2Specifications are subject to change without notice (25.10.99)
Supply Specifications
Power supply AC types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10 230
230 VAC ±15%, 45 to 65 Hz
115 115 VAC ±15%, 45 to 65 Hz
024 24 VAC ±15%, 45 to 65 Hz
Voltage interruption ≤40 ms
Rated insulation voltage ≥250 VAC (rms)
Rated operational power 3.0 VA
Rated impulse withstand voltage
4 kV (1.2/50 µs) (line/neutral)
Power supply DC type
Overvoltage cat. III (IEC 60664)
Rated operational volt. 724 24 VDC ±15% (pin 2 pos.)
Rated insulation voltage None
Rated operational power 1.5 W
Rated impulse withstand voltage
800 V (1.2/50 µs)
General Specifications
Power ON delay ≤150 ms
Power OFF delay ≥200 ms
Indication for
Power supply ON LED, green
Output ON LED, yellow
Remaining time to elapse 4 LEDs, yellow, 25% each
Environment
Degree of protection IP 20 B
Pollution degree 2 (IEC 60664)
Operating temperature 0° to +50°C (+34° to +122°F)
Storage temperature -50° to +85°C (-58° to +185°F)
Weight AC supply 200 g
DC supply 125 g
Approvals UL, CSA
S 1331
Mode of Operation
In connection with all func-
tions automatic start is pos-
sible by permanent intercon-
nection of pins 5 & 7.
Function 0: Delay on operate,
leading edge, man. start,
man. restart, man. time reset.
Function 1: Interval timer,
leading edge, man. start,
man. restart, man. time reset.
Function 2: Symmetrical
recycler, OFF-time first, lea-
ding edge, man. start, man.
restart, no time reset.
Function 3: Symmetrical
recycler, ON-time first, lea-
ding edge, man. start, man.
restart, no time reset.
Function 4: Delay on operate,
trailing edge, man. start, man.
restart, man. time reset.
Function 5: Interval timer,
trailing edge, man. start, man.
restart, man. time reset.
Note: The output relay only
operates when the time peri-
od is running.
Function 6: Interval timer,
trailing edge, man. start, man.
restart, man. time reset.
Function 7: Delay on operate,
leading edge, man. start,
man. restart, man. time reset.
Note: The relay releases on
trailing edge, which means
the trigger pulse must be of
longer duration than the time
period.
Function 8: Recycler with fix-
ed ON-time, leading edge,
man. start, man. restart, no
time reset. Fixed ON-time:
approx. 0.5 sec.
Function 9: Time period mul-
tiplier, leading edge, man.
start, man. restart, man. time
reset.
Note: Each pulse input adds
the set time the total timing
period. Max. time period
memory is 256 pulses.
Time stop function: By inter-
connection of pins 7 & 8 the
time function stops, and the
output relay remains either
released or operated. By dis-
connection of pins 7 & 8 the
remaining time continues to
elapse.
Accessories Function and Time Setting
Adjustable time setting by two
digital thumb-wheel switches
(1-99)
Upper knob:
Time period multiplier x 0.01,
x 0.1 and x 1.0.
Socket◊S 411
Hold down spring◊HF
Mounting rack SM 13
Socket cover BB 4
Front mounting bezel FRS 2
All 3/4-wire sensor types with NPN open collector output.
For further information refer to "Accessories".
For other AC/DC voltages refer to "General Information".
Centre knob:
Selection of time range
(seconds, minutes and hours).
Lower knob:
Selection of function.