5 25 60 11 2.5±0.5 61 60 25 6 15
3 150±2.5 75 62±2.5 68±2.5 32 60 11 3±0.5 75 70 25 6 18
4 200 84 80 90 50 85 10 3 102 87 - 8 30
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 2 to 100 Amps, Size 000
Size 000 Technical Data
Size 000 Time-Current Characteristics
10 000
100
C
6
10
82 648 24
1000
68 2
0.01
TIME (Seconds)
0.1
10
100
1000
6
2
4
2
4
6
4
2
6
6
1
2
4
6
4
6
2
4
2
16
10
20
35
25
32
80
50
40
63
100
4
2
6
2
4
CURRENT (Amps)
23-04-09 SB-SB09366 Form No.NH500V Page 2 of 9 Data Sheet 2142
Part Numbers with
Metal Gripping Lugs
Part Numbers with
Insulated Metal
Gripping Lugs Amp Rating
I2t(Amps2Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x In
@500Vac
*I1120kA
@500Vac
2NHG000B 2NHG000BI 2 4 - 6 3.9
0.13 kg
4NHG000B 4NHG000BI 4 6 - 12 1.8
6NHG000B 6NHG000BI 6 14 - 21 2.0
10NHG000B 10NHG000BI 10 58 290 252 1.5
16NHG000B 16NHG000BI 16 234 1170 1000 2.3
20NHG000B 20NHG000BI 20 584 3000 2400 2.2
25NHG000B 25NHG000BI 25 1000 4600 3700 2.8
32NHG000B 32NHG000BI 32 2400 11800 9400 3.7
35NHG000B 35NHG000BI 35 2400 11800 9400 3.7
40NHG000B 40NHG000BI 40 3300 16500 13200 4.0
50NHG000B 50NHG000BI 50 5600 27800 16700 4.9
63NHG000B 63NHG000BI 63 6300 24900 18700 4.6
80NHG000B 80NHG000BI 80 9800 38900 29200 6.3
100NHG000B 100NHG000BI 100 18100 72300 54300 7.4
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirement.
Dimensions - mm
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 125 & 160 Amps, Size 00
Size 00 Technical Data
Size 00 Time-Current Characteristics
100
6
10
82 648 24
1000
68 2 4
160
125
10 000
0.01
2
4
6
TIME (Seconds)
6
0.1
2
4
1
2
4
4
10
6
2
100
6
2
2
1000
4
6
6
4
6
CURRENT (Amps)
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
23-04-09 SB-SB09366 Form No.NH500V Page 3 of 9 Data Sheet 2142
Part Numbers with
Metal Gripping Lugs
Part Numbers with
Insulated Metal
Gripping Lugs Amp Rating
I2t(Amps2Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x In
@500Vac
*I1120kA
@500Vac
125NHG00B 125NHG00BI 125 25000 125000 80000 11.2
0.190 kg
160NHG00B 160NHG00BI 160 62000 310000 204600 11.2
Dimensions - mm
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 10 to 160 Amps, Size 0
Size 0 Technical Data
Size 0 Time-Current Characteristics
23-04-09 SB-SB09366 Form No.NH500V Page 4 of 9 Data Sheet 2142
Part
Number
Amp
Rating
I2t (Amps2Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x In
@500Vac
*I1120kA
@ 500Vac
10NHG0B 10 58 290 240 2.0
0.26kg
16NHG0B 16 240 1200 1000 3.0
20NHG0B 20 490 2500 2000 3.6
25NHG0B 25 1200 5600 4500 4.0
32NHG0B 32 1800 9000 7200 5.1
35NHG0B 35 2400 11800 9400 5.2
40NHG0B 40 3300 16500 13200 5.6
50NHG0B 50 5600 22300 16700 7.0
63NHG0B 63 6600 26100 19600 7.0
80NHG0B 80 9800 38900 29200 7.9
100NHG0B 100 20600 82300 61700 9.2
125NHG0B 125 25000 125000 72500 13.1
160NHG0B 160 62000 310000 179800 14.1
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
Dimensions - mm
TIME (Seconds)
6842682648 246
10 100 1000
2
6
4
0.1
0.01
1
6
4
2
6
2
4
10
100
6
4
2
6
4
2
6
4
2
1000
10 000
32
35
40
50
63
80
100
125
160
16
10
20
25
250
224
200
CURRENT (Amps)
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 10 to 250 Amps, Sizes 01 & 1
Sizes 01 & 1 Technical Data
Sizes 01 & 1 Time-Current Characteristics
TIME (Seconds)
6842682648 246
10 100 1000
2
6
4
0.1
0.01
1
6
4
2
6
2
4
10
100
6
4
2
6
4
2
6
4
2
1000
10 000
32
35
40
50
63
80
100
125
160
16
10
20
25
250
224
200
CURRENT (Amps)
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
23-04-09 SB-SB09366 Form No.NH500V Page 5 of 9 Data Sheet 2142
Part Numbers with
Metal Gripping Lugs
Part Numbers with
Insulated Metal
Gripping Lugs
Amp Rating
I2t(Amps2Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x In
@500Vac
*I1120kA
@500Vac
10NHG01B 10NHG01BI 10 58 300 300 2.0
0.270kg
16NHG01B 16NHG01BI 16 240 1200 1000 3.0
20NHG01B 20NHG01BI 20 490 2500 2000 3.6
25NHG01B 25NHG01BI 25 1200 5600 4500 4.0
32NHG01B 32NHG01BI 32 1800 9000 7200 5.1
35NHG01B 35NHG01BI 35 2400 11800 9400 5.2
40NHG01B 40NHG01BI 40 3300 16500 13200 5.6
50NHG01B 50NHG01BI 50 5600 22300 16700 7.0
63NHG01B 63NHG01BI 63 6600 26100 19600 7.0
80NHG01B 80NHG01BI 80 9800 38900 29200 7.9
100NHG01B 100NHG01BI 100 20600 82300 61700 9.2
125NHG01B 125NHG01BI 125 25000 125000 72500 13.1
160NHG01B 160NHG01BI 160 62000 310000 179800 14.1
200NHG1B 200NHG1BI 200 97000 368600 291000 17.0
0.387kg
224NHG1B 224NHG1BI 224 124000 471200 372000 19.0
250NHG1B 250NHG1BI 250 151300 574900 453800 22.0
Dimensions - mm
Size 01 Size 1
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 35 to 400 Amps, Sizes 02 & 2
Sizes 02 & 2 Technical Data
100
C
68 2 648 24
1000
68 2
355
315
400
0.01
2
4
6
TIME (Seconds)
6
0.1
2
4
1
2
4
4
10
6
2
100
6
10000
2
2
1000
4
6
6
4
10 000
250
224
200
160
125
100
80
63
50
40
35
Sizes 02 & 2 Time-Current Characteristics
CURRENT (Amps)
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
23-04-09 SB-SB09366 Form No.NH500V Page 6 of 9 Data Sheet 2142
Part Numbers with
Metal Gripping Lugs
Part Numbers with
Insulated Metal
Gripping Lugs
Amp
Rating
I2t (Amps2Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x In
@ 500Vac
*I1120kA
@ 500Vac
35NHG02B 35NHG02BI 35 2400 11800 9400 4.7
0.402kg
40NHG02B 40NHG02BI 40 3300 16500 13200 5.2
50NHG02B 50NHG02BI 50 5600 22300 16700 7.0
63NHG02B 63NHG02BI 63 6600 26100 19600 7.0
80NHG02B 80NHG02BI 80 9800 38900 29200 8.2
100NHG02B 100NHG02BI 100 20600 82300 61700 9.5
125NHG02B 125NHG02BI 125 25000 100000 72500 12.5
160NHG02B 160NHG02BI 160 62000 248000 179800 13.3
200NHG02B 200NHG02BI 200 96900 367900 290500 18.0
224NHG02B 224NHG02BI 224 124000 472000 372000 20.0
250NHG02B 250NHG02BI 250 151300 574900 453800 23.0
315NHG2B 315NHG2BI 315 361700 1446500 940300 26.0
0.630kg
355NHG2B 355NHG2BI 355 446500 1785800 1160800 31.0
400NHG2B 400NHG2BI 400 642900 2571500 1671500 34.0
Dimensions - mm
Size 02 Size 2
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 250 to 630 Amps, Sizes 03 & 3
Sizes 03 & 3 Technical Data
Sizes 03 & 3 Time-Current Characteristics
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
23-04-09 SB-SB09366 Form No.NH500V Page 7 of 9 Data Sheet 2142
Part Numbers with
Metal Gripping Lugs
Part Numbers with
Insulated Metal
Gripping Lugs
Amp
Rating
I2t(Amps2Seconds) Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x In
@500Vac
*I1120kA
@500Vac
250NHG03B 250NHG03BI 250 160800 642900 417900 23.0
0.64kg
315NHG03B 315NHG03BI 315 361700 1446500 940300 26.0
355NHG03B 355NHG03BI 355 446500 1785800 1160800 30.0
400NHG03B 400NHG03BI 400 642900 2571500 1671500 35.0
500NHG3B 500NHG3BI 500 886000 3898400 2923800 37.0
1.050kg
630NHG3B 630NHG3BI 630 1590000 6996000 5406000 46.0
Dimensions - mm
Size 03 Size 3
CURRENT (Amps)
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 500 to 1250 Amps, Size 4
Size 4 Technical Data
Size 4 Time-Current Characteristics
CURRENT (Amps)
* I1is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
23-04-09 SB-SB09366 Form No.NH500V Page 8 of 9 Data Sheet 2142
Part Numbers with
Metal Gripping Lugs
Amp Rating
I2t (Amps2Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
*I1120kA
@ 500Vac
500NHG4G 500 800,000 3,850,000 37.0
2.2kg
630NHG4G 630 880,000 4,100,000 47.0
800NHG4G 800 1,500,000 6,480,000 68.0
1000NHG4G 1000 4,800,000 13,000,000 80.0
1250NHG4G 1250 7,000,000 18,000,000 108.0
Dimensions - mm
Size 4
NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 2 to 1250 Amps, Sizes 000 to 4
Sizes 000 to 3 Cut-Off Current Characteristics
Size 4 Cut-OffCurrent Characteristics
PROSPECTIVE CURRENT (SYM. RMS kA)
23-04-09 SB-SB09366 Form No.NH500V Page 9 of 9 Data Sheet 2142
CUT-OFF CURRENT (kA PEAK)
PROSPECTIVE CURRENT (SYM. RMS kA)