CSM_E5CN_E5CN-U_DS_E_5_1
1
Basic-type Digital Temperature Controller
E5CN/E5CN-U (48 x 48 mm)
New 48 x 48-mm Basic Temperature
Controller with Enhanced Functions and
Performance. Improved Indication
Accuracy and Preventive Maintenance
Function.
Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
New E5CN-U Models (Plug-in Models) with analog inputs and
current outputs.
A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.
Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
Main I/O Functions
48 × 48-mm
E5CN
48 × 48-mm
E5CN-U
Refer to Safety Precautions for E5
@
N/E5
@
N-H.
Refer to Operation for E5
@
N/E5
@
N-H for operating
procedures.
Event Inputs
None
• Two
Sensor Inputs
• Universal thermocouple/Pt inputs
(Models with temperature inputs)
• Analog current/voltage inputs
(Models with analog inputs)
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period
• 250 ms
Control Output 1
• Relay output
Voltage output (for driving SSR)
• Current output
• Long-life relay output (hybrid)
Control Output 2
None
Voltage output
(for driving SSR)
Auxiliary Outputs
None
• One
• Two
2-level Display: PV and SV 4-digit Display
E5CN
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-485
communications
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
E5CN/E5CN-U
2
Lineup
Note: Models with one control output and one or two auxiliary outputs and models with two control outputs can be used for heating/cooling control.
Model Number Structure
Model Number Legend
Controllers
1. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
Y: Long-life relay output (hybrid) *1
2. Auxiliary Outputs *2
Blank: None
2: Two outputs
3. Option
M: Option Unit can be mounted.
4. Input Type
T: Universal thermocouple/platinum resistance thermometer
L: Analog current/voltage input
5. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
6. Case Color
Blank: Black
W: Silver
7. Terminal Cover
-500: With terminal cover
Option Units
1. Applicable Controller
CN: E5CN or E5CN-H
2. Function 1
Blank: None
Q: Control output 2 (voltage for driving SSR)
P: Power supply for sensor
3. Function 2
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
B: Two event inputs
03: RS-485 communications
H03: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + RS-485 communications
HB: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + Two event inputs
HH03: Heater burnout/SSR failure/Heater overcurrent detection
(CT2) + RS-485 communications
4. Version
N2: Applicable only to models released after January 2008
Note: 1. Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-@@@@).
2.
Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
*1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for
switching the circuit. For details, check the conditions in Ratings.
*2. Auxiliary outputs are contact outputs that can be used to output alarms or results of logic operations.
Plug-in
Terminal block
E5CN
Basic Type
Analog input
Temperature input
2 control outputs
1 control output
2 control outputs
1 control output
0 or 2 auxiliary outputs
2 auxiliary outputs
0 or 2 auxiliary outputs
2 auxiliary outputs
Analog input
Temperature input
1 control output
1 control output0, 1, or 2 auxiliary
outputs
0, 1, or 2 auxiliary
outputs
12345 6 7
E5CN-@@M@@-@-500
1234
E53-CN@@@
3
E5CN/E5CN-U
Ordering Information
Controllers with Terminal Blocks
Note: Models with analog inputs do not have temperature unit indicators.
Option Units
One of the following Option Units can be mounted to provide the E5CN with additional functions.
Note: 1. Option Units cannot be used for plug-in models.
These Option Units are applicable only to models released after January 2008.
2. If the E53-CNQHN2 or E53-CNQHHN2 Option Unit is used together with the E5CN-C@ Temperature Controller and control output 1
(current output) is assigned to the heating control output, heater burnout detection will be disabled.
Size Case color Power supply
voltage Input type Auxiliary outputs Control output 1 Model
1/16 DIN
48 × 48 × 78
(W × H × D)
Black
100 to 240 VAC Thermocouple or
Resistance
thermometer
None
Relay output E5CN-RMT-500
Voltage output (for driving SSR) E5CN-QMT-500
Current output E5CN-CMT-500
2
Relay output E5CN-R2MT-500
Voltage output (for driving SSR) E5CN-Q2MT-500
Current output E5CN-C2MT-500
Long-life relay output (hybrid) E5CN-Y2MT-500
24 VAC/VDC
Thermocouple or
Resistance
thermometer
None
Relay output E5CN-RMTD-500
Voltage output (for driving SSR) E5CN-QMTD-500
Current output E5CN-CMTD-500
2
Relay output E5CN-R2MTD-500
Voltage output (for driving SSR) E5CN-Q2MTD-500
Current output E5CN-C2MTD-500
100 to 240 VAC Analog
(current/voltage)
None
Relay output E5CN-RML-500
Voltage output (for driving SSR) E5CN-QML-500
Current output E5CN-CML-500
2
Relay output E5CN-R2ML-500
Voltage output (for driving SSR) E5CN-Q2ML-500
Current output E5CN-C2ML-500
Long-life relay output (hybrid) E5CN-Y2ML-500
24 VAC/VDC Analog
(current/voltage) 2
Relay output E5CN-R2MLD-500
Voltage output (for driving SSR) E5CN-Q2MLD-500
Current output E5CN-C2MLD-500
Silver
100 to 240 VAC Thermocouple or
Resistance
thermometer
None
Relay output E5CN-RMT-W-500
Voltage output (for driving SSR) E5CN-QMT-W-500
Current output E5CN-CMT-W-500
2
Relay output E5CN-R2MT-W-500
Voltage output (for driving SSR) E5CN-Q2MT-W-500
Current output E5CN-C2MT-W-500
Long-life relay output (hybrid) E5CN-Y2MT-W-500
24 VAC/VDC 2
Relay output E5CN-R2MTD-W-500
Voltage output (for driving SSR) E5CN-Q2MTD-W-500
Current output E5CN-C2MTD-W-500
Functions Model
(See Note 2.)
Communications
RS-485 3-phase heater burnout/SSR failure/
Heater overcurrent detection E53-CNHH03N2
Heater burnout/SSR failure/Heater
overcurrent detection Event inputs E53-CNHBN2
Communications
RS-485
Control output 2
(Voltage for driving SSR) E53-CNQ03N2
Event inputs External power supply for
ES1B E53-CNPBN2
Heater burnout/SSR failure/Heater
overcurrent detection External power supply for
ES1B E53-CNPHN2
Communications
RS-485
External power supply for
ES1B E53-CNP03N2
Communications
RS-485 Heater burnout/SSR failure/Heater
overcurrent detection E53-CNH03N2
Communications
RS-485 E53-CN03N2
Event inputs E53-CNBN2
Heater burnout/SSR failure/Heater
overcurrent detection Control output 2
(Voltage for driving SSR) E53-CNQHN2
3-phase heater burnout/SSR failure/
Heater overcurrent detection Control output 2
(Voltage for driving SSR) E53-CNQHHN2
Event inputs Control output 2
(Voltage for driving SSR) E53-CNQBN2
4
E5CN/E5CN-U
Model Number Structure
Model Number Legend (Plug-in-type Controllers)
1. Output Type
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
2. Number of Alarms
Blank: No alarm
1: One alarm
2: Two alarms
3. Input Type
T: Universal thermocouple/platinum resistance thermometer
L: Analog Input
4. Plug-in type
U: Plug-in type
Ordering Information
Plug-in-type Controllers
Note: Models with analog inputs do not have temperature unit indicators.
1234
E5CN-@@@U
Size Case color Power supply
voltage Input type Auxiliary outputs Control output 1 Model
1/16 DIN Black
100 to 240 VAC
Thermocouple or
resistance
thermometer
None
Relay output E5CN-RTU
Voltage output (for driving SSR) E5CN-QTU
Current output E5CN-CTU
1
Relay output E5CN-R1TU
Voltage output (for driving SSR) E5CN-Q1TU
Current output E5CN-C1TU
2
Relay output E5CN-R2TU
Voltage output (for driving SSR) E5CN-Q2TU
Current output E5CN-C2TU
Analog
(current/voltage)
1
Relay output E5CN-R1LU
Voltage output (for driving SSR) E5CN-Q1LU
Current output E5CN-C1LU
2
Relay output E5CN-R2LU
Voltage output (for driving SSR) E5CN-Q2LU
Current output E5CN-C2LU
24 VAC/VDC
Thermocouple or
resistance
thermometer
None
Relay output E5CN-RTDU
Voltage output (for driving SSR) E5CN-QTDU
Current output E5CN-CTDU
1
Relay output E5CN-R1TDU
Voltage output (for driving SSR) E5CN-Q1TDU
Current output E5CN-C1TDU
2
Relay output E5CN-R2TDU
Voltage output (for driving SSR) E5CN-Q2TDU
Current output E5CN-C2TDU
E5CN/E5CN-U
5
Accessories (Order Separately)
USB-Serial Conversion Cable
Terminal Cover
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Note: The Waterproof Packing is included with the Controller only for
models with terminal blocks.
Current Transformers (CTs)
Adapter
Note: Use this Adapter when the panel has been previously prepared
for the E5B@.
Sockets (for Plug-in Models)
Front cover
CX-Thermo Support Software
Model
E58-CIFQ1
Connectable models Model
Terminal block models E53-COV17
Model
Y92S-29
Hole diameter Model
5.8 dia. E54-CT1
12.0 dia. E54-CT3
Connectable models Model
Terminal block models Y92F-45
Type Model
Front-connecting Socket P2CF-11
Front-connecting Socket with Finger Protection P2CF-11-E
Back-connecting Socket P3GA-11
Terminal Cover for Back-connecting socket with
Finger Protection Y92A-48G
Type Model
Hard Front Cover Y92A-48B
Soft Front Cover Y92A-48D
Model
EST2-2C-MV4
E5CN/E5CN-U
6
Specifications
Ratings
Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power
consump-
tion
E5CN 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA)
24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA)
E5CN-U 100 to 240 VAC: 6 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W)
Sensor input
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Voltage input: 0 to 50 mV
Models with analog inputs
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Control
outputs
Relay output
E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
E5CN-U SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Voltage output
(for driving SSR)
E5CN
E5CN-U Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection
circuit
Current output E5CN 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000
Long-life relay
output E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply
voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA,
leakage current: 5 mA max. (250 VAC, 60 Hz)
Auxiliary
outputs
Number of outputs 1 or 2 max. (Depends on the model.)
Output
specifications
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA
Event
inputs
Number of inputs 2
External contact
input
specifications
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided
Setting method Digital setting using front panel keys
Indication method 11-segment digital display and individual indicators (7-segment display also possible)
Character height: PV: 11 mm, SV: 6.5 mm
Multi SP Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
communications.
Bank switching Not supported
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection (including SSR failure and heater overcurrent detection), 40% AT, 100% AT, MV limiter, input
digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF
counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple
program, automatic cooling coefficient adjustment
Ambient operating temperature 10 to 55°C (with no condensation or icing), for 3-year warranty: 10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature 25 to 65°C (with no condensation or icing)
E5CN/E5CN-U
7
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal Inputs)
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Models with Analog Inputs
Shaded settings are the default settings.
Input
Type
Platinum resistance
thermometer Thermocouple Infrared temperature
sensor
Analog
input
Name Pt100 JPt100 K J T E L U N R S B W PL
II
10 to
70°C
60 to
120
°C
115
to
165
°C
140
to
260
°C
0 to
50 mV
Temperature range (°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100.0
200.0
2300
Usable
in the
following
ranges
by
scaling:
1999 to
9999 or
199.9
to 999.9
1800
1700 1700
1300 1300 1300
850 850 850
600
500.0 500.0 500.0
400.0 400 400.0 400 400.0
260
120 165
100.0 100.0 90
100
0.0 0.0 00 00 0 0 0 0
20.0 100 20.0 100
200 199.9 199.9 200 200 199.9 200 200 199.9 200
Setting
number 012345 6 7 8 9 10 11 12 13 14 15 16 17 18 24 25 19 20 21 22 23
Input Type Current Voltage
Input specification 4 to 20mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Setting range Usable in the following ranges by scaling:
1999 to 9999, 199.9 to 999.9, 19.99 to 99.99 or 1.999 to 9.999
Setting number 01234
8
E5CN/E5CN-U
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
*1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
*2. Set value: 1, Upper- and lower-limit alarm
*3. Set value: 4, Upper- and lower-limit range
*4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
Case 3: Always OFF
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
*6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the operation of the standby sequence.
*7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the loop burnout alarm (LBA).
*8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the PV change rate alarm.
Set value Alarm type
Alarm output operation
Description of function
When alarm value
X is positive
When alarm value
X is negative
0 Alarm function OFF Output OFF No alarm
1 *1 Upper- and lower-limit *2Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
2 Upper-limit Set the upward deviation in the set point by setting
the alarm value (X).
3 Lower-limit Set the downward deviation in the set point by setting
the alarm value (X).
4 *1 Upper- and lower-limit range *3Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
5 *1Upper- and lower-limit with
standby sequence *4A standby sequence is added to the upper- and
lower-limit alarm (1). *6
6 Upper-limit with standby sequence A standby sequence is added to the upper-limit alarm
(2). *6
7 Lower-limit with standby sequence A standby sequence is added to the lower-limit alarm
(3). *6
8 Absolute-value upper-limit The alarm will turn ON if the process value is larger
than the alarm value (X) regardless of the set point.
9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller
than the alarm value (X) regardless of the set point.
10 Absolute-value upper-limit with
standby sequence A standby sequence is added to the absolute-value
upper-limit alarm (8). *6
11 Absolute-value lower-limit with
standby sequence A standby sequence is added to the absolute-value
lower-limit alarm (9). *6
12 LBA (alarm 1 type only) ---
*7
13 PV change rate alarm --- *8
ON
OFF SP
LH
SP
X
ON
OFF SP
X
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
SP
LH
ON
OFF
SP
LH
ON
OFF
*5
SP
X
ON
OFF SP
X
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
LH
H < 0, L > 0
H < L
SP
Case 1
LH
H > 0, L < 0
H > L
SP
Case 2
LH H < 0, L < 0
SP
LH
H < 0, L > 0
H L
SP
LH
H > 0, L < 0
H L
SP
Case 3 (Always ON)
LHSP
Case 1
LHSP
Case 2
LHSP
L
L
HSP
HSP
Case 3 (Always OFF)
H < 0, L > 0
H < L
H > 0, L < 0
H > L
H < 0, L < 0
H < 0, L > 0
H L
H > 0, L < 0
H L
9
E5CN/E5CN-U
Characteristics
*1. The indication accuracy of K thermocouples in the 200 to 1300°C range, T and N thermocouples at a temperature of 100°C max., and U
and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
*2. Ambient temperature: 10°C to 23°C to 55°C, Voltage range: 15% to 10% of rated voltage
*3. K thermocouple at 100°C max.: ±10° max.
*4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
*5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).
*6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time.
*7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket.
The P3GA-11 is not certified for UL listing.
*8. Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*9. Refer to information on maritime standards in Safety Precautions for E5
@
N/E5
@
N-H for compliance with Lloyd's Standards.
Indication accuracy
Thermocouple: *1
Terminal block models (E5CN): (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max.
Plug-in models (E5CN-U): (±1% of indicated value or ±2°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input:
Terminal block models (E5CN) and plug-in models (E5CN-U): (
±
0.2% of indicated value or
±
0.8
°
C, whichever is greater)
±
1 digit max.
Analog input:
Terminal block models (E5CN) and plug-in models (E5CN-U): ±0.2% FS ±1 digit max.
CT input:
Terminal block models (E5CN): ±5% FS ±1 digit max.
Influence of temperature *2
Thermocouple input (R, S, B, W, PL II):
Terminal block models (E5CN): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Plug-in models (E5CN-U): (±2% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: *3
Terminal block models (E5CN): (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Plug-in models (E5CN-U): (±2% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input:
Terminal block models (E5CN) and plug-in models (E5CN-U):
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input:
Terminal block models (E5CN) and plug-in models (E5CN-U): (±1%FS) ±1 digit max.
Influence of voltage *2
Input sampling period 250 ms
Hysteresis Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)
Proportional band (P) Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s) *5
Control period 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range 1999 to 9999 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Shock
resistance
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
Weight E5CN Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g
E5CN-U Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g
Degree of
protection
E5CN Front panel: IP66, Rear case: IP20, Terminals: IP00
E5CN-U Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.0 or higher
Setup Tool port Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An E58-CIFQ1
USB-Serial Conversion Cable is required to connect the computer to the E5CN. *6
Standards
Approved
standards *7UL 61010-1, CSA C22.2 No. 1010-1, KOSHA certified (some models) *8
Conformed
standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *9
EMC
EMI: EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Power Frequency Magnetic Field Immunity: EN 61000-4-8
Voltage Dip/Interrupting Immunity: EN 61000-4-11
10
E5CN/E5CN-U
USB-Serial Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Communications Specifications
*The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Current Transformer (Order Separately)
Ratings
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
*1. For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
*2. For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
*3. For heater overcurrent alarms, the heater current will be
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
Electrical Life Expectancy Curve for
Relays (Reference Values)
Note: Do not connect a DC load to a Controller with a Long-life Relay
Output.
Applicable OS Windows 2000, XP, or Vista
Applicable software CX-Thermo version 4 or higher
Applicable models E5AN/E5EN/E5CN/E5CN-U/E5AN-H/
E5EN-H/E5CN-H/E5GN
USB interface standard Conforms to USB Specification 1.1.
DTE speed 38400 bps
Connector
specifications
Computer: USB (type A plug)
Temperature Controller: Setup Tool port
(on bottom of Controller)
Power supply Bus power (Supplied from USB host
controller.)
Power supply voltage 5 VDC
Current consumption 70 mA
Ambient operating
temperature 0 to 55°C (with no condensation or icing)
Ambient operating
humidity 10% to 80%
Storage temperature 20 to 60°C (with no condensation or
icing)
Storage humidity 10% to 80%
Altitude 2,000 m max.
Weight Approx. 100 g
Transmission line
connection method RS-485: Multipoint
Communications RS-485 (two-wire, half duplex)
Synchronization
method Start-stop synchronization
Protocol CompoWay/F, SYSWAY, or Modbus
Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
Transmission code ASCII
Data bit length *7 or 8 bits
Stop bit length *1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control None
Interface RS-485
Retry function None
Communications
buffer 217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
Dielectric strength 1,000 VAC for 1 min
Vibration resistance 50 Hz, 98 m/s2
Weight E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories
(E54-CT3 only)
Armatures (2)
Plugs (2)
CT input
(for heater current
detection)
Models with detection for single-phase
heaters: One input
Models with detection for single-phase
or three-phase heaters: Two inputs
Maximum heater current 50 A AC
Input current indication
accuracy ±5% FS ±1 digit max.
Heater burnout alarm
setting range *1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
SSR failure alarm
setting range *2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Heater overcurrent
alarm setting range *3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
500
300
100
50
30
10
5
3
10123456
E5CN
250 VAC, 30 VDC
(resistive load)
cosφ = 1
Switching current (A)
Life (× 104 operations)
11
E5CN/E5CN-U
External Connections
A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.)
Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
E5CN
Controllers
Option Units
E5CN-U
Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
Voltage output (for driving SSR)
12 VDC, 21 mA
Control output 2
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Current output
0 to 20 mA DC
Load: 600 Ω max.
4 to 20 mA DC
Long-life relay output
250 VAC, 3 A (resistive load)
Control output 1
Auxiliary outputs
(relay outputs)
A
B
B
TC/Pt
universal input
Input power supply
Control output 1
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Analog input
V
Auxiliary output 2
mA
Auxiliary output 1
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
DO NOT
USE
DO NOT
USE
DO NOT
USE
The E5@N-@@@T@ is set for a K-type
thermocouple (input type = 5) by default. An
input error (s.err) will occur if the input type
setting does not agree with the temperature
sensor. Check the input type.
11
12
13
14
15
EV1
EV2
E53-CNHBN2
Event inputs
and CT
11
12
13
14
15
E53-CNPBN2
Event Inputs and
External Power Supply
EV1
EV2
+
External
power supply 12 VDC,
20 mA
11
12
13
14
15
E53-CNPHN2
External Power
Supply and CT
+
External
power supply 12 VDC,
20 mA
11
12
13
14
15
B(+)
A()
RS-485
E53-CNP03N2
Communications (RS-485)
and External Power Supply
+
External
power supply 12 VDC,
20 mA
11
12
13
14
15
E53-CNQHN2
Control Output 2
and CT
+
Control output 2
11
12
13
14
15
EV1
EV2
E53-CNQBN2
Event Inputs and
Control Output 2
+
Control output 2
11
12
13
14
15
B(+)
A()
RS-485
E53-CNHH03N2
Communications
(RS-485) and CT2
11
12
13
14
15
B(+)
A()
RS-485
E53-CNQ03N2
Communications
(RS-485) and
Control Output 2
+
Control output 2
11
12
13
14
15
B(+)
A()
RS-485
E53-CN03N2
Communications
(RS-485)
11
12
13
14
15
EV1
EV2
E53-CNBN2
Event inputs
11
12
13
14
15
E53-CNQHHN2
Control Output 2
and CT2
+
Control output 2
11
12
13
14
15
B(+)
A()
RS-485
E53-CNH03N2
Communications
(RS-485) and CT
DO NOT
USE DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
CT1
CT1
CT1
CT1
CT1
CT1
CT2
CT2
A
B
B
Auxiliary output
250 VAC, 3 A (resistive load)
Control output 1
TC/Pt
universal input
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarit
y
)
Auxiliary output 1
(Relay outputs)
Analog input
V
m A An input error is sent to the
output to which the alarm 1
function is assigned.
Current output
0 to 20 mA DC
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Load: 600 W max.
4 to 20 mA DC
Control output 1
Auxiliary output 2
(Control output (cooling side))
DO NOT
USE
DO NOT
USE
DO NOT
USE
The E5@N-@@@T@ is set for a
K-type thermocouple (input type = 5)
by default. An input error (s.err) will
occur if the input type setting does
not agree with the temperature
sensor. Check the input type.
E5CN/E5CN-U
12
Nomenclature
Dimensions (Unit: mm)
Accessories (Order Separately)
USB-Serial Conversion Cable
Operation indicators
Level Key
Temperature unit
No.1 display
No. 2 display
Up Key
Mode Key Down Key
E5
C
N
E5CN-U
The front panel is the same for the E5CN and E5CN-U.
45+0.6
0
45+0.6
0
45+0.6
0
60 min.
(48 × number of units 2.5)+1.0
0
Group mounting does not
allow waterproofing.
Panel Cutout
Mounted Separately Group Mounted
48 × 48
Terminal Cover
(E53-COV17)
(Accessory)
44.8 × 44.8
48.8
6
1.5
91
78
Mounting Adapter
(Accessory)
58
Waterproof
Packing
(Accessory)
E5CN
Terminal Models
Note: The terminal block cannot be removed.
Recommended panel thickness is 1 to
5 mm.
Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature
specified in the specifications.
48 × 48 614.2
58 44.8 × 44.8
70.5
(84.7)
Mounting Adapter
(Accessory)
45+0.6
0
45+0.6
0
45+0.6
0
60 min.
(48 × number of units 2.5)+1.0
0
Panel Cutout
Mounted Separately Group Mounted
E5CN-U
Plug-in Models
Recommended panel thickness is 1 to 5
mm.
Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature specified
in the specifications.
(2,100)
250 1,765
USB connector (type A plug) Serial connector
LED indicator
(
RD
)
LED indicator (SD)
E58-
C
IF
Q
1
13
E5CN/E5CN-U
Current Transformers
48
48.8
22
9.1
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Terminal Cover
E53-COV17
Waterproof Packing
Y92S-29 (for DIN 48 × 48)
Note: The E53-COV10
cannot be used.
E54-CT3 Accessory
Armature
30
21
15 5.8 dia.
25 3
40
10.5
2.8
7.5
10
Two, 3.5 dia.
40 × 40
30
12 dia.
9
2.36 dia.
15
30
Two, M3 (depth: 4)
Approx. 3 dia.
18
(22)
Approx. 6 dia.
Plug
Armature
Lead
E54-CT1
E54-CT3
Connection Example
Plug
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2
Thru-current (Io) A (r.m.s.)
1 10 100 mA 1 10 100
1,000 A
Output voltage (Eo) V (r.m.s.)
100 V
50 Hz
Distortion
factor 10%
3%
1%
100
RL = 10
10
1
100 mV
10
1
100 µV
10
1 k
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for the
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8
3%
1%
1 k
100
50
RL = 10
500
Distor-
tion
factor
10%
Thru-current (Io) A (r.m.s.)
1 10 100 mA 1 10 100
1,000 A
Output voltage (Eo) V (r.m.s.)
100 V
50 Hz
10
1
100 mV
10
1
100 µV
10
E5CN/E5CN-U
14
Adapter
E5CN-U Wiring Socket
Note: A model with finger protection (P2CF-11-E) is also available.
Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets.
2. A Protective Cover for finger protection (Y92A-48G) is also available.
Fixture (Accessory)
69.6 to 77.6
8767 × 67
72 × 72
76
4.7
72 × 72
48 × 48
Panel (1 to 8 mm)
77.3 (to back of E5CN)
2.2 4.7
Y92F-45
Mounted to E5CN
Note: 1. Note: 1. Use this Adapter when the panel has already been prepared for the E5B@.
2. The Adapter is available only in black.
40±0.2
4.5
567
8
4
3
21
9
10 11
70 max.
4
Eleven, M3.5 × 7.5
sems screws 7.8
Two,
4.5-dia.
holes
50 max.
3
31.2 max.
35.4
Note: Can also be mounted to a DIN track.
Mounting Holes
Terminal Layout/Internal Connections
(Top View)
Two, 4.5 dia. mounting holes
Front-connecting Socket
P2CF-11
5 6 7 8
4
3
2
9
10
11
1
25.6
27 dia.
45
45
4.5 16.3 6.2
47
3
8.7
6
Terminal Layout/Internal Connections
(Bottom View)
Back-connecting Socket
P3GA-11
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2011.1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2011 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
E5CN-RMT-500-AC100-240 E5CN-Q2MT-500-AC100-240 E5CN-R2MTD-500-AC/DC24 E5CN-CMT500 AC100240
E5CNQMT500AC100240 E5CN-Q2M-TD-500 ACDC24 E5CN-C2MLD-500 AC/DC24 E5CN-FR2MT-500 AC100-240
E5CN-FRMT-500 AC100-240 E5CN-HV2M-500 AC100-240 E5CN-Q2ML-500 AC100-240 E5CN-QMTD-500 AC/DC24
E5CN-R1TU AC100-240 E5CN-R2HBT AC100-240 E5CN-QMT-500 AC100-240 E5CN-CMT-500 AC100-240