Up counters/Down
-
48 x 48
-
CTR48 Multicoloured LCD display (green
-
red) Part number 87621221
Counter, Tachometer, Chronometer, Multi-totalizer, Batch counter, Preselection totalizer
Maximum input frequency 40 k Hz
Simple parameter setting, configuration using text menus
Easy modification of presets
Scaling factor
5 A changeover relay and solid state output
Removable connectors
Backlit LCD display (orange) : 2 lines, 6 digits or multicoloured display (green-red)
IP 65 sealed panel
Option of locking the keypad, completely or partially (preset, programming)
Accessories for 72 x 72 or 55 x 55 cut-out, DIN rail adaptor
Part numbers
Specifications
Type
Functions
Preset
Voltages
87621221
Multicoloured LCD display (green
-
red)
Counter, Tachometer, Chronometer, Multi
-totalizer, Batch counter, Preselection
totalizer
2
10→30
VDC
Physical details and protection
Supply
10→30VDC/24VAC/90→260VAC
Relative humidity (no condensation)
EN 60068
-2-
30 40/93 % RLF
Altitude
0 < 2000 m
Certifications
UL
- cULus (pending) -
CE
Vibration resistance in 3 axes
10-
55 Hz/1 min/XYZ EN 60068
-2-
6 : 30 min. in each direction
Connection by screw terminals
Removable
Protection
Conforming to standard EN 60529 IP65 for panel/IP20 for connections
Front panel watertight seal
Temperature limits use (°C)
-
20→+65
Temperature limits stored (°C)
-
25→+75
Weight (g)
150
DC version
250 AC version
General characteristics
Reset to zero or to preset
On panel : if not locked during programming
Electrical : automatic, voltage or solid state (NPN or PNP depending on programming)
Minimum pulse time
Impulse counter : < 15 ms
Chronometer : 500
μ
s
Option to protect against reset from front panel
Scale factor (each input pulse is multiplied by this figure)
00,0001→99,9999
Scaling factor (each input impulse is divided by this
value)
01,0000→99,9999
Decimal point selectable for ease of reading
0
0,0
0,00
0,000
0,0000
0,00000
Sensor supply version AC
24 VDC
-20/+15 %
50 mA
Programming and current value backed up via EEPROM
memory
Service life 10 years
Operating characteristics
Functions
Preselection counter, Tachometer, Chronometer, Multi
-totalizer, Batch counters, Totalizer
Number of presets
1 or 2
Display
LCD with orange backlighting/Multicoloured LCD (green
-red)
Height digits (mm)
LCD 9
Display details
-999999→999999
Inputs specifications
Inputs
2 counter inputs
1 reset input, 1 gate input
Input modes
Dir : Directional
AS : up/dn
AA : up/up
PP : phase
PP2 : phase 2
PP4 : phase 4
Input type
Voltage or solid state
High level
8VDC→30VDC
Low level
0→2VDC
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Accessories
Solid state output characteristics
Maximum current
30 mA
Max. voltage
10→30VDCfortheDCversion
24 VDC
-20/+15 %
Relay output characteristics
Changeover relay
NO contact
Depending on version
Maximum current
5 A
Minimum current
10 mA
Maximum voltage
30 VDC / 250 VAC
Min. voltage
5 VAC/DC
Response time
< 13 ms
Mechanical life (operations)
20 x 106
Number of operations to 5 A
5 x 104
Output modes : maintained or pulsed
0.01→99.99s
Description
Code
Adaptor for 72 x 72 mm cut-out
26546842
Adaptor for 55 x 55 mm cut-out
26546846
DIN rail adaptor
26546841
Principles
N
o
Legend
Current value
Selected value
Chronometer display
Active output indication
Shows which value is displayed
Prog/mode button
Preset control buttons
Button required for programming parameters
Dimensions (mm)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
N
o
Legend
10.5 max.
Dimensions (mm)
26546842 - Adaptor for 72 x 72 mm cut-out
Dimensions (mm)
26546846 - Adaptor for 55 x 55 mm cut-out
Dimensions (mm)
Panel cut-out
Dimensions (mm)
26546841 - DIN rail adaptor
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Inp A : counter input
Inp B : count direction
rS0:Display0→Preset
rSP2:DisplayPreset→0
Inp A : Add. counter input 1
Inp B : Sub.. counter input 2
rS0:Display0→Preset
rSP2:DisplayPreset→0
Inp A : Add. counter input 1
Inp B : Sub.. counter input 2
rS0:Display0→Preset
Curves
Counter : dir
Curves
Counter : AS
Curves
Counter : AA
Curves
Counter : PP
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A 90° B
Inp A : Counter input
Counting on an edge
Inp B : Reversal of directionrS0:Display0→Preset
rSP2:DisplayPreset→0
A 90° B
Inp A : Counter input
Counting on a rising edge and on a falling edge
Inp B : Reversal of directionrS0:Display0→Preset
rSP2:DisplayPreset→0
A 90° B
Inp A : Counter input
Counting on a rising edge and on a
falling edge
Inp B : Counter input
Counting on a rising edge and on a falling edge, reversal of directionrS0:Display0→Preset
rSP2 :
DisplayPreset→0
Inp A : No function Inp B : On/Off
Cumulative time counting while B is active
Add:Display0→Preset
Sub:DisplayPreset→0
Curves
Counter : PP2
Curves
Counter : PP4
Curves
Chronometer : Start tcCb
Curves
Chronometer : Start tcCbb
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Inp A : No function Inp B : On/Off
Cumulative time counting
Add:Display0→Preset
Sub:DisplayPreset→0
Inp A : On
Inp B : Off
Cumulative time counting
Add:Display0→Preset
Sub:DisplayPreset→0
Inp A : No function Inp B : On/Off Individual time counting, automatic reset before each new countAdd:Display0→Preset
Sub:DisplayPreset→0
Inp A : No function Inp B : On/Off Individual time counting, automatic reset before each new countAdd:Display0→Preset
Sub:DisplayPreset→0
Curves
Chronometer : Start tcCAb
Curves
Chronometer : Start tcSb
Curves
Chronometer : Start tcSbb
Curves
Chronometer : Start tcSAb
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Inp A : On
Inp B : Off Individual time counting, automatic reset before each new countAdd:Display0→Preset
Sub:DisplayPreset→0
Inp A : No function
Inp B : No function
Time counting command via Reset (manual or electrical)
Add:Display0→Preset
Sub:DisplayPreset→0
The Gate input has a display memory function
Inp A : Frequency input
Inp B : No function
Inp A : Frequency input 1
Inp B : Frequency input 2
Formula : A
-
B
Curves
Chronometer : Start tcAuto
Curves
Tachometer : Start tA.A
Curves
Tachometer : Start tA.AS
Curves
Tachometer : Start tA.AA
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Inp A : Frequency input 1
Inp B : Frequency input 2
Formula : A + B
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
Curves
Tachometer : Start tA.PP
Curves
Output operation : OutoP rS0
Curves
Output operation : OutoP rSA0
Curves
Output operation : OutoP bCrSA0
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
Curves
Output operation : OutoP tCrSA0
Curves
Output operation : OutoP rSP2
Curves
Output operation : OutoP rSAP2
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
Curves
Output operation : OutoPbCrSA2
Curves
Output operation : OutoP tCrSA2
Curves
Output operation : OutoP bCrS0
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
Curves
Output operation : OutoP tCrS0
Curves
Output operation : OutoP MurS0 (AA)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
Curves
Output operation : OutoP bCrSP2
Curves
Output operation : OutoP tCrSP2
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
A 90° B Inp A : Frequency input 1 Inp B : Reversal of direction
Curves
Output operation : OutoP MurS0 (AS)
Connections
87621111 / 211
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Output : 5 A/250 VAC/AC : 24 VAC
N
o
Legend
Sensor voltage supply (* UB interconnected)
GND (0 VDC)
INP A (signal A input)
INP B (signal B input)
Reset (Reset input)
Gate input
Output 1
- 10-
30 VDC/30 mA
11-12-
13 : Output 1
14-15 : Supply
Connections
87621112 / 212
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Output : 5 A/250 VAC/AC : 90
260 VDC
N
o
Legend
Sensor voltage supply
GND (0 VDC)
INP A (signal A input)
INP B (signal B input)
Reset (Reset input)
Gate input
Output 1
-
24 VDC/30 mA
11-12-
13 : Output 1
14-15 : Supply
Connections
87621115 / 215
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Output : 5 A/250 VAC/AC : 24 VAC
N
o
Legend
Sensor voltage supply
GND (0 VDC)
INP A (signal A input)
INP B (signal B input)
Reset (Reset input)
Gate input
Output 1
-
24 VDC/30 mA
11-12-
13 : Output 1
14-15 : Supply
Connections
87621121 / 221
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Output : 5 A/250 VAC/DC : 10
30 VDC
N
o
Legend
Sensor voltage supply (* UB interconnected)
GND (0 VDC)
INP A (signal A input)
INP B (signal B input)
Reset (Reset input)
Gate input
Output 1 : 10
-
30 VDC/30 mA
Output 2 : 10
-
30 VDC/30 mA
9-
10 : Output 1
11-12-
13 : Output 2
14-15 : Supply
Connections
87621122 / 222
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Output : 5 A/250 VAC/AC : 90
260 DC
N
o
Legend
Sensor voltage supply
GND (0 VDC)
INP A (signal A input)
INP B (signal B input)
Reset (Reset input)
Gate input
Output 1 : 24 VDC/30 mA
Output 2 : 24 VDC/30 mA
9-
10 : Output 1
11-12-
13 : Output 2
14-15 : Supply
Connections
87621125 / 225
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Output : 5 A/250 VAC/AC : 90
260 VDC
N
o
Legend
Sensor voltage supply
GND (0 VDC)
INP A (signal A input)
INP B (signal B input)
Reset (Reset input)
Gate input
Output 1 : 24 VDC/30 mA
Output 2 : 24 VDC/30 mA
9-
10 : Output 1
11-12-
13 : Output 2
14-15 : Supply
Applications
Programming diagram
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
23/06/2014 www.crouzet.com
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Crouzet:
87621221