https://www.phoenixcontact.com/us/produkte/2835435
05.12.2012Page2/4
Signal isolator-PI-EX-ME-RPS-I/I-2835435
Technical data
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Stripping length 8 mm
Screw thread M3
Connection method Pluggable screw connection
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
General data
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Ambient temperature (operation) -20 °C ... 60 °C
Ambient temperature (storage/transport) -25 °C ... 80 °C
Permissible relative humidity (operation) < 75 % (annual average)
Permissible relative humidity (operation) < 95 % (30 days/year, no condensation)
Step response (10-90%) 2.2 ms
Status display Green LED (supply voltage)
Width 22.5 mm
Height 99 mm
Depth 114.5 mm
Inflammability class according to UL 94 V0
Standards/regulations NAMUR recommendation NE 21
Housing material Polyamide PA non-reinforced
Color green
Electrical isolation input / output / supply 375 V (Peak value, in acc. with EN 50020)
Line monitoring NE 21
Conformance CE-compliant
ATEX II (1)GD, [EEx ia] IIC, TÜV 00 ATEX 1522
UL, USA / Canada cULus
Classifications
ETIM
ETIM 2.0 EC001431
ETIM 3.0 EC001596
ETIM 4.0 EC001596
ETIM 5.0 EC001596