Safe Connections for Higher Voltage Power Distribution Systems Anderson Power Products(R) has lead the connector industry in development of DC power connection solutions since the introduction of the SB(R) electrical connector in 1953. Saf-D-Grid(R) builds on the proven contact technology used in SB (R) and Powerpole(R) connectors by offering features required in 380-400 VDC power distribution systems. First Mate, Last Break Ground Contact APP(R) introduced the Saf-D-Grid(R) connector system in January 2009 as a safe appliance power connector for server, telecommunication, and other devices up to 600 VDC. Integral Latch The APP(R) Saf-D-Grid (R) plug and receptacle provide for the direct connection of DC electronic devices to a DC micro-grid powered by renewable energy or high efficiency DC sources. The connector meets international safety requirements for hazardous, low voltage applications including UL 950 and IEC 60950. The Saf-D-Grid(R) is size compatible with the IEC 320 C13 and C14 AC connection system. It is the only connector system so sized that is UL rated for disconnect of a 400 VDC, 20 amp load. * Provides the safety of an earthing path before engagement of the power contacts. Ultra Short Receptacle * Connectors cannot be accidentally unmated, preventing unwanted power loss to critical equipment. Saf-D-Grid(R) also enables greater power density by allowing up to 40A and 600V DC or AC within the same space of the IEC 320 C13 & C14 system that is limited to 10A and 250 VAC. This allows the use of Saf-D-Grid(R) in AC systems that require more power by increasing the wattage capability within the existing connector space. T-Latch Straight Plug Hot Plug Rated * The connectors are rated for current interruption for both electronic (capacitive) and electrical (resistive) loads. Touch Safe / Shock Protection * Minimizes the risk of personal contact with a hazardous voltage. Passes UL & IEC finger probe (plug & receptacle) and 3mm probe tests (receptacle). Arcing Protection * Housings contain the arc if connectors are mated or unmated while under load minimizing risk to personnel. | SPECIFICATIONS | Mechanical Contact Retention (lbf) (N) Plug Latch Retention (lbf) (N) 20 89 20 89 Panel Latch Retention (lbf) (N) 60 267 Durability 5,000 cycles - no load Receptacle Max Wire OD (in) (mm) 0.22 5.6 Creep & Clearance per UL & IEC 60950 Between live parts of different polarity, earthing circuit and the mating surface. * Short and Flush Receptacle with Crimp Contacts * Ultra Short Receptacle, Short and Flush Receptacle with Solder or PCB Contacts Maximum PCB Thickness A (in) (mm) Mechanical Shock B IEC 60512-4-6C Vibration, High Frequency B IEC 60512-4-6d A B 8.0 mm Protection IEC 60529 Voltage (AC/DC) * UL 1977 / CSA 22.2 600 * IEC 400 Current Rating (Amperes) 40 Wire Range (AWG) #12 to #18 (mm) 2.5 to 0.75 Hot Plug Rated * 250 cycles 400V @ 440A in-rush * 250 cycles (UL) 400V @ 20A load Dielectric Withstanding Voltage 3,300 Operating Temperature (C) -20 to 80 (F) -4 to 176 Fault Current Withstand UL 467 14 AWG, 300A, 4 Sec. 7.0 mm Materials (RoHS Compliant) 0.093 Housings 2.4 50g's 20g's Applicable only to receptacles intended for termination to PCB Tested with straight plug and flush mount receptacle with #14 AWG wire and 2003G1 contacts. -2- Electrical * 2006G1 Series Receptacles Hi Temp Nylon + 30% GF, UL94 V-0, Halogen Free * All other Receptacles & Plugs Polycarbonate UL94 V-0 Springs Stainless Steel Contacts Copper, Silver Plate Cable / Strain Relief Thermoplastic UL94 V-2 IP20 | TEMPERATURE CHARTS | Saf-D-Grid (R) Temperature Rise at Constant Current 60 85 75 Temperature (C) Temperature (C) 50 40 30 20 10 0 Saf-D-Grid(R) Derating vs. Ambient Temperature 65 55 45 35 25 0 5 10 15 20 25 30 35 40 45 0 5 10 15 A mperes Applied 12 AWG 16 AWG Series Flush 2002 & Short 2005 Flush 2002 & Short 2005 Flush 2002 & Short 2005 Flush 2002 & Short 2005 Flush 2002 & Short 2005 Ultra Short 2006G Ultra Short 2006G Ultra Short 2006G Wire Size 18 AWG plug & receptacle 16 AWG plug & receptacle 1.5 mm plug & receptacle 14 AWG plug & receptacle 12 AWG plug & receptacle 18 AWG plug & receptacle 1.5 mm plug & receptacle 14 AWG plug & receptacle Rating Rated Voltage AC / DC CNR UL 1977 12 18 600 600 UL 1977 12 400 CNR UL 1977 14 18 600 600 UL 1977 14 400 Agency of Use Disconnect Only Disconnect Only Current Interrupt Disconnect Only Current Interrupt Disconnect Only Current Interrupt Disconnect Only Current Interrupt Disconnect Only Current Interrupt 30 35 40 45 50 Connector T ype / Cable T ype W ire Size Straight Plug / IEC 61984 3 14 400 IEC 61984 3 25 400 20 400 30 40 600 600 UL 1977 30 400 CNR IEC 61984 UL 1977 IEC 61984 UL 1977, CNR 13 13 21 13 12 600 400 600 400 400 IEC 61984 14 400 CNR IEC 61984 UL 1977 UL 1977, CNR IEC 61984 25 25 35 600 400 600 20 400 Disconnect Current Only Interrupt (600V Max) (400V Max) 14 AWG 18 18 Straight Plug / 18 AWG 10 10 ST 600V 16 AWG 13 13 14 AWG 18 18 14 AWG 18 1 18 1 14 AWG 16 2 N/A 18 AWG 10 10 16 AWG 13 13 14 AWG 18 18 18 AWG 10 10 16 AWG 13 13 14 AWG 18 18 SOOW 600V Straight Plug / UL 1977, CNR IEC 61984 3 CNR UL 1977 14 AWG 18 AWG | UL 817 RATINGS | Rated Current Amp Conditions Current Interrupt Disconnect Only Current Interrupt Disconnect Only Current Interrupt 25 12 AWG 16 AWG 14 AWG 18 AWG | UL 1977 & IEC 61984 RATINGS | Receptacle 20 A mperes Applied SJT 300V IEC C20 Plug / SJT 250V Right Angle Plug / ST 600V T-Latch Plug / ST 600V 1 2 Note: Voltage limited by wire insulation rating Note: Voltage limited by the IEC connector on the cord set | CCC RATINGS | Receptacle - Pending Wire Size Conditions Series AWG Ultra Short 2006G 2.5 mm plug & receptacle of Use Current Interrupt Rated Rated Current Voltage Amp AC / DC 20 400 3 Note: No IEC 61984 approvals for 2002N, 2002V, 2005N & 2005V series receptacles. * UL1977 ratings are for recognized components under UL1977 file# E26226. Ratings may vary once the final listing category is considered. Do not exceed maximum operating temperature of connector or wire insulation. Ratings are based on an ambient temperature of 25C. * CNR - indicates investigation to Canadian National Standards, C22.2 No. 182.3. * UL817 recognized or listed cord sets under UL file number E 343569. * IEC 61984 certification by TUV certification number R 7212289. * "Disconnect Only" indicates the devices are not for interrupting current. * "Current Interrupt" indicates the devices have been investigated for the interruption of current. * APP assembly tooling is required for UL, CSA & other safety agency compliance. Use of unapproved tooling will void connector warranty. * CCC Certification to: GB/T11918-2001: Part 1 (idt IEC 60309-1:1999) & GB/T11919-2001: Part 2 (idt IEC 60309-2:1999) * CCC Certification is only required for connectors which are built to CCC recognized dimensional & performance standards. Saf-D-Grid was voluntarily submitted to CCC under performance only aspects of relevant standards. -3- | PANEL MOUNT RECEPTACLES | - For Crimp Termination to Wire Receptacle Housings Only Housing Style & Panel Thickness Non-Bulk - Part Numbers - Std. Pack Bulk - Part Numbers - Std. Pack Short Depth 0.8mm 1.0mm 1.6mm 2005G1 2005G3 2005G4 1 1 1 2005G1-BK 2005G3-BK 2005G4-BK 100 100 100 Flush Mount 0.8mm 1.0mm 1.2mm 1.6mm 2.0mm 2.5mm 2002G1 2002G3 2002G2 2002G4 2002G5 2002G6 1 1 1 1 1 1 2002G1-BK 2002G3-BK 2002G2-BK 2002G4-BK 2002G5-BK 2002G6-BK 100 100 100 100 100 100 Short Receptacle Mid-flange snap-in panel mount design shortens space required inside the panel. For use with crimp wire contacts. Flush Mount Receptacle Flush snap-in panel mount design is compatible with crimp wire contacts. Contacts - #12 to 18 AWG Compatible Loose Piece Std. Reeled Receptacles - Part Numbers - Pack - Part Numbers Flush Mount 2003G1-LPBK 1 2003G1 Std. Pack 2,500 Crimp Contact | TOOLING | Tooling Available Directly from Anderson Power Products (All Customers) Contact Part Number Automated Tooling Hand Tool Description 2003G1 Receptacle Contact, Reeled 2003G1-LPBK Receptacle Contact, Loose Piece Press Applicator 115V = TE0101 230V = TE0102 TD0104 1309G9 Hand Tool Additional Tooling Available Directly from ATS (North American Customers Only) Contact Part Number 2003G1 Automated Tooling Description Press Air Feed Applicator Receptacle Contact, Reeled 354500-1 354578-1 1852859-3 * Contact ATS Directly to Purchase or Lease Tooling P.O. Box 6780, Harrisburg, PA 17112 USA T: 877-671-2955 F: 717-810-2862 www.applicationtooling.com Press Applicator NOTE: Tooling recommended by APP is required for UL, CSA & other safety agency compliance. Use of unapproved tooling will void connector warranty. NOTE: Shading Indicates Build to Order -4- | PANEL MOUNT RECEPTACLES | - For Solder Termination to Wire Receptacle Kits (Housing & Contacts) Housing Termination Type Panel Thickness Non-Bulk - Part Numbers - Flush Mount Flush Mount Flush Mount Flush Mount Flush Mount Flush Mount Flush Mount Flush Mount Short Depth Short Depth Short Depth Short Depth Short Depth Short Depth Ultra Short Depth Ultra Short Depth Ultra Short Depth Ultra Short Depth Ultra Short Depth Ultra Short Depth Wire, Crimp* Wire, Crimp* Wire, Crimp* Wire, Crimp* Wire, Solder Wire, Solder Wire, Solder Wire, Solder Wire, Crimp* Wire, Crimp* Wire, Crimp* Wire, Solder Wire, Solder Wire, Solder Wire, Solder Wire, Solder Wire, Solder Wire, Solder Wire, Solder Wire, Solder 0.8mm 1.0mm 1.2mm 1.6mm 0.8mm 1.0mm 1.2mm 1.6mm 0.8mm 1.0mm 1.6mm 0.8mm 1.0mm 1.6mm 0.8mm 1.0mm 1.2mm 1.6mm 2.0mm 2.5mm 2002G1KIT 2002G3KIT 2002G2KIT 2002G4KIT 2002N1 2002N3 2002N2 2002N4 2005G1KIT 2005G3KIT 2005G4KIT 2005N1 2005N3 2005N4 2006G1 2006G3 2006G2 2006G4 2006G5 2006G6 Std. Pack Bulk - Part Numbers - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 N/A N/A N/A N/A 2002N1-BK 2002N3-BK 2002N2-BK 2002N4-BK N/A N/A N/A 2005N1-BK 2005N3-BK 2005N4-BK 2006G1-BK 2006G3-BK 2006G2-BK 2006G4-BK 2006G5-BK 2006G6-BK Std. Pack Ultra Short Receptacle Mid-flange snap in panel mount design for direct solder wire termination uses minimal space inside the panel. Halogen free. N/A N/A N/A N/A 100 100 100 100 N/A N/A N/A 100 100 100 100 100 100 100 100 100 Short Receptacle Short receptacle housing fully assembled with contacts for direct solder wire termination. Flush Mount Receptacle Standard receptacle housing fully assembled with contacts for direct solder wire termination. *Includes Contact Part Number 2003G1 Pre-Terminated to 12 inches of #16 AWG, 600V Wire Contacts - #14 to 18 AWG Receptacle Housings Only Housing Style & Panel Thickness Non-Bulk - Part Numbers - Std. Pack Bulk - Part Numbers - Std. Pack Ultra Short Depth 0.8mm 1.0mm 1.2mm 1.6mm 2.0mm 2.5mm 2006G1-NC 2006G3-NC 2006G2-NC 2006G4-NC 2006G5-NC 2006G6-NC 1 1 1 1 1 1 2006G1-NC-BK 2006G3-NC-BK 2006G2-NC-BK 2006G4-NC-BK 2006G5-NC-BK 2006G6-NC-BK 100 100 100 100 100 100 Compatible Loose Piece Std. Reeled Receptacles - Part Numbers - Pack - Part Numbers Ultra Short 2016G1-LPBK 1 - Std. Pack - NOTE: * Ultra short contacts are to be used with ultra short depth housings only, for soldering to stranded copper wire. Ultra Short Solder Contact | PANEL MOUNT RECEPTACLES | - For Solder Termination to PCB Receptacle Kits (Housing & Contacts) Housing Termination Type Panel Thickness Non-Bulk - Part Numbers - Flush Mount Flush Mount Flush Mount Flush Mount Short Depth Short Depth Short Depth PCB, Solder PCB, Solder PCB, Solder PCB, Solder PCB, Solder PCB, Solder PCB, Solder 0.8mm 1.0mm 1.2mm 1.6mm 0.8mm 1.0mm 1.6mm 2002V1 2002V3 2002V2 2002V4 2005V1 2005V3 2005V4 Std. Pack Bulk - Part Numbers - 1 1 1 1 1 1 1 2002V1-BK 2002V3-BK 2002V2-BK 2002V4-BK 2005V1-BK 2005V3-BK 2005V4-BK Std. Pack 100 100 100 100 100 100 100 Short Receptacle Short receptacle housing fully assembled with PCB contacts for 0.062 (1.57 mm) to 0.093 (2.36 mm) inch boards. Flush Mount Receptacle Standard receptacle housing fully assembled with PCB contacts for 0.062 (1.57 mm) to 0.093 (2.36 mm) inch boards. NOTE: Shading Indicates Build to Order -5- | DRAWINGS | - See Product Drawings on the Website for Additional Information 19.90 + 0.10 0.00 0.783 + 0.004 - 0.000 [ 2.2 ] 0.09 [ 3.08 ] 0.15 26.80 + 0.10 0.00 1.055 + 0.004 - 0.000 [ 3.0 ] 0.12 [ 5.6 ] 0.22 [ 2.5 ] R. 10 MAX TYP. [ 3.8 ] 0.15 [ 29.6 ] 1.17 [ 0.8 ] 0.03 Ultra Short Contact Panel Cut Out for All Receptacle Types [ 31.0 ] 1.22 [ 17.0 ] 0.67 GROUND [ 24.0 ] 0.94 [ 17.1 ] 0.67 NEGATIVE (-) [ 3.8 ] 0.15 [ 5.4 ] 0.21 [ 6.4 ] 0.25 [ 26.9 ] 1.06 [ 5.0 ] 0.20 (+) POSITIVE Flush Mount & Short Contact Ultra Short Depth - For Solder Termination to Wire [ 31.0 ] 1.22 [ 29.0 ] 1.14 GROUND [ 24.0 ] 0.94 [ 14.0 ] 0.55 [ 12.4 ] 0.49 NEGATIVE (-) (+) POSITIVE Short Depth - For Crimp Termination to Wire [ 40.7 ] 1.60 [ 33.4 ] 1.32 [ 22.6 ] 0.89 GROUND [ 24.1 ] 0.95 [ 44.5 ] 1.75 NEGATIVE (-) (+) POSITIVE Flush Mount - For Crimp Termination to Wire [ 2.26 ] 57.4 DIM "A" (3) PLC'S [ 2.11 ] [ 1.60 ] 53.6 40.7 [ 1.97 ] 50.1 Flush Mount - For Solder Termination to Wire [ 0.55 ] 14.0 [ 2.26 ] 57.4 [ 1.05 ] 26.6 DIM "A" (3) PLC'S Short Depth - For Solder Termination to Wire -6- [ 1.05 ] 26.6 [ 0.77 ] 19.7 [ 1.05 ] 26.6 [ 1.82 ] 46.3 REF. DIM "A" (3) PLC'S [ 0.21 ] 5.3 [ 0.77 ] 19.7 Flush Mount - For Solder Termination to PCB [ 1.71 ] 43.5 [ 1.14 ] 29.0 [ 1.97 ] 50.1 [ 0.77 ] 19.7 [ 0.21 ] 5.3 [ 0.55 ] 14.0 [ 1.42 ] 36.1 DIM "A" (3) PLC'S [ 1.05 ] 26.7 Short Depth - For Solder Termination to PCB [ 0.78 ] 19.8 | POWER CORDS | - All Plug Types Mate to All Receptacle Types Wide "T" Latch Plug Small Latch Plug Right Angle "T" Latch Plug Wide latch release button across the top of the plug body to allow easy latch access around PSU handles or other obstacles. Small latch release button in the center top of the plug body. Right angle cord over mold to the plug with wide latch button. [ 1.03 ] 26 [ 1.22 ] 31 [ 0.66 ] O 16.8 [ 0.94 ] 23.9 [ 0.74 ] 18.9 POSITIVE (+) NEGATIVE (-) POSITIVE (+) NEGATIVE (-) GROUND GROUND 18 - 14 AWG | 1.0mm - 2.0mm 12 AWG [ 1.03 ] 26.0 [ 0.74 ] 18.9 POSITIVE (+) [ 2.05 0.04 ] 52.0 1.0 [ 2.90 0.04 ] 73.7 1.0 NEGATIVE (-) GROUND Simplified Power Connection Design 1. The Same Receptacle is Used on Both the Power & Load Sides. 2. The Same Plug is Used on Both Sides of the Power Cord. 1 3. Both Plug & Receptacle Connectors are Touch Safe. 2 1 2 Ultra Short Receptacle 3 3 Wide "T" Latch Plug | Common Cable Types Used in Saf-D-Grid(R) Power Cords | Cable Voltage Jacket Conductor Conductor Insulation Type Rating Approvals Material Insulation Coloring Notes SJT 300V UL, CSA PVC PVC Black, White, Green North American Junior Hard Service, Suitable for Medium Duties in Office or Home, Not Outdoor Rated ST 600V UL, CSA PVC PVC Black, White, Green North American Hard Service, Suitable for Medium Duties in Office or Home, Not Outdoor Rated SOOW 600V UL, CSA Rubber Rubber Black, White, Green North American Extra Hard Service, Outdoor Rated, Oil Resistant HVCT 600V PSE PVC PVC Black, White, Green Japanese, JIS C 3312, Suitable for Medium Duties in Office or Home, Not Outdoor Rated H05VVF 300/500V IEC PVC PVC Blue, Brown, Green/Yellow International Harmonized, Suitable for Medium Duties in Office or Home, Not Outdoor Rated 60245 IEC 57 300/500V CCC Rubber Rubber Blue, Brown, Green/Yellow Suitable for Low Mechanical Stress Open Air Environment NOTE: Reference the plug cordset drawings for exact information on the cable used. Some of the above cables may be for special order use only. Plug cordsets that are available with short lead times are shown in the part number charts of this catalog without a shaded background. Additional cable types may be available on request. Contact customer service. -7- Single-Ended "T" Latch Plug Power Cord Length M FT Description UL 817 TUV 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 * CCC Pending CCC * 12 AWG ST UL 600V 90C 12 AWG ST UL 600V 90C 12 AWG ST UL 600V 90C 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 16 AWG ST UL 600V 90C * * 16 AWG ST UL 600V 90C * * 16 AWG ST UL 600V 90C * * 18 AWG ST UL 600V 90C * * 18 AWG ST UL 600V 90C * * 18 AWG ST UL 600V 90C * * 1.0 mm H05VVF CE 500/300V 75C 1.0 mm H05VVF CE 500/300V 75C 1.0 mm H05VVF CE 500/300V 75C 1.5 mm H05VVF CE 500/300V 75C * 1.5 mm H05VVF CE 500/300V 75C * 1.5 mm H05VVF CE 500/300V 75C * 2.5 mm 60245 IEC 57 / CCC 500/300V 60C * 2.5 mm 60245 IEC 57 / CCC 500/300V 60C * 2.5 mm 60245 IEC 57 / CCC 500/300V 60C * 1.0 mm HVCT PSE 600V 75C 1.0 mm HVCT PSE 600V 75C 1.0 mm HVCT PSE 600V 75C 1.25 mm HVCT PSE 600V 75C 1.25 mm HVCT PSE 600V 75C 1.25 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C Non-Bulk - Part Numbers - Std. Pack Bulk - Part Numbers - 2034KZ2 2034KZ3 2034KZ6 2031KZ2 2031KZ3 2031KZ6 2036KZ2 2036KZ3 2036KZ6 2033KZ2 2033KZ3 2033KZ6 2043KZ2 2043KZ3 2043KZ6 2047KZ2 2047KZ3 2047KZ6 2045KZ2 2045KZ3 2045KZ6 2023KZ2 2023KZ3 2023KZ6 2025KZ2 2025KZ3 2025KZ6 2021KZ2 2021KZ3 2021KZ6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2034KZ2-BK 2034KZ3-BK 2034KZ6-BK 2031KZ2-BK 2031KZ3-BK 2031KZ6-BK 2036KZ2-BK 2036KZ3-BK 2036KZ6-BK 2033KZ2-BK 2033KZ3-BK 2033KZ6-BK 2043KZ2-BK 2043KZ3-BK 2043KZ6-BK 2047KZ2-BK 2047KZ3-BK 2047KZ6-BK 2045KZ2-BK 2045KZ3-BK 2045KZ6-BK 2023KZ2-BK 2023KZ3-BK 2023KZ6-BK 2025KZ2-BK 2025KZ3-BK 2025KZ6-BK 2021KZ2-BK 2021KZ3-BK 2021KZ6-BK Std. Pack 20 13 7 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 L Top View Single Ended Plug Assembly Single-Ended Small Latch Plug Power Cord Length Non-Bulk M FT Description UL 817 TUV - Part Numbers 2.0 6.56 12 AWG ST UL 600V 90C 2034G2 3.0 9.84 12 AWG ST UL 600V 90C 2034G3 6.0 19.68 12 AWG ST UL 600V 90C 2034G6 2.0 6.56 14 AWG ST UL 600V 90C * * 2030G2 3.0 9.84 14 AWG ST UL 600V 90C * * 2030G3 6.0 19.68 14 AWG ST UL 600V 90C * * 2030G6 2.0 6.56 18 AWG ST UL 600V 90C * * 2032G2 3.0 9.84 18 AWG ST UL 600V 90C * * 2032G3 6.0 19.68 18 AWG ST UL 600V 90C * * 2032G6 2.0 6.56 1.5 mm H05VVF CE 500/300V 75C * 2040G2 3.0 9.84 1.5 mm H05VVF CE 500/300V 75C * 2040G3 6.0 19.68 1.5 mm H05VVF CE 500/300V 75C * 2040G6 1.5 4.92 2.0 mm HVCT PSE 600V 75C 2020G1 2.0 6.56 2.0 mm HVCT PSE 600V 75C 2020G2 3.0 9.84 2.0 mm HVCT PSE 600V 75C 2020G3 6.0 19.68 2.0 mm HVCT PSE 600V 75C 2020G6 Std. Pack Bulk - Part Numbers - 12034G2-BK 12034G3-BK 12034G6-BK 12030G2-BK 12030G3-BK 12030G6-BK 12032G2-BK 12032G3-BK 12032G6-BK 12040G2-BK 12040G3-BK 12040G6-BK 12020G1-BK 12020G2-BK 12020G3-BK 12020G6-BK Std. Pack 20 13 7 50 30 6 50 30 6 50 30 6 50 50 30 6 L Top View Single Ended Plug Assembly NOTE: Shading Indicates Build to Order -8- Single-Ended Right Angle "T" Latch Plug Power Cord Length M FT Description UL 817 TUV 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 16 AWG ST UL 600V 90C * 16 AWG ST UL 600V 90C * 16 AWG ST UL 600V 90C * 18 AWG ST UL 600V 90C * 18 AWG ST UL 600V 90C * 18 AWG ST UL 600V 90C * 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C Non-Bulk - Part Numbers - Std. Pack Bulk - Part Numbers - Std. Pack 2031LZ2 2031LZ3 2031LZ6 2036LZ2 2036LZ3 2036LZ6 2033LZ2 2033LZ3 2033LZ6 2021LZ2 2021LZ3 2021LZ6 1 1 1 1 1 1 1 1 1 1 1 1 2031LZ2-BK 2031LZ3-BK 2031LZ6-BK 2036LZ2-BK 2036LZ3-BK 2036LZ6-BK 2033LZ2-BK 2033LZ3-BK 2033LZ6-BK 2021LZ2-BK 2021LZ3-BK 2021LZ6-BK 50 30 6 50 30 6 50 30 6 50 30 6 L Double-Ended "T" Latch Plug Power Cord Length Non-Bulk Std. Bulk M FT Description UL 817 TUV CCC * - Part Numbers Pack - Part Numbers 2.0 6.56 12 AWG ST UL 600V 90C 2035KK2 1 2035KK2-BK 3.0 9.84 12 AWG ST UL 600V 90C 2035KK3 1 2035KK3-BK 6.0 19.68 12 AWG ST UL 600V 90C 2035KK6 1 2035KK6-BK 2.0 6.56 14 AWG ST UL 600V 90C * * 2031KK2 1 2031KK2-BK 3.0 9.84 14 AWG ST UL 600V 90C * * 2031KK3 1 2031KK3-BK 6.0 19.68 14 AWG ST UL 600V 90C * * 2031KK6 1 2031KK6-BK 2.0 6.56 16 AWG ST UL 600V 90C * * 2036KK2 1 2036KK2-BK 3.0 9.84 16 AWG ST UL 600V 90C * * 2036KK3 1 2036KK3-BK 6.0 19.68 16 AWG ST UL 600V 90C * * 2036KK6 1 2036KK6-BK 2.0 6.56 18 AWG ST UL 600V 90C * * 2033KK2 1 2033KK2-BK 3.0 9.84 18 AWG ST UL 600V 90C * * 2033KK3 1 2033KK3-BK 6.0 19.68 18 AWG ST UL 600V 90C * * 2033KK6 1 2033KK6-BK 2.0 6.56 1.0 mm H05VVF CE 500/300V 75C 2043KK2 1 2043KK2-BK 3.0 9.84 1.0 mm H05VVF CE 500/300V 75C 2043KK3 1 2043KK3-BK 6.0 19.68 1.0 mm H05VVF CE 500/300V 75C 2043KK6 1 2043KK6-BK 2.0 6.56 1.5 mm H05VVF CE 500/300V 75C * 2047KK2 1 2047KK2-BK 3.0 9.84 1.5 mm H05VVF CE 500/300V 75C * 2047KK3 1 2047KK3-BK 6.0 19.68 1.5 mm H05VVF CE 500/300V 75C * 2047KK6 1 2047KK6-BK 2.0 6.56 2.5 mm 60245 IEC 57 / CCC 500/300V 60C * 2045KK2 1 2045KK2-BK 3.0 9.84 2.5 mm 60245 IEC 57 / CCC 500/300V 60C * 2045KK3 1 2045KK3-BK 6.0 19.68 2.5 mm 60245 IEC 57 / CCC 500/300V 60C * 2045KK6 1 2045KK6-BK 2.0 6.56 1.0 mm HVCT PSE 600V 75C 2023KK2 1 2023KK2-BK 3.0 9.84 1.0 mm HVCT PSE 600V 75C 2023KK3 1 2023KK3-BK 6.0 19.68 1.0 mm HVCT PSE 600V 75C 2023KK6 1 2023KK6-BK 2.0 6.56 1.25 mm HVCT PSE 600V 75C 2025KK2 1 2025KK2-BK 3.0 9.84 1.25 mm HVCT PSE 600V 75C 2025KK3 1 2025KK3-BK 6.0 19.68 1.25 mm HVCT PSE 600V 75C 2025KK6 1 2025KK6-BK 2.0 6.56 2.0 mm HVCT PSE 600V 75C 2021KK2 1 2021KK2-BK 3.0 9.84 2.0 mm HVCT PSE 600V 75C 2021KK3 1 2021KK3-BK 6.0 19.68 2.0 mm HVCT PSE 600V 75C 2021KK6 1 2021KK6-BK Std. Pack 20 13 7 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 50 30 6 L * CCC Pending Top View Double Ended Plug Assembly NOTE: Shading Indicates Build to Order -9- Double-Ended Small Latch Plug Power Cord Length M FT Description UL 817 TUV 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 Non-Bulk - Part Numbers - 12 AWG ST UL 600V 90C 12 AWG ST UL 600V 90C 12 AWG ST UL 600V 90C 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 18 AWG ST UL 600V 90C * * 18 AWG ST UL 600V 90C * * 18 AWG ST UL 600V 90C * * 1.5 mm H05VVF CE 500/300V 75C * 1.5 mm H05VVF CE 500/300V 75C * 1.5 mm H05VVF CE 500/300V 75C * 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C Std. Pack Bulk - Part Numbers - Std Pack 2035G2-BK 2035G3-BK 2035G6-BK 2031G2-BK 2031G3-BK 2031G6-BK 2033G2-BK 2033G3-BK 2033G6-BK 2041G2-BK 2041G3-BK 2041G6-BK 2021G2-BK 2021G3-BK 2021G6-BK 20 13 7 50 30 6 50 30 6 50 30 6 50 30 6 Std. Pack Bulk - Part Numbers - Std. Pack 1 1 1 2052KH2-BK 2052KH3-BK 2052KH6-BK 50 30 6 Bulk - Part Numbers - Std. Pack 2035G2 2035G3 2035G6 2031G2 2031G3 2031G6 2033G2 2033G3 2033G6 2041G2 2041G3 2041G6 2021G2 2021G3 2021G6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 L Top View Double-Ended "T" Latch / IEC C20 Power Cord Length Non-Bulk M FT Description UL 817 TUV* - Part Numbers 2.0 3.0 6.0 6.56 9.84 19.68 14 AWG SJT UL 250V 105C 14 AWG SJT UL 250V 105C 14 AWG SJT UL 250V 105C * * * * * * 2052KH2 2052KH3 2052KH6 * TUV applies only to Saf-D-Grid(R) connector side. L Top View IEC C20 Plug Saf-D-Grid Plug Double-Ended Right Angle "T" Latch / Straight "T" Latch Plug Power Cord Length Non-Bulk M FT Description UL 817 TUV - Part Numbers 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 2.0 3.0 6.0 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 6.56 9.84 19.68 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 14 AWG ST UL 600V 90C * * 16 AWG ST UL 600V 90C * 16 AWG ST UL 600V 90C * 16 AWG ST UL 600V 90C * 18 AWG ST UL 600V 90C * 18 AWG ST UL 600V 90C * 18 AWG ST UL 600V 90C * 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C 2.0 mm HVCT PSE 600V 75C 2031KL2 2031KL3 2031KL6 2036KL2 2036KL3 2036KL6 2033KL2 2033KL3 2033KL6 2021KL2 2021KL3 2021KL6 Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 2031KL2-BK 2031KL3-BK 2031KL6-BK 2036KL2-BK 2036KL3-BK 2036KL6-BK 2033KL2-BK 2033KL3-BK 2033KL3-BK 2021KL2-BK 2021KL3-BK 2021KL6-BK 50 30 6 50 30 6 50 30 6 50 30 6 L NOTE: Shading Indicates Build to Order - 10 - Double-Ended Right Angle "T" Latch / Right Angle "T" Latch Power Cord Length Non-Bulk M FT Description UL 817 TUV - Part Numbers 2.0 6.56 14 AWG ST UL 600V 90C * * 2031LL2 3.0 9.84 14 AWG ST UL 600V 90C * * 2031LL3 6.0 19.68 14 AWG ST UL 600V 90C * * 2031LL6 2.0 6.56 16 AWG ST UL 600V 90C * 2036LL2 3.0 9.84 16 AWG ST UL 600V 90C * 2036LL3 6.0 19.68 16 AWG ST UL 600V 90C * 2036LL6 2.0 6.56 18 AWG ST UL 600V 90C * 2033LL2 3.0 9.84 18 AWG ST UL 600V 90C * 2033LL3 6.0 19.68 18 AWG ST UL 600V 90C * 2033LL6 2.0 6.56 2.0 mm HVCT PSE 600V 75C 2021LL2 3.0 9.84 2.0 mm HVCT PSE 600V 75C 2021LL3 6.0 19.68 2.0 mm HVCT PSE 600V 75C 2021LL6 Std. Pack Bulk - Part Numbers - Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 2031LL2-BK 2031LL3-BK 2031LL6-BK 2036LL2-BK 2036LL3-BK 2036LL6-BK 2033LL2-BK 2033LL3-BK 2033LL6-BK 2021LL2-BK 2021LL3-BK 2021LL6-BK 50 30 6 50 30 6 50 30 6 50 30 6 L Double-Ended Right Angle "T" Latch / Left Angle "T" Latch Power Cord Length Non-Bulk Std. Bulk M FT Description UL 817 TUV - Part Numbers Pack - Part Numbers 2.0 6.56 14 AWG ST UL 600V 90C * * 2031LM2 1 2031LM2-BK 3.0 9.84 14 AWG ST UL 600V 90C * * 2031LM3 1 2031LM3-BK 6.0 19.68 14 AWG ST UL 600V 90C * * 2031LM6 1 2031LM6-BK 2.0 6.56 16 AWG ST UL 600V 90C * 2036LM2 1 2036LM2-BK 3.0 9.84 16 AWG ST UL 600V 90C * 2036LM3 1 2036LM3-BK 6.0 19.68 16 AWG ST UL 600V 90C * 2036LM6 1 2036LM6-BK 2.0 6.56 18 AWG ST UL 600V 90C * 2033LM2 1 2033LM2-BK 3.0 9.84 18 AWG ST UL 600V 90C * 2033LM3 1 2033LM3-BK 6.0 19.68 18 AWG ST UL 600V 90C * 2033LM6 1 2033LM6-BK 2.0 6.56 2.0 mm HVCT PSE 600V 75C 2021LM2 1 2021LM2-BK 3.0 9.84 2.0 mm HVCT PSE 600V 75C 2021LM3 1 2021LM3-BK 6.0 19.68 2.0 mm HVCT PSE 600V 75C 2021LM6 1 2021LM6-BK Std. Pack 50 30 6 50 30 6 50 30 6 50 30 6 L NOTE: Shading Indicates Build to Order - 11 - DC Electrical Power Distribution Systems DC Efficiency DC electrical distribution systems have a basic advantage over AC systems. By eliminating AC to DC conversions a DC distribution system is simpler than an AC system. With less electrical and electronic devices, a DC system can be designed with lower electrical losses and higher reliability. These advantages are further multiplied for systems having DC energy storage for backup power or peak shaving, or a local DC energy source such as photovoltaic cells, wind turbines or fuel cells. Standardization APP(R) has been a leader in the development of system and product safety standards for low voltage DC. We are active on key product and safety committees within the EMerge Alliance(R), NEMA and the IEC. Saf-D-Grid(R) meets or exceeds all relevant industry safety standards. The product has also been successfully tested to new product safety standards under consideration for adoption. On September 26, 2012 the Emerge Alliance(R) board of directors ratified the Emerge Standard for DC Power Distribution Systems (DC-PDS) in Data & Telecom Centers (DTC). Within the Standard, the APP(R) Saf-D-Grid(R) connector system is designated as the interconnection of choice for power strip, power cord and device inlet power connections. DC Arcing AC system voltage phases cause the voltage to pass through zero at some point during the disconnection sequence. This zero crossing significantly reduces the damage to a contact system from an AC arc. DC arcing is more destructive to contact systems due to the lack of phasing to a zero voltage point. The APP(R) Saf-D-Grid(R) connector overcame this technical challenge by using adequate contact mass, arc reducing geometry, and a sacrificial contact tip. Saf-D-Grid(R) has undamaged electrical contact surfaces after 250 DC arcing cycles. DC Safety There is near global acceptance that 380V is the most practical voltage for low voltage DC distribution systems. By using a center-point ground, a +/- 190 volt DC distribution system can be constructed which has lower risk of electrocution than the 200-250 VAC systems installed throughout the world. The system can additionally be made safe by using connectors such as Saf-D-Grid(R), which meet IEC and UL finger probe requirements for touch safety and have a latching system to avoid accidental disconnection. Saf-D-Grid(R) also has adequate voltage isolation to contain arcing from disconnection within the insulating housings. Video of the disconnection of APP(R) Saf-D-Grid(R) connectors under load shows extinguishing of the internal arc well in advance of the connector separation and potential exposure to the user. The Saf-D-Grid(R) connector applies to power supplies and PDU's inside information and communication technology racks. EMerge Alliance is a registered trademark of the EMerge Alliance Industry Association NEMA is a registered trademark of the National Electric Manufacturers Association All Data Subject To Change Without Notice "Saf-D-Grid, APP and Anderson Power Products are registered trademarks of Anderson Power Products" 15709 DS-SDG REV 15 HEADQUARTERS: Anderson Power Products(R), 13 Pratts Junction Road, Sterling, MA 01564-2305 USA T:978-422-3600 F:978-422-0128 * EUROPE: Anderson Power Products(R) Ltd., Unit 3, Europa Court, Europa Boulevard, Westbrook, Warrington, Cheshire, WA5 7TN United Kingdom T: +44 (0) 1925 428390 F: +44 (0) 1925 520203 * ASIA / PACIFIC: IDEAL Anderson Asia Pacific Ltd., Unit 922-928 Topsail Plaza, 11 On Sum Street, Shatin N.T., Hong Kong T:+(852) 2636 0836 F:+(852) 2635 9036 * CHINA: IDEAL Anderson Technologies (Shenzhen) Ltd., Block A8 Tantou Western Industrial Park, Songgang Baoan District, Shenzhen, PR. China 518105 T: +(86) 755 2768 2118 F: +(86) 755 2768 2218 * TAIWAN: IDEAL Anderson Asia Pacific Ltd., Taiwan Branch, 4F.-2, No.116, Dadun 20th St., Situn District, Taichung City 407, Taiwan (R.O.C.) T: +(886) 4 2310 6451 F:+(886) 4 2310 6460 * www.andersonpower.com