246/247 Series - Timer Delay Relay
DPDT, 4PDT,6PST, 10 Amp
GENERAL SPECIFICATIONS (@ 25° C)
Timing:
Functions Available
Time Range
Timing Adjustment
Timing Repeatability
(Constant voltage and temperature)
Reset Time maximum
Input Pulse Length minimum
Contacts:
Contact Conguration
Contact Material
Contact Rating
120 / 240VAC Resistive
28VDC Resistive
Motor 120VAC
Motor 240VAC
Minimum Contct Load
Contact Resistance, Initial
Coil:
Coils Available
Nominal Coil Power
Input Voltage Tolorance -AC
Input Voltage Tolorance -DC
Transient Protection
Reverse Polarity Protection
Duty
Dielectric Strength:
Across Open Contacts
Between Mutally Insulated Points
Insulation Resistance
Temperature:
Operating
Storage
Life Expectancy:
Electrical (full load operations)
Mechanical (no load operations)
Miscellaneous:
Mounting Position
Mating Socket
Accessories
Enclosure
Weight
On-delay, Off-delay
Up to 10 minutes
Knob
3%
150mS
50mS
DPDT, 4PDT, 6PST
Silver Alloy Gold Diffused
10 Amp / 5 Amp
10 Amp
-
-
500mW
100 milliohms max @ 6VDC, 1A
AC and DC
5VA 2.5W
85% to 110% of nominal
80% to 110% of nominal
Yes
Yes
Continuous
500Vrms
1500Vrms
1,000 Mohms min @ 500VDC
-20 to 70°C (-4 to 158°F)
-40 to 105°C (-40 to 221°F)
100,000
10,000,000
Any
12 pin =27390, 27390D
14 pin = 33377, 33377D
Hold down clip integral to relay
Clear Polycarbonate
8.6oz (244 grams)
Industrial Pin Out
Rugged, industrial time delay versions of the popular 219 series. Contacts can be congured up
to four pole double throw or six pole single throw. Time ranges are adjustable over a 1:10 range.
Knob adjustment and integral hold down clip are standard. A large option list makes this product
easily customized for special applications.
with socket
www.struthers-dunn.com (843) 664-3303
7/9
246/247 Contact Load Specications
Voltage Make Carry Resistive Inductive
120VAC 30 Amp 10 Amp 10 Amp 3 Amp
240VAC 30 Amp 10 Amp 5 Amp 1 Amp
24VDC 30 Amp 10 Amp 10 Amp 5 Amp
28VDC 30 Amp 10 Amp 10 Amp 3 Amp
125VDC 30 Amp 10 Amp 0.5 Amp 0.1 Amp
For versions with sufx “69” permant magnet blowouts
Voltage Make Carry Resistive Inductive
125VDC (SM) 30 Amp 10 Amp 1.5 Amp 0.5 Amp
125VDC (DM) 30 Amp 10 Amp 4 Amp 1.5 Amp
250VDC (SM) 30 Amp 10 Amp 0.5 Amp 150 mAmp
250VDC (DM) 30 Amp 10 Amp 1.5 Amp 0.5 Amp
Note: SM = Single make
DM = Double make
E13224
Section 7
Timer / Sensor - Time Delay & Sensor Relays
5 - 25 Amp
246/247 Wire Diagram
247XBX
246XBX
246ABA
246BBX
247XCX
Ordering Code 247 XBX P -010 120VAC
Series
246 - On delay plug-in
247 - Off delay plug-in
Contact Arrangement
XBX (DPDT) - (2 form C)
XCX (3PDT) - (3 form C)
ABA (1 form A & 2 form C & 1 form B)
BBX (2 form A & 2 form C) 246 only
FXX (6 form A) 246 only
Standard Features
Blowout magnet - CODE 69
Bifurcated Contacts (5 Amps max) - CODE 33
Plug in with polycarbonate cover - CODE P
Indicator Lamp - CODE L
Manual Actuator - CODE M
Timing Ranges
0.1 - 1.0 Seconds - CODE 001
0.2 - 2.0 Seconds - CODE 002
1.0 - 10 Seconds - CODE 010
3.0 - 30 Seconds - CODE 033
6.0 - 60 Seconds - CODE 060
18 - 180 Seconds - CODE 180
30 - 300 Seconds - CODE 300
Adjustment Options
Adjustment knob - No CODE
Fixed - Timing code does not apply. Example - 3f = 3 seconds
CODE F (ie 3F) - 3 Seconds
Remote adjustment (Ext. pot required) - CODE R
Operating Voltage
AC: 24, 120, 240, (Add VAC)
DC: 12, 24, 115-125 (Add VDC)
235 46 1
8911 1012 7
2.45
(62.3)
1.55
(39.4)
0.67
(17.2)
3.75
(95.2)
1.46
(37.2)
0.80
(20.3)
2.63
(66.8)
Outline Dimensions
Dimensions Shown in inches & (millimeters)
12
1
11
2
10
3
9
4
8
5
7
6
12
1
11
2
10
3
9
4
8
5
7
6
12
1
11
2
10
3
9
4
8
5
7
6
12
1
11
2
10
3
9
4
8
5
7
6
12
1
11
2
10
3
9
4
8
5
7
6
External Trigger pins 5 & 6
7/10
www.struthers-dunn.com (843) 664-3303