RFI Power Line Filters for DC Applications
150 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
DC Series
DC Series
CORCOM Product Guide
The DC series filters were designed as general purpose line filters
for DC applications. They are available with or without circuit
breakers for extra protection. They are available with feed-through
capacitors for added high frequency performance. The DC series
is designed to comply with UL 1283, CSA 22.2 No. 8 and
EN60950.
The DC series was developed in response to the increasing
demand for DC filtering in the telecom-datacom market. These
filters are generally used in central office equipment like switches,
routers, and hubs to clean up the 48 VDC power, but are not
exclusive to that equipment. They can also be used at the primary
input of the DC power supply. The DC Series is available in both a
flange mount (DCF) and bulkhead mount (DCB) configuration.
Circuit Breaker Features (B Suffix)
always hold 100% of rated current independent of ambient
temperature (minimize nuisance tripping)
Always trip at 125% of rated current independent of ambient
temperature
Can be combined with feed through capacitor in bulk head
mount (DCB prefix) for high performance applications (BF
Suffix)
Feed Through Capacitor for High Performance (F Suffix)
High performance results out to 3Ghz
Available only in bulk head (DCB prefix ) configuration only
Can be combined with circuit breaker feature (BF Suffix)
Hipot rating (one minute):
line-to-ground 2250 VDC
line-to-line 1450 VDC
Operating Voltage (max): 80 VDC
Operating Ambient Temperature Range:
(@ rated current Ir)-10˚Cto +55˚C
In an ambient, Ta,higher than +55˚C, the maximum
operating current, Io,is as follows:
Specifications
Electrical Schematics
Standard Performance Version
High Frequency Performance Version
Note 1
Note 2 Note 3
Note 4
Note 1
LINE LOAD
Note 3
Note 2
Note 4
Note 1
LINE LOAD
Minimum insertion loss in dB:
Standard Performance
Line-to-ground in 50 ohm circuit
Current Frequency-MHz
Rating .01 .05 .1 .15 .5 1 3 5 10 30
15A - 1 12 20 41 45 61 63 47 39
30A - 4 15 23 47 59 64 56 44 36
60A - - 9 17 38 40 59 50 39 34
100A - - 10 18 38 39 53 50 35 21
125A - - 12 18 30 32 44 49 29 18
Line-to-line in 50 ohm circuit
Current Frequency-MHz
Rating .01 .05 .1 .15 .5 1 3 5 10 30
15A 7 22 27 30 30 36 56 49 38 31
30A 722 28 31 32 59 56 51 41 28
60A 15 30 36 40 40 35 60 51 39 32
100A 14 29 35 39 33 30 53 53 41 30
125A 14 24 35 39 40 28 53 60 42 33
High Frequency Performance ("F" & "BF" Styles)
Line-to-ground in 50 ohm circuit
Current Frequency-MHz 50 300
to to
Rating .01 .05 .1 .15 .5 1 3 5 10 20 300 3000
15A -112 20 41 45 55 50 45 25 50 30
30A - 4 15 20 46 58 60 60 48 35 50 30
60A - - 9 16 38 42 52 60 48 26 40 30
100A --916 38 42 52 60 42 26 40 30
125A - - 9 16 28 34 46 54 34 34 40 30
Line-to-line in 50 ohm circuit
Current Frequency-MHz
Rating .01 .05 .1 .15 .5 1 3 5 10 20
15A 7 22 27 30 30 50 60 60 60 36
30A 722 27 30 33 56 60 60 60 40
60A 15 30 36 40 37 26 46 54 48 30
100A 14 29 35 39 33 30 56 53 41 30
125A 14 29 35 39 40 28 53 60 42 33
UL Recognized
CSA Certified
TUV Approved
EN
60 950
Resistor location for reference only.
Note 1: Depicts redundant style 6 terminals.
Note 2: Depicts optional circuit breaker.
Note 3: For 100 & 125A versions delete second coil.
Note 4: Depicts style 10 terminal versions which have separate ground stud.
85-Ta
30
Io= Ir
DC
Cutout Dimensions Recommended Panel Cutouts
A
B
C
Holes: .157 [3.99] Dia. (4)
See case dimensions for
spacing.
Tolerance: ±.005/±.13
DCB6(F) & DCB10(F)
(Viewed from filter side)
F
B
AE
C
D
Holes: .157 [3.99] Dia. (4)
See case dimensions for
spacing.
Tolerance: ±.005/±.13
DCB6B(F) & DCB10B(F) – 15 to 60 Ampss
(Viewed from filter side)
B
A
C
1.250
31.75 .625
15.88
.262
6.65 1.557
39.55 1.500 x 0.781
38.10 x 19.84
Holes: .157 [3.99] Dia. (4)
See case dimensions for
spacing.
Tolerance: ±.005/±.13
DCB6B(F) & DCB10B(F) – 100 to 125 Amps
(Viewed from filter side)
Part Numbers
15DCB10F
30DCB10F
60DCB10F
100DCB10F
125DCB10F
15DCB6BF
30DCB6BF
60DCB6BF
100DCB6BF
125DCB6BF
15DCB10BF
30DCB10BF
60DCB10BF
100DCB10BF
125DCB10BF
15DCB6F
30DCB6F
60DCB6F
100DCB6F
125DCB6F
15DCF6
30DCF6
60DCF6
100DCF6
125DCF6
15DCF6B
30DCF6B
60DCF6B
100DCF6B
125DCF6B
15DCB6
30DCB6
60DCB6
100DCB6
125DCB6
15DCB6B
30DCB6B
60DCB6B
100DCB6B
125DCB6B
15DCF10
30DCF10
60DCF10
100DCF10
125DCF10
15DCF10B
30DCF10B
60DCF10B
100DCF10B
125DCF10B
15DCB10
30DCB10
60DCB10
100DCB10
125DCB10
15DCB10B
30DCB10B
60DCB10B
100DCB10B
125DCB10B
Standard Performance High Performance
RFI Power Line Filters for DC Applications (Continued)
151
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
DC Filters
DC Series
CORCOM Product Guide
DCB6(F) & DCB10(F)
Part No. A B C
15DCB6(F) 1.375 1.249 3.472
30DCB6(F) 34.93 31.72 88.19
15DCB10(F) 1.250 1.000 3.472
30DCB10(F) 31.75 25.40 88.19
60DCB6(F) 1.375 1.249 3.472
34.93 31.72 88.19
60DCB10(F) 1.674 1.010 3.443
42.52 25.65 87.45
100DCB6(F) 1.700 1.549 3.472
125DCB6(F) 43.18 39.34 88.19
100DCB10(F) 1.954 1.500 2.830
49.63 38.10 71.20
125DCB10(F) 2.250 1.590 2.725
57.15 40.39 69.22
DCB6B(F) & DCB10B(F) – 100 to 125 Amps
Part No. A B C
100DCB6B(F)
100DCF6B 1.700 1.549 4.222
125DCB6B(F) 43.18 39.34 107.23
125DCF6B
100DCB10B(F) 1.954 1.50 4.295
100DCF10B 49.63 38.10 109.09
125DCB10B(F) 2.250 1.590 4.147
57.15 40.39 105.33
125DCF10B 2.250 1.590 2.725
57.15 40.39 105.33
** All cutout dimensions ± .005 [±.13]
DCB6B(F) & DCB10B(F) – 15 to 60 Amps
Part No. A B C D E F
15DCB6B(F) 1.50 0.781 1.308 3.472 1.375 1.249
15DCF6B 38.10 19.84 33.22 88.19 34.93 31.72
15DCB10B(F) 1.50 0.781 1.308 3.472 1.250 1.000
15DCF10B 38.10 19.84 33.22 88.19 31.75 25.40
30DCB6B(F) 1.50 0.781 1.308 3.472 1.375 1.249
30DCF6B 38.10 19.84 33.22 88.19 34.93 31.72
30DCB10B(F) 1.50 0.781 1.308 3.472 1.250 1.0
30DCF10B 38.10 19.84 33.22 88.19 31.75 25.40
60DCB10B(F) 1.50 0.781 1.308 3.443 1.674 1.010
60DCF10B 38.10 19.84 33.22 87.45 42.52 25.65
60DCF6B(F) 1.50 0.781 1.308 3.472 1.375 1.249
60DCF6B 38.10 19.84 33.22 88.19 34.93 31.72
RFI Power Line Filters for DC Applications (Continued)
Case Styles
DCF10 (15 & 30 Amp)
F
D
A
C
B
E
L
I
N
E
L
O
A
D
-VDC
RTN
OFFOFF ONON
-VDC
RTN
Tapped insert: 6-32 (4)
A
D
E
F
C
B
L
I
N
E
L
O
A
D
RTN
-VDC
RTN
-VDC
Note: Delete circuit breaker for DCB10 models.
Typical dimensions:
Mounting Holes: .156 x .203 [4.0 x 5.2]Dia. (4)
DCF10B (15 & 30 Amp)
B
A
C
D
E
F
-VDC
RTN
-VDC
RTN
L
I
N
E
L
O
A
D
OFFOFF ONON
Tapped insert: 6-32 (4)
Typical dimensions:
Mounting Slots: .260 x .39 [6.6 x 9.9](4)
DCB6 & DCB6B
F
D
B
A
E
C
L
I
N
E
L
O
A
D
-VDC
RTN
VDCVDC
RTNRTN
-VDC
RTN
OFFOFF ONON
Tapped insert: 6-32 (4)
Note: Delete circuit breaker for DCB6 models.
DCF6B
DCB10 & DCB10B (15 & 30 Amp)
Typical dimensions:
Mounting Slots: .260 x .39 [6.6 x 9.9](4)
DCF6
A
D
E
F
C
B
L
I
N
E
L
O
A
D
-VDC
RTN
-VDC
RTN
Typical dimensions:
Mounting Slots: .260 x .39 [6.6 x 9.9](4)
Mounting Holes: .203x.156 [5.2 x 4.0](4)
Note: 15A & 30A versions come with mounting holes in place of mounting slots.
DCB10 & DCB10B (60 to 125 Amp)
F
D
A
C
B
E
L
I
N
E
L
O
A
D
RTN
VDC
RTN
VDC
OFFOFF ONON
Tapped insert: 6-32 (4)
Note: Delete circuit breaker for DCB10 models
152 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
DC Series
CORCOM Product Guide
DCF10 (60 to 126 Amps)
A
D
E
F
C
B
L
I
N
E
L
O
A
D
RTN
-VDC
RTN
-VDC
Typical dimensions:
Mounting Slots: .260 x .39 [6.6 x 9.9](4)
Case Styles (continued)
RFI Power Line Filters for DC Applications (Continued)
Case Dimensions (cont'd)
Part A B C D E F
Number (max) (max) (max) * (max) *
60DCF10 8.56 5.48 2.55 4.92 5.94 2.576
217.4 139.2 64.8 124.97 150.9 65.43
60DCF10B 11.75 5.06 1.48 5.74 9.06 6.52
298.5 128.5 37.6 145.8 230.1 165.61
100DCB6(F) 10.31 5.06 1.78 4.50 8.06 1.25
261.9 128.5 45.2 114.3 204.7 31.75
100DCB6B(F) 12.31 6.06 1.78 5.50 10.06 1.25
312.7 153.9 45.2 139.7 255.5 31.75
100DCB10(F) 11.13 5.06 1.78 4.50 8.06 1.25
282.6 128.5 45.2 114.3 204.7 31.75
100DCB10B(F) 13.13 6.06 1.78 5.50 10.06 1.25
333.5 153.9 45.2 139.7 255.5 31.75
100DCF6 10.60 6.30 2.52 5.70 8.46 4.52
269.2 160.0 64.0 144.78 214.9 114.81
100DCF6B 12.31 6.06 1.78 6.74 10.06 7.52
312.7 153.9 45.2 171.2 255.5 191.01
100DCF10 11.50 6.30 2.52 5.70 8.46 4.52
292.1 160.0 64.0 144.78 214.9 114.81
100DCF10B 13.13 6.06 1.78 6.74 10.06 7.52
333.5 153.9 45.2 171.2 255.5 191.01
125DCB6(F) 10.31 5.06 1.78 4.50 8.06 1.25
261.9 128.5 45.2 114.3 204.7 31.75
125DCB6B(F) 12.31 6.06 1.78 5.50 10.06 1.25
312.7 153.9 45.2 139.7 255.5 31.75
125DCB10(F) 11.50 5.06 1.78 4.50 8.06 1.25
292.1 128.5 45.2 114.30 204.7 31.75
125DCB10B(F) 13.50 6.06 1.78 5.50 10.06 1.25
342.9 153.9 45.2 139.7 255.5 31.75
125DCF6 10.60 6.30 2.52 5.70 8.46 4.52
269.2 160.0 64.0 144.78 214.9 114.81
125DCF6B 12.31 6.06 1.78 6.74 10.06 7.52
312.7 153.9 45.2 171.2 255.5 191.01
125DCF10 11.86 6.30 2.52 5.70 8.46 4.52
301.2 160.0 64.0 144.78 214.9 114.81
125DCF10B 13.50 6.06 1.78 6.74 10.06 7.52
342.9 153.9 45.2 171.2 255.5 191.01
*±.020 [±.51]
153
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
DC Filters
DC Series
CORCOM Product Guide
DCF10B (60 to 125 Amps)
B
A
C
D
E
F
L
I
N
E
L
O
A
D
RTN
VDC
RTN
VDC
OFFOFF ONON
Tapped insert: 6-32 (4)
Typical dimensions:
Mounting Slots: .260 x .39 [6.6 x 9.9](4)
Case Dimensions
Part A B C D E F
Number (max) (max) (max) *(max) *
15DCB6(F) 5.69 5.06 1.48 4.50 4.06 0.950
144.5 128.5 37.6 114.3 103.1 24.13
15DCB6B(F) 7.69 5.06 1.48 4.50 6.06 0.950
195.3 128.5 37.6 114.3 153.9 24.13
15DCB10(F) 5.06 5.06 1.48 4.50 4.06 0.950
128.5 128.5 37.6 114.3 103.1 24.13
15DCB10B(F) 7.06 5.06 1.48 4.50 6.06 0.950
179.3 128.5 37.6 114.3 153.9 24.13
15DCF6 5.33 3.10 1.78 2.677 3.70 2.00
135.4 78.7 45.2 68.0 94.0 50.80
15DCF6B(F) 7.69 5.06 1.48 5.740 6.06 3.52
195.3 128.5 37.6 145.8 153.9 89.41
15DCF10 4.75 3.10 1.78 2.677 3.70 2.0
120.7 78.7 45.2 68.0 94.0 50.8
15DCF10B(F) 7.06 5.06 1.48 5.740 6.06 3.520
179.3 128.5 37.6 145.80 153.9 89.41
30DCB6(F) 7.69 5.06 1.48 4.50 6.06 0.95
195.3 128.5 37.6 114.3 153.9 24.13
30DCB6B(F) 8.69 5.06 1.48 4.50 7.06 0.95
220.7 128.5 37.6 114.3 179.3 24.13
30DCB10(F) 7.06 5.06 1.48 4.50 6.06 0.95
179.3 128.5 37.6 114.3 153.9 24.13
30DCB10B(F) 8.06 5.06 1.48 4.50 7.06 0.95
204.7 128.5 37.6 114.3 179.3 24.13
30DCF6 6.19 3.96 2.18 3.50 4.56 2.00
157.2 100.6 55.4 88.9 115.8 50.8
30DCF6B 8.69 5.0 1.48 5.74 7.06 4.52
220.73 127.0 37.6 145.8 179.3 114.81
30DCF10 5.56 3.96 2.18 3.5 4.56 2.0
141.2 100.58 55.4 88.9 115.8 50.8
30DCF10B 8.06 5.06 1.48 5.74 7.06 4.52
204.7 128.52 37.6 145.8 179.3 114.81
60DCB6(F) 8.69 5.06 1.48 4.50 7.06 0.95
220.73 128.52 37.6 114.3 179.3 24.13
60DCB6B(F) 10.69 5.06 1.48 4.50 9.06 0.95
271.5 128.52 37.6 114.3 230.1 24.13
60DCF6 7.56 5.48 2.55 4.92 5.94 2.756
192.0 139.2 64.8 124.97 150.9 70.0
60DCF6B 10.69 5.06 1.48 5.74 9.06 6.52
271.5 128.52 37.6 145.8 230.1 165.61
Terminations
Style 6 (15, 30 & 60A) Style 6 (100 & 125A)
Supplied with #10-32 redundant Supplied with 1/4-20 redundant
studs - 0.625 [15.88]spacing like studs - 0.750 [19.05]spacing like
polarity, 0.750 [19.05]spacing polarity.1.000 [25.4]spacing
opposing polarity. opposing polarity.
Torque Spec: 27±3 in-lb. Torque Spec: 45±2 in-lb.
Style 10 (15 & 30A) Style 10 (60A)
Phoenix Contact Phoenix Contact
Part No. VDFK4 Part No. HDFK 16-VP
Accepts 12 AWG stranded wire Accepts 6 AWG stranded wire
Wire Strip Length: 0.315 [8.0] Wire Strip Length: 0.630 [16.0]
Torque Spec: 5.5 - 7.0 in-lb. Torque Spec: 17.7 - 21.2 in-lb.
Ground Stud 8-32 Ground Stud 10-32
Style 10 (100A) Style 10 (125A)
Phoenix Contact Phoenix Contact
Part No. HDFK 25-VP Part No. HDFK-50-VP
Accepts 4 AWG stranded wire Accepts 1 AWG stranded wire
Wire Strip Length: 0.748 [19.0] Wire Strip Length: 0.945 [24.0]
Torque Spec: 35.4 - 39.9 in-lb. Torque Spec: 35.4 - 39.9 in-lb.
Ground Stud 1/4 - 20 Ground Stud 1/4 - 20