NC1V
Circuit Protectors
2
(2-pole) (3-pole)
Finger-safe, spring-up terminals reduce
wiring time.
Ring terminal tabs can be installed easily, and screws are
held secure.
Retractable Actuator
The actuator retracts when the circuit protector turns on.
Inadvertent operation, due to touching the actuator, is
prevented. Status of the circuit protector can easily be
confirmed by viewing the position of the actuator.
Slim Housing Saves Space
ON OFF
78.8 mm
Main Circuit Terminals are Fingersafe
(IP20)
Spring-up, fingersafe structure requires no terminal cover.
1-pole 17.5mm Wide
2-pole 35.0mm Wide
3-pole 52.5mm Wide
17.5 mm 35.0 mm 52.5 mm
Auxiliary/alarm contact terminals
are equipped with terminal covers.
Auxiliary/Alarm Contact Terminals are
Equipped with a Terminal Cover
Voltage coil terminals on the relay trip version are also
equipped with a terminal cover as standard.
IDEC's original Spring-up Terminals and Cover
Provide IP20 Finger-safe Protection.
(1-pole)
Retractable
Actuator
3
Auxiliary/Alarm Contact, and Relay Trip Voltage
Coil Terminals are Equipped with a Terminal Cover.
35mm-wide DIN Rail Mounting
or Direct Panel Mounting
Distinguishing Characteristics
Wide variety of rated currents and tripping curves.
One and 2-pole models are AC/DC compatible and
allow for a reduction in inventory.
Rated Short-circuit Capacity 2500A
Available with Inertia Delay
Allows for use with large inrush currents such as
motors and lamps.
Safe Trip-free Mechanism
The circuit remains open even when the operator is turned
on after tripping (unit must be manually reset after
removing the cause of the tripping).
Available with Auxiliary or Alarm Contacts
Conforms to various international
standards
ON OFF Tripped
After tripping, the retractable actuator is
in the middle position.
Circuit protector must be turned off before it can be reset.
Auxiliary or Alarm Contact
(Shown without terminal cover.)
4
NC1V Circuit Protectors
IDEC’s original spring-up, fingersafe terminals enhance reliability and safety.
• Integrated electric shock protection structure (IP20).
• Auxiliary/alarm contact terminals and voltage coil terminals on
the relay trip types are equipped with terminal covers.
• Spring-up, fingersafe terminals reduce wiring time.
• Ring terminals can be installed. Captive terminal screws.
• Available with inertia delay
• Available with auxiliary or alarm contacts
• Rated short-circuit capacity: 2500A
• Slim, space-saving housing
1-pole: 17.5mm wide
2-pole: 35.0mm wide
3-pole: 52.5mm wide
• Retractable actuator
• The trip-free mechanism maintains the circuit open even
when the operator is turned on after tripping.
Applicable Standards Certification Mark Certification Organization
(File No.)
UL1077 E68029
CSA C22.2 No. 235 LR83454
EN60934
B07 09 13332 063
European Commission's
Low Voltage Directive
GB17701-1999 No. 2008010307265840
Electrical Applicance and
Material Safety Law
Technical Standard
Series Trip
JET
Relay Trip
Specifications
Operator Style Retractable actuator
Internal Circuit Series trip (current trip), Relay trip (voltage trip)
Protection Method Hydraulic magnetic tripping system, Magnetic tripping system (voltage trip)
No. of Poles 1-pole 2-pole 3-pole
Rated Voltage (AC/DC) (Note 1) 250V AC 50/60Hz, 65V DC 250V AC 50/60Hz, 125V DC 250V AC, 50/60Hz
Series Trip
(Current Trip)
Rated Short-circuit
Capacity
250V AC, 2500A
65V DC, 2500A
250V AC, 2500A
125V DC, 2500A 250V AC, 2500A
Rated Current 0.1A, 0.3A, 0.5A, 1A, 2A, 3A, 5A, 7A, 10A, 15A, 20A, 25A, 30A
Operation Characteristics
(Note 2)
Time delay curve curve M (slow), curve A (medium), S (instantaneous)
Curves M and A are avilable with inertia delay.
Relay Trip
(Voltage Trip)
(Note 3)
Rated Current 30A
Trip Voltage 24 to 48V DC (at 25°C)
Voltage application duration 10 sec maximum, tripping time 0.1 sec maximum (at rated voltage)
Auxiliary Contact/
Alarm Contact
Contact Rating 125V AC 3A (resistive load), 30V DC 2A (resistive load)
Minimum Applicable Load 24V DC 1mA (resistive load, reference value)
Insulation Resistance 100 MΩ minimum (500V DC megger)
Dielectric Strength
2000V AC, 1 minute (between terminals when main contacts are open, between live parts of different
poles, between live and dead parts)
600V AC (between terminals when auxiliary circuits are open)
Vibration Resistance
(with rated current applied)
Damage limits: 147 m/s2 (10 to 55 Hz) (1-pole, 2-pole), 78 m/s2 (3-pole)
Operating extremes: 98 m/s2 (1-pole, 2-pole), 78 m/s2 (3-pole)
Shock Resistance
(S time delay curve: 80% rated current,
A, M time delay curve: 100% rated current)
Damage limits: 490 m/s2 (1-pole, 2-pole), 297 m/s2 (3-pole)
Operating extremes: 196 m/s2 (S, A, M types)
Electrical Life 10,000 cyles minimum (at rated curent), 10 operations per minute
Reference Temperature 40°C
Operating Tempperature
−10 to +60°C (no freezing)
Rated current is based on an ambient temperature of 40°C. When the operating temperature exceeds
40°C, derate the rated current by using the factors shown below.
Operating Humidity 45 to 85% RH (no condensation)
Terminal Style
Main Circuit Terminal Spring-up, fingersafe terminal: M4 screw (up to 20A), M5 screw (25A and 30A)
Auxiliary/Alarm Contacts,
Voltage Coil Terminal M3.5 screw
Weight (approx.) 1-pole: 90g, 2-pole: 170g, 3-pole: 260g
Operating Temp. Derating Factor
50°C 0.9
55°C 0.8
60°C 0.7
Note 1: 3-pole type is for AC voltage only.
Note 2: For S (instantaneous) tripping curve, humming sound may be caused when used in an AC sinusoidal-wave current circuit around 80% of
the rated current, however, the performance of the circuit protector will not be affected.
To avoid unnecessary tripping, do not use in circuits where inrush currents may be present.
Note 3: Relay trip (voltage trip) type is not equipped with an overcurrent trip function.
• Do not use the NC1V circuit protectors in environments where they are exposed to extreme temperature, humidity, dust, corrosive gases,
vibration, shock, or in a circuit where inrush current may be present, otherwise unnecessary operations and damage may occur.
Note: TÃœV, CE, and CCC marks are applicable for series trip type only.
5
Auxiliary/Alarm Contacts
00: None
11: With one auxiliary contact
12: With two auxiliary contacts
13: With three auxiliary contacts
21: With one alarm contact
31: With one auxiliary contact and one alarm contact
32: With two auxiliary contacts and one alarm contact
NC1V Circuit Protectors
Type No. Development
Types
• Specity rated current, time delay curve, or voltage trip coil voltage in place of 6 7 8
in the Ordering Type No.
Internal
Circuit
No. of
Poles
Inertia
Delay
Auxiliary Contact
Alarm Contact Ordering Type No. Applicable Standards
Code
6 Rated
Current 7 Time Delay
Curve 8 Voltage Trip
Coil Voltage
Series Trip
(Current Trip)
1-pole
–
—NC1V-1100- 6 7
0.1A
0.3A
0.5A
1A
2A
3A
5A
7A
10A
15A
20A
25A
30A
M (slow)
A (medium)
S (instantaneous) —
One Auxiliary Contact NC1V-1111- 6 7
One Alarm Contact NC1V-1121 6 7
With
—NC1V-1100F- 6 7
One Auxiliary Contact NC1V-1111F- 6 7
One Alarm Contact NC1V-1121F- 6 7
2-pole
—
—NC1V-2100- 6 7
One Auxiliary Contact NC1V-2111- 6 7
Two Auxiliary Contacts NC1V-2112- 6 7
One Alarm Contact NC1V-2121- 6 7
One Auxiliary Contact
and One Alarm Contact NC1V-2131- 6 7
With
—NC1V-2100F- 6 7
One Auxiliary Contact NC1V-2111F- 6 7
Two Auxiliary Contacts NC1V-2112F- 6 7
One Alarm Contact NC1V-2121F- 6 7
One Auxiliary Contact
and One Alarm Contact NC1V-2131F- 6 7
3-pole
—
—NC1V-3100- 6 7
One Auxiliary Contact NC1V-3111- 6 7
Two Auxiliary Contacts NC1V-3112- 6 7
Three Auxiliary Contacts NC1V-3113- 6 7
One Alarm Contact NC1V-3121- 6 7
One Auxiliary Contact
and One Alarm Contact NC1V-3131- 6 7
Two Auxiliary Contacts
and One Alarm Contact NC1V-3132- 6 7
With
—NC1V-3100F- 6 7
One Auxiliary Contact NC1V-3111F- 6 7
Two Auxiliary Contacts NC1V-3112F- 6 7
Three Auxiliary Contacts NC1V-3113F- 6 7
One Alarm Contact NC1V-3121F- 6 7
One Auxiliary Contact
and One Alarm Contact NC1V-3131F- 6 7
Two Auxiliary Contacts
and One Alarm Contact NC1V-3132F- 6 7
Relay Trip
(Voltage Trip)
1-pole
——
NC1V-1500- 8
— — DC24V2-pole NC1V-2500- 8
3-pole NC1V-3500- 8
Note: Inertia delay is for AC circuit. Also, time delay curve of S (instantaneous) is not available with inertia delay.
NC1V - 2 1 00 F - 30A A DC24V
Type
NC1V: Flap actuator type
DIN rail and panel mounting
Voltage Trip Coil Voltage
DC24V: 24-48V DC
∗ Specified for relay trip only.
Time Delay Curve
M: Slow
A: Medium
S: Instantaneous
∗ For both AC/DC.
∗ Specified for series trip only.
Rated Current
0.1A, 0.3A, 0.5A, 1A, 2A, 3A,
5A, 7A, 10A 15A, 20A, 25A, 30A
∗ Specified for series trip only.
Inertia Delay
Blank: Without
F: With
∗ Inertia delay is for AC voltage only.
∗ Available with medium and slow types
(not applicable with relay trip).
No. of Poles
1: 1-pole
2: 2-pole
3: 3-pole
Internal Circuit
1: Series trip (current trip)
5: Relay trip (voltage trip) 6
5
7
8
1
2
3
4
6
Internal Circuit
• 1-pole
NC1V-1100
(Without auxiliary/alarm contacts)
NC1V-1111
(With auxiliary contact)
NC1V-1121
(With alarm contact)
NC1V-1500
(Relay Trip)
NC1V-2100
(Without auxiliary/alarm contacts)
NC1V-2111
(With auxiliary contact)
NC1V-2121
(With alarm contact)
NC1V-2500
(Relay Trip)
NC1V-3100
(Without auxiliary/alarm contacts)
NC1V-3111
(With auxiliary contact)
NC1V-3121
(With alarm contact)
NC1V-3500
(Relay Trip)
LOAD
LINE
LOAD
LINE
LOAD
LINE
N
C
N
O
C
LOAD
LINE
LOAD
LINE
LOAD
LINE
N
C
N
O
C
LOAD
LINE
LOAD
LINE
LOAD
LINE
D
C
B
A
D
C
B
A
D
C
B
A
Overcurrent-Time Delay Characteristics (sec at 40°C) [vertical mounting]
Item Time Delay Curve Percent of Rated Current
100% 125% 150% 175% 200% 400% 600% 800% 1000%
AC (50/60 Hz)/DC
S (instantaneous) NO TRIP —∗0.005
to 0.1
0.003
to 0.06
0.0027
to 0.05
0.002
to 0.03
0.002
to 0.028
0.002
to 0.025
0.002
to 0.022
A (medium) NO TRIP ∗25 to 240 16 to 140 —6 to 32 0.4 to 4 0.0055
to 1.5
0.004
to 0.8
0.004
to 0.65
M (slow) NO TRIP ∗60 to 600 30 to 200 —9 to 60 0.4 to 10 0.006
to 4.5
0.004
to 1.8
0.004
to 0.8
AC (50/60 Hz)
With Inertia Delay
A (medium) NO TRIP 25 to 240 ——
6 to 32 0.8 to 6 0.09
to 3.5
0.02
to 1.8
0.01
to 1.0
With Inertia Delay
M (slow) NO TRIP 60 to 600 ——
10 to 60 0.8 to 10 0.06
to 4.5
0.02
to 3
0.01
to 1.75
LINE
LOAD
D
C
B
A
N
C
N
O
C
LINE
LOAD N
C
N
O
C
LINE
LOAD
N
C
N
O
C
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD N
C
N
O
C
LOADLOAD
LINELINE
A
B
C
DD
C
B
A
One auxiliary contact. Also available
with two or three auxiliary contacts.
One alarm contact.
• 2-pole
Note: Those with two auxiliary contacts and with one auxiliary contact and one alarm contact have been applied for UL and CCC.
Note: Those with two or three auxiliary contacts, with one auxiliary contact and one alarm contact, and with two auxiliary contacts and one alarm
contacts have been applied for UL and CCC.
• 3-pole
One alarm contact.
Also available with one
auxiliary contact and
one alarm contact.
One alarm contact. Also available with one
auxiliary and one alarm contacts, and two
auxiliary and one alarm contacts.
One auxiliary contact.
∗: MAY TRIP on DC
NC1V Circuit Protectors
One auxiliary contact.
Also available with two
auxiliary contacts.
7
NC1V Circuit Protectors
Time Delay Curves at 40°C
1000
100 200 300 400 500 600 700 800 900 1000
125
100
10
1
0.1
0.01
Curve A
(medium)
AC
DC (Note)
Current (percent load of the rated current)
1000
100 200 300 400 500 600 700 800 900 1000
125
100
10
1
0.1
0.01
AC
Curve S
(instantaneous)
DC (Note)
Current (percent load of the rated current)
Time in sec
Current (percent load of the rated current)
1000
100 200 300 400 500 600 700 800 900 1000
125
100
10
1
0.1
0.01
Curve A
(medium)
With Inertia Delay
Time in sec
Current (percent load of the rated current)
1000
100 200 300 400 500 600 700 800 900 1000
125
100
10
1
0.1
0.01
Curve M
(slow)
With Inertia Delay
Time in sec
Current (percent load of the rated current)
Note: The entire shaded area applies to AC.
For DC, the shaded area on the right of the dashed line applies.
Time in sec
100 200 300 400 500 600 700 800 900 1000
125
1000
100
10
1
0.1
0.01
Curve M
(slow)
AC
DC (Note)
Time in sec
8
NC1V Circuit Protectors
Time Delay Curve and Ambient
Temperature
NC1V circuit protectors employ an electromagnetic tripping
system, where the rated current (trip current) is not affected
by ambient temperatures. But the time delay may vary with
the oil viscosity in the oil dash pot. Lower oil viscosity at
higher temperatures results in a shorter delay, whereas at
lower temperatures the delay will be longer.
Temperature Correction Curve
The time delay curves on the preceding page are measured
at 40°C. With reference to the following curves, time delays
can be corrected according to ambient temperature.
60
40
200
300
400
500
600
100
706050400-10
Ambient Temperature (°C)
Change of Time Delay (%)
-20 30
80
10 20
Inertia Delay
Inertia delay is designed not to trip on a non-repeating
single pulse of 20 times the rated current (peak value) for a
duration of 8 ms. In addition, circuit protectors equipped
with inertia delay do not respond to high inrush currents
caused by transformer or lamp loads, but perform the
specified interruption on the subsequent overcurrents.
Inertia delay is available on AC circuits, and is not available
with the series trip curve S (instantaneous).
123456 89107
2000
4000
6000
8000
10000
12000
Pulse Width
(
ms
)
1. Percent of rated current
Pulse peak current
Protector rated current
2. Sinusoidal or parabolic pulse
×100
Pulse peak current
Pulse width (Duration)
Percent of Rated Current (%)
Rated
Current
For AC 50/60 Hz
Impedance (Ω)
For DC
Resistance (Ω)
Curve S Curves A, M Curve S Curves A, M
0.1A 66.0 116.0 43.0 106.0
0.3A 6.6 11.0 4.1 10.0
0.5A 1.92 3.65 0.86 3.40
1A 0.50 0.93 0.25 0.90
2A 0.16 0.27 0.11 0.25
3A 0.07 0.12 0.050 0.11
5A 0.025 0.050 0.015 0.045
7A 0.014 0.027 0.011 0.025
10A 0.007 0.021 0.005 0.020
15A 0.006 0.010 0.005 0.009
20A 0.005 0.006 0.004 0.005
25A 0.004 0.005 0.004 0.005
30A 0.003 0.004 0.003 0.004
The time delay is based on an ambient temperature of
40°C. Time delays at other temperatures are corrected
according to the temperature correction curve. The time
delay of the instantaneous time delay curve (S) is not
affected by the ambient temperature.
Tolerance: ±25% (up to 20A),
±50% (25A and 30A)
Impedance and Coil Resistance
• Series Trip (Current Trip) at 25°C
Voltage Drop Due to Coil Resistance or Impedance
The internal resistance or impedance of a circuit protector
tends to be larger for a smaller rated current. Therefore,
when circuit protectors of a small rated current are used,
voltage drop should be taken into consideration. Internal
resistance also varies with time delay curves, which should
also be considered during installation.
• Relay Trip (Voltage Trip) at 25°C
Tripping Voltage For DC
Resistance (Ω)
24-48V 100.0
Tolerance: ±25%
When operating temperature
exceeds 40°C, derate the rated
current by multiplying the derating
factor shown on the right.
Operating
Temp.
Derating
Factor
50°C 0.9
55°C 0.8
60°C 0.7
9
NC1V Circuit Protectors
Dimensions
• 1-pole
NC1V-1100
12.0 6.6 66.0
48.3
78.8
5.0
33.0
17.5
56.0
71.4
44.0
72.5
M4 Terminal Screw
(up to 20A)
M5 Terminal Screw
(25A or more)
DIN Rail (BNDN1000)
2-ø4.5 Holes
(for screw mounting)
ON
Mounting Hole Layout
(M4 Mounting Screws)
12
71.4
2-M4
NC1V-1111
(Auxiliary Contact)
NC1V-1121
(Alarm Contact)
72.5
48.4
71.4
56.0
17.5 33.0
5.0
78.8
48.3
66.06.6
12.0
2-ø4.5 Holes
(for screw mounting)
DIN Rail (BNDN1000)
Terminal Cover
M4 Terminal Screw
(up to 20A)
M5 Terminal Screw
(25A or more)
M3.5 Terminal Screw
ON
NC1V-1500
(Relay Trip)
72.5
48.4
71.4
56.0
17.5 33.0
5.0
78.8
48.3
66.06.6
12.0
2-ø4.5 Holes
(for screw mounting)
DIN Rail (BNDN1000)
M5 Terminal Screw (30A)
M3.5 Terminal Screw
Terminal Cover
ON
• 2-pole
NC1V-2100
29.5
35.0
56.0
71.4
6.6 66.0
48.3
78.8
5.0
33.0
44.0
72.5
M4 Terminal Srew
(up to 20A)
M5 Terminal Screw
(25A or more)
2-ø4.5 Holes
(for screw mounting)
DIN Rail (BNDN1000)
ON
Mounting Hole Layout
(M4 Mounting Screws)
29.5
71.4
2-M4
All dimensions in mm.
10
• 2-pole
NC1V-2111
(one auxiliary contact)
NC1V-2112
(two auxiliary contacts)
NC1V-2121
(one alarm contact)
NC1V-2131
(one auxiliary contact
and one alarm contact)
29.5
56.0
71.4
35.0
72.5
48.4
33.0
5.0
78.8
48.3
66.06.6
DIN Rail (BNDN1000)
M4 Terminal Screw
(up to 20A)
M5 Terminal Screw
(25A or more)
2-ø4.5 Holes
(for screw mounting)
Terminal Cover
M3.5 Terminal Screw
ON
Mounting Hole Layout
(M4 Mounting Screws)
29.5
71.4
2-M4
NC1V-2500
(Relay Trip)
35.0
71.4
56.0
29.5
72.5
48.4
33.0
5.0
78.8
48.3
66.06.6
DIN Rail (BNDN1000)
M5 Terminal Screws (30A)
2-ø4.5 Holes
(for screw mounting)
M3.5 Terminal Screw
Terminal Cover
ON
NC1V-3100
47.0
52.5
56.0
71.4
6.6 66.0
48.3
78.8
5.0
33.0
44.0
72.5
DIN Rail (BNDN1000)
2-ø4.5 Holes
(for screw mounting)
M4 Terminal Screw
(up to 20A)
M5 Terminal Srew
(25A or more)
ON Mounting Hole Layout
(M4 Mounting Screws)
47.0
2-M4
71.4
NC1V-3111
(one auxiliary contact)
NC1V-3112
(two auxiliary contacts)
NC1V-3113
(three auxiliary contacts)
NC1V-3121
(one alarm Contact)
NC1V-3131
(one auxiliary contact
and one alarm contact)
NC1V-3132
(two auxiliary contacts
and one alarm contact)
71.4
56.0
52.5
47.0
72.5
48.4
33.0
5.0
78.8
48.3
66.06.6
M3.5 Terminal Srew
DIN Rail (BNDN1000)
2-ø4.5 Holes
(for screw mounting)
M4 Terminal Screw
(up to 20A)
M5 Terminal Srew
(25A or more)
Terminal Cover
ON
NC1V Circuit Protectors
• 3-pole
The dimensions are for NC1V-2111 and NC1V-2121.
The dimensions are for NC1V-3111 and NC1V-3121.
11
• 3-pole
NC1V-3500
(Relay Trip)
47.0
52.5
56.0
71.4
72.5
48.4
33.0
5.0
78.8
48.3
66.06.6
DIN Rail (BNDN1000)
2-ø4.5 Holes
(for screw mounting)
M5 Terminal Screw (30A)
Terminal Cover
M3.5 Terminal Screw
ON
Mounting Hole Layout
(M4 Mounting Screws)
47.0
2-M4
71.4
Instructions
• Installation Angle
Tripping method is hydraulic magnetic. Minimum operating
current varies with installation angle. Operating currents
are influenced by the weight of movable iron core. With
reference to the following figures, correct the rated current.
Latch
Flat
Srcrewdriver
Push
35mm-wide
DIN Rail
35mm-wide
DIN Rail
RemovingInstalling
NC1V Circuit Protectors
Minimum operating current is calculated from the following
formula:
(Minimum operating current) = (Rated current) ×
(Correction factor by installation angle) × (Reference
minimum tripping current rate)
• DIN Rails
[Installation on DIN Rail]
1. Fasten the DIN rail securely.
2. With the latch facing downward, install the NC1V circuit
protector on the DIN rail as shown below.
[Removal from DIN Rail]
Using a flat screwdriver, pull the latch on the circuit
protector to remove from the DIN rail.
120% 90%
100%
100%
Installation of Auxiliary/Alarm Terminal Cover
After wiring the terminals, install the terminal cover by
aligning with the circuit protector as shown below.
Terminal cover installed
All dimensions in mm.
• Applicable Wire and Crimp Terminal
Terminal Terminal Screw Connectable
Wire Size
(mm2)
Applicable
Crimping
Terminal
Tightening
Torque
(N·m)
Main Circuit
Terminals
Spring-up, fingersafe,
slotted Phillips screw
with square washer
(up to 20A)
0.25 to 1.65 R1.25-4
1 to 1.41.04 to 2.63 R2-4
2.63 to 6.64 R5.5-4
Spring-up fingersafe
terminal
(25A and 30A)
0.25 to 1.65 R1.25-5
1.8 to 2.21.04 to 2.63 R2-5
2.63 to 6.64 R5.5-5
Auxiliary Contact
Alarm Contact
Voltage Coil
Terminals
Slotted Phillips screw
with square washer
0.25 to 1.65 R1.25-3.5
0.7 to 0.9
1.04 to 2.63 R2-3.5
• For wiring the main circuit terminal, use the applicable crimp terminals and
tighten to the recommended torque.
• When using the NC1V circuit protector as CSA-certified product, use with CSA-
certified crimp terminal.
• When using the NC1V circuit protector as UL-listed product, use with UL-listed
crimp terminal.
Panel Mounting Screw (not supplied)
Srew Type Tightening Torque Shape
M4 0.8 to 1.0 N·m
Product Markings (Example: NC1V-1111-30AA)
Spring Washer
Plain Washer
PSE Certification
Reference Operating
Temperature
Auxiliary/Alarm Contact Rating
Time Delay Curve
No. of Poles
Certification Marks
Rated Current
Type No.
Rated Voltage
JAPAN
LINE
LOAD
30A
E
S
P
220VAC
I.C.2500A
J E T
POLE 1
In 30A
CIRCUIT PROTECTOR
Suppl. Prot.
A.T. 40°C
CURVE A
Ue 250VAC 50/60Hz · 65VDC
NC1V-1111
AUX. SW
125VAC 3A
30 VDC 2A
Accessories
• DIN Rail
35mm-wide DIN Rails
Length Part No. Material
1000mm BNDN1000 Aluminum
Part No. Applicable Rail Material Package Quantity
BNL6 BNDN1000 Galvanized Trivalent
Chromate Treatment 10
Type No. Material Package Quantity
NC1V-AUX-CV Nylon (PA66) 1
• Auxiliary/Alarm Terminal Cover
NC1V Circuit Protectors
• End Clip
IDEC CORPORATION (USA)
1175 Elko Drive, Sunnyvale, CA 94089-2209, USA
Tel: +1-408-747-0550 / (800) 262-IDEC (4332)
Fax: +1-408-744-9055 / (800) 635-6246
E-mail: opencontact@idec.com
IDEC CANADA LIMITED
3155 Pepper Mill Court, Unit 4, Mississauga,
Ontario, L5L 4X7, Canada
Tel: +1-905-890-8561, Toll Free: (888) 317-4332
Fax: +1-905-890-8562
E-mail: sales@ca.idec.com
IDEC AUSTRALIA PTY. LTD.
2/3 Macro Court, Rowville, Victoria 3178, Australia
Tel: +61-3-9763-3244, Toll Free: 1800-68-4332
Fax: +61-3-9763-3255
E-mail: sales@au.idec.com
IDEC ELECTRONICS LIMITED
Unit 2, Beechwood, Chineham Business Park,
Basingstoke, Hampshire RG24 8WA, UK
Tel: +44-1256-321000, Fax: +44-1256-327755
E-mail: sales@uk.idec.com
7-31, Nishi-Miyahara 1-Chome, Yodogawa-ku, Osaka 532-8550, Japan
Tel: +81-6-6398-2571, Fax: +81-6-6392-9731
E-mail: products@idec.co.jp
Specifications and other descriptions in this catalog are subject to change without notice.
Cat. No. NC9Y-B100-0 PRINTED IN U.S.A. 5K 09/08
IDEC ELEKTROTECHNIK GmbH
Wendenstrasse 331, 20537 Hamburg, Germany
Tel: +49-40-25 30 54 - 0, Fax: +49-40-25 30 54 - 24
E-mail: service@idec.de
IDEC (SHANGHAI) CORPORATION
Room 608-609, 6F, Gangtai Plaza, No. 700,
Yan'an East Road, Shanghai 200001, PRC
Tel: +86-21-5353-1000, Fax: +86-21-5353-1263
E-mail: idec@cn.idec.com
IDEC (BEIJING) CORPORATION
Room 211B, Tower B, The Grand Pacific Building,
8A Guanghua Road, Chaoyang District,
Beijing 100026, PRC
Tel: +86-10-6581-6131, Fax: +86-10-6581-5119
IDEC (SHENZHEN) CORPORATION
Unit AB-3B2, Tian Xiang Building, Tian’an Cyber Park,
Fu Tian District, Shenzhen, Guang Dong 518040, PRC
Tel: +86-755-8356-2977, Fax: +86-755-8356-2944
IDEC IZUMI (H.K.) CO., LTD.
Units 11-15, Level 27, Tower 1,
Millennium City 1, 388 Kwun Tong Road,
Kwun Tong, Kowloon, Hong Kong
Tel: +852-2803-8989, Fax: +852-2565-0171
E-mail: info@hk.idec.com
IDEC TAIWAN CORPORATION
8F-1, No. 79, Hsin Tai Wu Road, Sec. 1,
Hsi-Chih, Taipei County, Taiwan
Tel: +886-2-2698-3929, Fax: +886-2-2698-3931
E-mail: service@tw.idec.com
IDEC IZUMI ASIA PTE. LTD.
No. 31, Tannery Lane #05-01,
HB Centre 2, Singapore 347788
Tel: +65-6746-1155, Fax: +65-6844-5995
E-mail: info@sg.idec.com
www.idec.com
A
C
Overall length 39.4" (1000mm)
K
F
H
G
BD
H
9mm wide
• Miscellaneous Accessories (available 2009)
Type No. Description
NC9Z-MA11 Panel Cut-Out Mounting bracket for 1-pole mode
NC9Z-MA21 Panel Cut-Out Mounting bracket for 2-pole model
NC9Z-MA31 Panel Cut-Out Mounting bracket for 3-pole model
NC9Z-TA1 Fast-On Tab terminal Adapter
NC9Z-PW1 Marking Plate
NC9Z-LK1 Lock-Out Bracket