POWER TRANSFORMERS P-8611, P-8612, P-8613 P-8671, P-8672, P-8673, P-8674 SPECIFICATIONS: ! WARNING ELECTROCUTION HAZARD Disconnect electric power to system at main fuse or circuit breaker box before servicing. Failure to do so could result in death or serious injury. FIRE HAZARD Do not exceed transformer ratings. Higher voltage may damage control and could cause personal injury or property damage. INPUT: 117 V, 50/60Hz OUTPUT: 36V CT: SEE OUTPUT AMP RATING & VA CAPACITY IN TABLE INSULATION RATING: CLASS A (105C) TEMPERATURE RISE: 65C RISE ABOVE 40C AMBIENT DIELECTRIC STRENGTH: 1500 VRMS NOTE: 1. Primary leads Black, #22 AWG. 2. All leads 8" long minimum. D MAX. D MAX. PRI 117V 50/60Hz STANCOR H MAX. P-XXXX 2 OR STANXCXX 1 P-X 7V PRI 11 z 50/60H H MAX. 2 1 MW MD MS (4 PLACES) W MAX. STYLE NV MW W MAX. .188 .015 DIA. (2 HOLES) 1 3 PRIMARY 117V, 50/60 Hz 2 4 SECONDARY 36V CT STYLE A 5 SCHEMATIC DIAGRAM STANCOR Sec. VA Part No. Curr. Cap. P-8611 P-8612 P-8613 P-8671 P-8672 P-8673 P-8674 .135A .30A .55A 1.0A 2.0A 4.0A 6.0A 4.9 10.8 19.8 36.0 72.0 144.0 216.0 Sec. Lead Wires Mtg. Dimensions - Inches Color Awg Style #3 #4 (CT) #5 H W D MW MD MS .031 BLU YEL BLU #22 A 1.44 2.44 1.50 2.00 BLU YEL BLU #22 A 1.75 2.88 1.62 2.38 GRN YEL GRN #22 A 2.06 3.31 2.00 2.81 BLU YEL BLU #22 A 2.38 3.75 2.38 3.12 GRN YEL GRN #22 NV 3.56 2.88 2.88 2.25 2.13 .188 X..312 GRN YEL GRN #18 NV 4.38 3.56 3.19 2.75 2.38 .188 X .312 GRN YEL GRN #18 NV 4.69 3.81 3.62 3.06 2.47 .203 X .500 Wt. Lbs. 0.35 0.60 1.00 2.00 3.50 6.00 8.30 PART NO. 37-6774B www.stancor.com Replaces 37-6774A 0741