Input
Network frequency 50/60 Hz +/- 3 Hz auto-sensing
Plug standard NEMA 5-15P
Input voltage limits 75...154 V adjustable
82...144 V
Number of cables 1
Input voltage 120 V
Output
Rated power in W 700W
Maximum configurable power in W 700W
Harmonic distortion Less than 5 %
Output frequency 50/60 Hz +/- 3 Hz sync to mains
UPS type Line interactive
Wave type Sine wave
Nb of power socket outlets 8 NEMA 5-15R
Curve equation Efficiency
Curve fixed loss 0.0111
Curve load maximum 100%
Curve load minimum 2%
Curve proportional loss 0
Curve square loss 0.006
Curve X-axis maximum 100%
Curve test cond ID Curve fit of data measured in accordance with the US DOE Test Procedure for Uninterruptible Power
Supplies. All measurements taken in normal mode(s), at typical environmental conditions, with
120V/60Hz electrical input and balanced resistive load (PF = 1.0) output.
Curve X-axis minimum 0%
Curve X-axis title Load
Curve X-axis units Percentage
Curve Y-axis maximum 100%
Curve Y-axis minimum 50%
Curve Y-axis title Efficiency
Curve Y-axis units Percentage
Graph display 1
Output voltage 120 V
Maximum configurable power in VA 1000VA
Rated power in VA 1000VA
Transfer time 4 ms typical : 8 ms maximum
Conformance
Product certifications CUL listed
TAA compliance
Standards UL 1778
Equipment protection policy Lifetime : $150000
Environmental
Ambient air temperature for operation 0…40°C
Relative humidity 0…95%
Operating altitude 0...10000 ft
Ambient air temperature for storage -15…45°C
Storage altitude 0.00…15240.00m
Acoustic level 41 dBA
2