ø30mm - TWND Series Switches & Pilot Devices
746 www.IDEC.com 1904041136
Specifications
Conforming to Standards EN60947-5-1, UL508, CSA C22-2 No.14
Approvals
CSA: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbut-
tons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
UL: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbuttons
with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
TÜV: pushbuttons and selector switches: A600 pilot lights and illuminated pushbuttons, direct supply pilot lights and illuminated pushbut-
tons with integral transformer (100/110, 115, 120, 200/220, 230, 240, 380, 400/440, 480V)
Operating Temperature Operation: –25 to +50°C (illuminated versions) -25 ~ +70C non-illuminated
Storage: –40 to +80°C (without freezing) C-> °C
Vibration Resistance 5 to 55Hz, 98m/sec2 (10g) conforming to IEC60068-2-6
Shock Resistance 980m/sec2 (100g) conforming to IEC60068-2-27
Electric Shock Protection Class 2 conforming to IEC60664-1
Degree of Protection IP65 (from front of the panel) (conforming to IEC60529)
UL Type 1, 2, 3, 3R, 3S, 4, 4X, 5, 12, 13 (conforming to NEMA ICS6-110)
Mechanical Life Momentary pushbuttons: 5,000,000 (1800 operations per hour)
All other switches: 500,000
Pollution Degree
(conforming to IEC60947-1) 3
Mechanical-Electrical Specifications
Rated Operational Characteristics AC-15: A600
Rated Insulation Voltage 600V
Rated Impulse Withstanding Voltage
øDielectric Strength
Between live and dead metal parts
2.5kV AC, 1 minute
Rated Thermal Current 10 Amp
Minimum Switching Capacity 5 mA at 3V AC/DC (applicable range may vary with operating conditions and load types)
Contact Operation Slow break NC or NO
Operating Force Flush and extended pushbuttons—with 1NO or 1NC contact: 6.2±2N (momentary), 9.0±1.5N
Additional contacts—1NO or 1NC: +3.0N
Recommended Terminal Torque
Unit Wire Number of Wires Recommended Tightening
Torque (Nm) Terminal Screw
HW-U Contact Block
Crimping Terminal 2 1.0 to 1.3
M3.5
Solid Wire ø0.5 to 1.6 mm (AWG14 to 22) 2 1.0 to 1.3
ø1.7 to 2.0 mm (AWG12) 1 1.2 to 1.3
Stranded Wire 0.3 to 2.0 mm2 (AWG14 to 22) 2 1.0 to 1.3
2.1 to 3.5 mm2 (AWG12) 1 1.2 to 1.3
Illuminated Unit (*1)
Crimping Terminal
2 1.0 to 1.3 M3.5Solid Wire ø0.5 to 1.6 mm (AWG14 to 22)
Stranded Wire 0.3 to 2.0 mm (AWG14 to 22)
Applicable Wire Size Pilot Light
Crimping Terminal
2
0.6 to 1.0 (M3.0)
1.0 to 1.3 (M3.5)
Solid Wire ø0.5 to 1.6 mm (AWG14 to 22)
Stranded Wire ø0.3 to 2.0 mm (AWG14 to 22)
1. * refers to the lamp terminals of the illuminated push buttons and selector switches.
Contact Resistance Initial contact resistance of 50mΩ or less
Contact Gap 4mm (NO and NC)
2mm (NO-EM and NC-LB)
LED Ratings LEDs: 6V: 8mA, 12V: 11mA, 24V: 11mA, 120V: 8.8mA, 240V: 8.6mA
Contact Material Silver
Contact Ratings
Contact Ratings by Utilization Category IEC 60947-5-1 AC-15 (A600)
DC-13 (P600)
Contact Ratings by Utilization Category
Operational Voltage 24V 48V 50V 110V 220V 440V
Operation Current
AC 50/60 Hz AC-12 Control of resistive loads & solid state loads 10A — 10A 10A 6A 2A
AC-15 Control of electromagnetic loads (> 72VA) 10A — 7A 5A 3A 1A
DC DC-12 Control of resistive loads & solid state loads 10A 5A — 2.2A 1.1A —
DC-13 Control of electromagnets 5A 2A — 1.1A 0.6A —