www.stancor.com
60
RElAYS AND CONTACTORS
General Purpose Relay
General Purpose Relays-Type 184
Engineering Design Data
Magnet Coil Rating Operation in % of Breakdown Voltages
(Volt Amperes) Nom. Coil Rating All Terminals - 60 Hz RMS Contact Material Electrical Life Mechanical Life
Open Max.
A.C. Max. Contacts Oper. Oper. Oper.
or Sealed Safe Opposite Same To Oper. At Per Oper. At Per Amb.
Type D.C Inrush Nom. Max. Pick-up Operate Polarity Polarity Ground Power Rated Load Min. No Load Min °F
184 A.C. 4 2.8 3 85% 110% 1500 1000 1500 Silver 100,000† 6 1,000,000 60 150
Alloy
D.C. 2 - - 66% 110% 1500 1000 1500 Silver 100,000 6 1,000,000 60 150
Alloy
12 Amps. Continuous
60 Amps. Inrush
@ 125 V.A.C.
8 Amps. Continuous
48 Amps. Inrush
@ 250 V.A.C.
7 Amps Continuous
42 Amps. Inrush
@ 277 V.A.C.
18 Amps.
Continuous
@ 277 V.A.C.
† Load tests – making inrush ratings (0.4 to 0.5 P.F.) – breaking 125% continuous rating (0.65 to 0.8 P.F.)
For schematic diagrams and outline drawings refer to page 62.
–– Totally Enclosed
–– A.C. Coils Rated 50/60Hz
STANCOR A.C. DIMENSIONS-INCHES
PART or Contact Rating Case Weight Agency
Sec. NUMBER Pole Form Coil Volt. D.C. Inductive Resistive L W H (oz.) Certification
A 184-911 SPNO 6 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-912 SPNO 24 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-913 SPNO 120 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-914 SPNO 208/240 A.C. 1.88 1.27 1.56 3.0 UL/CSA
184-929 SPNO 277 A.C. 1.84 1.27 1.56 3.0 UL/CSA
B 184-915 SPDT 6 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-916 SPDT 24 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-917 SPDT 120 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-918 SPDT 208/240 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-930 SPDT 277 A.C. 1.84 1.27 1.56 3.0 UL/CSA
C 184-919 SPNO/SPNC 24 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-920 SPNO/SPNC 120 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-921 SPNO/SPNC 208/240 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184-931 SPNO/SPNC 277 A.C. 1.84 1.27 1.56 3.0 UL/CSA
184D-901 SPDT 12 D.C. 4 Amps @ 12V 1.88 1.27 1.56 3.0 UL/CSA
D 184-927 SPNO/SPNC 120 A.C. 14 Amps. Continuous 25 Amps. 1.84 1.27 1.56 3.0 UL/CSA
60 Amps. Inrush Continuous
@125 V.A.C.
Agency Certification Note: UL Recognized (File E12139 or E22381)
CSA Certified (File LR 13360)
www.stancor.com 61
RElAYS AND CONTACTORS
13
56
2 4
1.265
.500
1.842
2.156
2.670
1.265
1.500
H
L
W
3 4
21 5
6
Type 184
1PNO/1PNC
Schematic
184 1PNO/1PNC
13
56
2 4
1.265
.500
1.842
2.156
2.670
1.265
1.500
H
L
W
3 4
21 5
6
Type 184
1PNO/1PNC
Schematic
184 1PNO/1PNC
Schematic
184 SPNO
Schematic
184 SPDT
Schematic
184 SPNO/SPNC
Type 184
Universal Mounting Bracket