MODEL NUMBERS AC CONTROL A4812 A4825 A4850 A4875 A4890
DC CONTROL D4812 D4825 D4850 D4875 D4890
OUTPUT SPECIFICATIONS
➀
Operating Voltage (47-63 Hz) [Vrms] 80-530 80-530 80-530 80-530 80-530
Max. Load Current ➂[Arms] 12 25 50 75 90
Min. Load Current, [mArms] 40 40 40 40 40
Transient Overvoltage [Vpk] 800 800 800 800 800
Max. Surge Current, (16.6ms) [Apk] 140 250 625 1000 1200
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.7 1.7 1.7 1.7 1.7
Thermal Resistance Junction to Case (R θJC
) [˚C/W] 1.48 1.02 0.63 0.31 0.28
Maximum I2 t for Fusing, (8.3 msec.) [A 2sec] 81 260 1620 4150 6000
Max. Off-State Leakage Current @ Rated Voltage [mArms] 10 10 10 10 10
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] ➁500 500 500 500 500
Max. Turn-On Time 1/2 Cycle (DC Input), 10.0 msec (AC Input)
Max. Turn-Off Time 1/2 Cycle (DC Input), 40.0 msec (AC Input)
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5 0.5
INPUT SPECIFICATIONS ➀DC CONTROL AC CONTROL
(D PREFIX) (A PREFIX)
Control Voltage Range 3-32 Vdc 90-280 Vrms (60Hz)
Max. Reverse Voltage -32 Vdc ---
Max. Turn-On Voltage 3.0 Vdc 90 Vrms
Min. Turn-Off Voltage 1.0 Vdc 10 Vrms
Nominal Input Impedance See Note 60K Ohms
Typical Input Current 2.0 mA 2mA @ 120 Vrms, 4mA @ 240 Vrms
GENERAL NOTES
➀All parameters at 25˚C unless otherwise specified.
➁Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➂Heat sinking required, for derating curves see page 2.
➃
➄
Turn-on time for random turn-on versions
is 0.02 msec (DC Control Models).
Input circuitry incorporates active current limiter.
• Zero Voltage and Random
Turn-On Switching
• Panel Mount
• 800V Transient Capability
FastFax Document No.
SERIES A48/D48.
Rev. 111003
PAGE 1 OF 3
Featuring state-of-the-art Surface
Mount Technology, these SPST-NO
relays deliver proven reliability in the
most demanding applications.
Output consists of an SCR AC switch
and is available in zero-cross, random
turn-on (phase controllable) and ver-
sions with either AC or DC input (coil)
control.
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
© 2003 CRYDOM CORP, Specifications subject to change without notice.
• Internal Snubber
➃
➄
➄
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com
WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
S
e
r
i
e
s
A
48
,
D
48
12
-
90
A
m
p
•
480
V
ac
-
A
C
O
U
T
P
U
T