2Specifications are subject to change without notice (25.09.06)
Mode of Operation
DIB71 monitors both AC and
DC over or under current
through an internal shunt.
Example 1
(connection between termi-
nals Z1, Y1 - latching func-
tion enabled)
The relay operates and latch-
es in operating position
when the measured value
exceeds (or drops below) the
set level for morethan the
set delay time. Provided that
the current has dropped
below (or has exceeded) the
set point (see hysteresis set-
ting), the relay releases when
the interconnection between
terminals Z1, Y1 is interrupt-
ed or the power supply is
interrupted as well.
The red LED flashes until the
delay time has expired or the
measured value comes back
to a non-alarm value (see
hysteresis setting).
Example 2 (Stardard CT)
(no connection between ter-
minals Z1, Y1 - latch func-
tion disabled)
The relay operates when the
measured value exceeds (or
drops below) the set level for
more than the set delay time.
It releases when the current
drops below (or exceeds) the
set level (see hysteresis set-
ting) or when power supply
is interrupted.
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
DIB71
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1, A2 or A3, A2
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage
Supply to input 4 kV (1.2/50 µs)
Supply to output 4kV (1.2/50 µs)
Input to output 4 kV (1.2/50 µs)
Rated operational power
AC 3 VA
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 100 ms
Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 3
Operating temperature
5A -20 to 50°C, R.H. < 95%
others -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions 35.5 x 81 x 67.2 mm
Material PA66
Weight Approx. 150 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA
CE Marking Yes
EMC
Electromagnetic Compatibillity
Immunity According to EN 61000-6-2
Emission According to EN 61000-6-3
General Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2)µ
Resistive loads AC 1 5 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life ≥30 x 106operations
Electrical life ≥105operations
(at 5 A, 250 V, cos ϕ=1)
Operating frequency ≤7200 operations/h
Dielectric strength
Dielectric voltage
2kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications