Miniature Fuses
Miniature Fuses
MI74 12/04
Axial leads
5x20
250V - FC “AL” Fast Acting
Dimensions
Electricals characteristics :
according to IEC 127-2 Standard Sheet 1
Sand-filled fuses
Max weight : 1,5 g
73 mm
Ø 0,8 mm
5,1 + 0,1 mm
20,0 ± 0,5 mm
23 mm maxi
Basic Characteristics
Size
mm VAC A A2sV
Rated
Voltage
Rated
Current Reference
Number
Catalog
Number
Breaking
Capacity
Designation
[I2t]
Pre-arcing
[I2t]
Total
clearing at
250 V
Max voltage
drop at
In
0,0011 0,0025
0,0018 0,004
0,0035 0,008
0,0072 0,016
0,015 0,032
0,032 0,066
0,052 0,082
0,098 0,16
0,2 0,32
0,11 0,35
0,28 0,55
0,55 1,2
1,1 2,4
2,5 5
6,1 12
11 22
25 45
72 130
150 270
250V FC 0,160 A 5x20 AL
250V FC 0,200 A 5x20 AL
250V FC 0,250 A 5x20 AL
250V FC 0,315 A 5x20 AL
250V FC 0,400 A 5x20 AL
250V FC 0,500 A 5x20 AL
250V FC 0,630 A 5x20 AL
250V FC 0,800 A 5x20 AL
250V FC 1,000 A 5x20 AL
250V FC 1,250 A 5x20 AL
250V FC 1,600 A 5x20 AL
250V FC 2,000 A 5x20 AL
250V FC 2,500 A 5x20 AL
250V FC 3,150 A 5x20 AL
250V FC 4,000 A 5x20 AL
250V FC 5,000 A 5x20 AL
250V FC 6,300 A 5x20 AL
250V FC 8,000 A 5x20 AL
250V FC 10,00 A 5x20 AL
L205032
M205033
N205034
E206061
F206062
P205035
H206064
G206063
Q205036
R205037
S205038
T205039
V205040
W205041
X205042
Y205043
Z205044
A205045
B205046
MI5FCP25V0,16
MI5FCP25V0,20
MI5FCP25V0,25
MI5FCP25V0,31
MI5FCP25V0,4
MI5FCP25V0,5
MI5FCP25V0,63
MI5FCP25V0,8
MI5FCP25V1
MI5FCP25V1,25
MI5FCP25V1,6
MI5FCP25V2
MI5FCP25V2,5
MI5FCP25V3,15
MI5FCP25V4
MI5FCP25V5
MI5FCP25V6,3
MI5FCP25V8
MI5FCP25V10
0,160
0,200
0,250
0,315
0,400
0,500
0,630
0,800
1,000
1,250
1,600
2,000
2,500
3,150
4,000
5,000
6,300
8
10
1,6
1,45
1,3
1,15
1,1
1
0,45
0,4
0,37
0,55
0,42
0,38
0,34
0,28
0,23
0,21
0,18
0,13
0,11
BETWEEN 0,16 TO 10A
These fuses are not SEMKO approved. IEC 127 doesn’t take into account 5x20 fuses with axial leads.
5 x 20
250
Along
IEC 127
1500 A
@ 250 VAC
cos ϕ0,7
Along
IEC 269.1
and 269.3
6 kA
@ 250 VAC
cos ϕ0,2
Miniature Fuses
Miniature Fuses
MI75
12/04
Axial leads
5x20
250V - FC “AL” Fast Acting
I margin ± 12 %. Actual prearcing time(s). R.M.S. Value of prearcing current (A).
Time-current characteristics
83,5
63 mm
LT15,6 m
10
6
78 labelling
Ø 360 mm
Ø 31,5 mm
Installation instruction
Soldering heat resistance : according IEC 68-2-20 / 260°C for 10 seconds.
Material:
Body: ceramic tube
Connection: Tin plated copper
100 mA
200 mA
250 mA
315 mA
400 mA
500 mA
650 mA
800 mA
1 A
125 mA
16 A
2 A
25 A
315 mA
4 A
6,3 A
8 A
10 A
Packaging: in tape per 2000 pieces
250V FC 5x20 AL 250V FC 5x20 AL