427 Van Camp Road
P.O. Box 468
Bowling Green, OH 43402
Marathon offers 600 Volt Power Distribution
Blocks with high SCCR’s in response to new
2005 NEC® and UL508A marking requirements
The requirements of the 2005 National Electric Code (NEC) and UL508A now require many
electrical panels to carry a Short Circuit Current Rating (SCCR). Analyzing the SCCR of
individual components and overcurrent protection devices is a method of determining the
SCCR of an electrical assembly.
Marathon’s Power Distribution Blocks are standard products that have been used in
electrical control panels for over 35 years. These blocks have now been tested and
approved for higher SCCR. The higher ratings are based on proper wire sizes and the
appropriate circuit protection device. UL508A does allow default SCCR for Power
Distribution Blocks of 10,000A with no additional testing.
Standard Power Distribution Blocks
With High Short-Circuit Current Ratings
Power Distribution Block with hinge cover
8/7/2014
Rev. C
Marathon’s Power Distribution Blocks (UL File # E62806) are recognized under UL
Standard 1059 and have been investigated by UL for Short-Circuit Current Ratings (SCCR)
as described in the UL Guide Information for category XCFR2; Terminal Blocks-Component.
Marathon's new Power Distribution Blocks (UL File # E309401) are listed to UL 1953. The
feeder spacing requirements of UL508A are achieved with these blocks.
UL 1953 Listed Power Distribution Blocks
meeting
spacing requirements for UL 508A service entrance
clearances. Short-Circuit Current Ratings (SCCR)
with fuses up to 100,000A and circuit breakers up
to 65,000A.
UL 1059 Recognized Power Terminal Blocks
with
SCCR ratings with fuses up to 200,000A and circuit
breakers up to 65,000A.
For rating details see detailed data sheets at www.marathonsp.com. These data sheets contain
valuable product information including a photo of the product, technical drawings, short circuit current
ratings, electrical and mechanical ratings and agency approvals.
Phone: (419) 352-8441 * Fax: (800) 515-7151 * Website: www.marathonsp.com
8/7/2014
Rev. C
High SCCR with Fuse Protection
UL 1059
XCFR2 - E62806
Configuration
Wire
Line
Load
Line
Load
Line
Load
Class
J
RK1
RK5
G
CC
1321570 1 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1322570 2 175 (1) 2/0 - 14 (4) 4 - 14 1-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1323570 3
1321572 1 2/0-6 2/0-6 B, C 200 200 200 100 60 30 100,000 A
1322572 2 175 (1) 2/0 - 14 (1) 2/0 - 14 1-6 1-6 G, H, I 150 150 100 30 60 30 100,000 A
1323572 3
1321574 1 2/0-6 2/0-6 B, C 300 300 200 100 60 30 100,000 A
1322574 2 175 (1) 2/0 - 14 2/0-10 2/0-10 B, C 150 150 100 30 60 30 100,000 A
1323574 3 1-6 1-6 G, H, I 150 150 100 30 60 30 100,000 A
1321580 1 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1322580 2 175 (1) 2/0 - 14 (6) 4 - 14 1-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1323580 3
1321970 1 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1322970 2 175 (1) 2/0 - 14 (4) 4 - 14 1-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1323970 3
1321972 1 2/0-6 2/0-6 B, C 300 300 200 100 60 30 100,000 A
1322972
2
175
(1) 2/0 - 14
(1) 2/0 - 14
1-6 6-14 G, H, I 150 150 100 30 60 30 100,000 A
SCCR, RMS SYM
Amps (1)
Marathon
Catalog # Poles Amps
(1) 1/4 - 20 x 1/2
(kcmil/AWG)
(2)
POWER BLOCK DESCRIPTION HIGH SCCR CONDITIONS
Overcurrent Protection Fuse Required
Class/Max Amp Rating
(3)
Rated Wire Range
(openings) kcmil/AWG Suitable Conductors
1322972
2
175
(1) 2/0 - 14
(1) 2/0 - 14
1323972 3
1331320 1 250-1/0 250-1/0 B, C 500 500 400 200 60 30 100,000 A
1332320 2 510 3/0-1/0 3/0-1/0 G, H, I 500 500 400 200 60 30 100,000 A
1333320 3
1331360 1 600-3/0 2-8 B, C 400 400 400 200 60 30 100,000,A
1332360 2 420 (1) 600 - 2 (1) 600 - 2 600-2 2-10 B, C 200 200 200 100 60 30 100,000,A
1333360 3 350-2 4-10 G, H, I 150 150 100 30 60 30 100,000,A
1331552 1 400-3/0 2-8 B, C 400 400 400 100 60 30 100,000 A
1332552 2 335 (1) 400 - 6 (4) 2 - 14 400-6 2-10 B, C 200 200 200 100 60 30 100,000 A
1333552 3 250-1/0 1-6 G, H, I 150 150 100 30 60 30 100,000 A
1331554 1 350-3/0 2/0-1 B, C 500 500 400 200 60 30 100,000 A
1332554 2 310 (1) 350 - 6 (2) 2/0 - 14 350-6 2/0-10 B, C 200 200 200 100 60 30 100,000 A
1333554 3 250-1/0 1-10 G, H, I 150 150 100 30 60 30 100,000 A
1331555 1 2/0-2 4-8 B, C 400 400 400 100 60 30 100,000 A
1332555 2 350 (2) 2/0 - 14 (6) 4 - 14 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1333555 3 1-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1331559 1 250-1/0 4-10 B, C 450 450 400 100 60 30 100,000 A
1332559 2 310 (1) 350 - 6 3/0-1/0 6-14 G, H, I 150 150 100 30 60 30 100,000 A
1333559 3
1331585 1 600-3/0 2-8 B, C 400 400 400 200 60 30 100,000,A
1332585 2 420 (1) 600 - 2 (8) 2 - 14 600-2 2-10 B, C 200 200 200 100 60 30 100,000,A
1333585 3 350-2 4-10 G, H, I 150 150 100 30 60 30 100,000,A
(2) 250 - 1/0 (2) 250 - 1/0
(1) 3/8 - 16 x 1 1/4
1331587 1 (3) 2 - 14 500-3/0 350-6 B, C 500 500 400 200 60 30 100,000 A
1332587 2 380 (1) 500 - 4 500-4 350-10 B, C 200 200 200 100 60 30 100,000 A
1333587 3 (1) 350 - 6 350-2 1-6 G, H, I 500 500 400 200 60 30 100,000 A
350-2 1-10 G, H, I 200 200 200 100 60 30 100,000 A
1331588 1 (6) 2 - 14 600-3/0 1/0-8 B, C 500 500 400 200 60 30 100,000 A
1332588 2 420 (1) 600 - 2 600-2 1/0-10 B, C 200 200 200 100 60 30 100,000 A
1333588 3 (3) 1/0 - 14 350-2 1-8 G, H, I 500 500 400 200 60 30 100,000 A
350-2 1-10 G, H, I 200 200 200 100 60 30 100,000 A
1331595 1 600-3/0 4-8 B, C 500 500 400 200 60 30 100,000 A
1332595 2 420 (1) 600 - 2 (12) 4 - 14 600-2 4-10 B, C 200 200 200 100 60 30 100,000 A
1333595 3 350-2 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1331596 1 250-1/0 4-10 B, C 450 450 400 100 60 30 100,000 A
1332596 2 510 (12) 4 - 14 3/0-1/0 6-14 G, H, I 150 150 100 30 60 30 100,000 A
1333596 3
1331597 1 250-1/0 2-8 B, C 350 350 200 100 60 30 100,000 A
1332597 2 510 (8) 2 - 14 3/0-1/0 4-14 G, H, I 150 150 100 30 60 30 100,000 A
1333597 3
1331953 1 500-3/0 2-10 B, C 400 400 400 100 60 30 100,000,A
1332953 2 380 (1) 500 - 4 (6) 2 - 14 500-4 2-10 B, C 200 200 200 100 60 30 100,000,A
1333953 3 350-2 4-10 G, H, I 150 150 100 30 60 30 100,000,A
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
(2) 250 - 1/0
(2) 250 - 1/0
High SCCR with Fuse Protection UL 1059
XCFR2 - E62806
Configuration
Wire
Line Load Line Load Line Load Class J T RK1 RK5 G CC
1331955 1 2/0-2 4/8 B, C 400 400 400 100 60 30 100,000 A
1332955 2 350 (2) 2/0 - 14 (6) 4 - 14 2/0-6 4-10 B, C 200 200 200 60 60 30 100,000 A
1333955 3 1-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1402401 2 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
2/0-10 4-14 B, C 60 60 60 30 60 30 100,000 A
1-6 6-10 G, H, I 60 60 60 30 60 30 100,000 A
1403401 3 1-10 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1402402 2 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1403402 3 1-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
350-3/0 4-8 B, C 400 400 400 200 60 30 100,000 A
1402404 2 350-6 4-10 B, C 250 250 200 100 60 30 100,000 A
1403404 3 250-6 6-10 G, H, I 150 150 100 30 60 30 100,000 A
1411300 1 2-6 2-6 B, C 200 200 200 100 60 30 100,000 A
310 (1) 350 - 6 (6) 4 - 14
175 (1) 2/0 - 14 (6) 4 - 14
Marathon
Catalog #
POWER BLOCK DESCRIPTION
Poles Amps
175 (1) 2/0 -14 (4) 4 - 14
HIGH SCCR CONDITIONS
Overcurrent Protection Fuse Required
Class/Max Amp Rating
(3)
(kcmil/AWG)
(2)
Rated Wire Range Suitable Conductors
SCCR, RMS
SYM Amps (1)
(openings) kcmil/AWG
1412300 2 2-10 2-10 B, C 100 100 100 30 60 30 100,000 A
1413300 3 4-10 4-10 G, H, I 150 150 100 30 60 30 100,000 A
1414300 4
1411400 1 2-6 10 B, C 200 200 200 60 60 30 100,000 A
1412400 2 2-10 10-14 B, C 150 150 100 30 60 30 100,000 A
1413400 3 4-10 10-14 G, H, I 150 150 100 30 60 30 100,000 A
1414400 4
1421120 1 2/0-6 2/0-6 B, C 300 300 200 100 60 30 65,000 A
1422120 2 175 (1) 2/0 - 14 (1) 2/0 - 14 1-6 1-6 G, H, I 300 300 200 100 60 30 65,000 A
1423120 3
1421121 1 1/0-6 1/0-6 B, C 175 175 100 60 60 30 100,000 A
1422121 2 150 (1) 1/0 - 18 (1) 1/0 - 18 1-6 1-6 G, H, I 175 175 100 60 60 30 100,000 A
1423121 3
1421552 1 2-6 2-6 B, C 300 300 200 100 60 30 100,000 A
1422552 2 115 (1) 2 - 14 (1) 2 - 14 2-10 2-10 B, C 150 150 100 30 60 30 100,000 A
1423552 3 4-10 4-10 G, H, I 150 150 100 30 60 30 100,000 A
1421553 1 2/0-6 2/0-6 B, C 200 200 200 100 60 30 100,000 A
1422553 2 175 (1) 2/0 - 14 2/0-10 2/0-10 B, C 100 100 100 30 60 30 100,000 A
1423553 3 1-6 1-6 G, H, I 150 150 100 30 60 30 100,000 A
115 (1) 2 - 14 (1) 2 - 14
115 (1) 2 - 14
(1) 1/4-20 X
1/2
(4) 10 - 16
1421570 1 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1422570 2 175 (1) 2/0 - 14 (4) 4 - 14 2/0-6 4-14 B, C 150 150 100 30 60 30 100,000 A
1423570 3 1-6 6-12 G, H, I 150 150 100 30 60 30 100,000 A
1421572 1 2/0-6 2/0-6 B, C 300 300 200 100 60 30 65,000 A
1422572 2 175 (1) 2/0 - 14 (1) 2/0 - 14 1-6 1-6 G, H, I 300 300 200 100 60 30 65,000 A
1423572 3
1421574 1 2/0-6 2/0-6 B, C 200 200 200 100 60 30 100,000 A
1422574 2 175 (1) 2/0 - 14 2/0-10 2/0-10 B, C 100 100 100 30 60 30 100,000 A
1423574 3 1-6 1-6 G, H, I 150 150 100 30 60 30 100,000 A
1421970 1 2/0-6 4-10 B, C 200 200 200 100 60 30 100,000 A
1422970 2 175 (1) 2/0 - 14 (4) 4 - 14 1-6 6-12 G, H, I 150 150 100 30 60 30 100,000 A
1423970 3
1431123 1 250-6 250-6 B, C 300 200 200 100 60 30 100,000 A
1432123 2 255 (1) 250 - 6 (1) 250 - 6 250-1/0 250-1/0 G, H, I 300 300 200 100 60 30 100,000 A
1433123 3
1431124 1 250-6 250-6 B, C 300 200 200 100 60 30 100,000 A
1432124 2 255 (1) 250 - 6 (1) 250 - 6 250-1/0 250-1/0 G, H, I 300 300 200 100 60 30 100,000 A
1433124 3
1431126
350-1/0
350-1/0
B, C
400
400
400
100
60
30
100,000 A
(1) 1/4-20 X
1/2
1431126
350-1/0
350-1/0
B, C
400
400
400
100
60
30
100,000 A
1432126 2 310 (1) 350 - 6 (1) 350 - 6 350-6 350-6 B, C 300 300 200 100 60 30 100,000 A
1433126 3 250-1/0 250-1/0 G, H, I 300 300 200 100 60 30 100,000 A
1431552 1 400-3/0 2-6 B, C 400 400 400 100 60 30 100,000 A
1432552 2 335 (1) 400 - 6 (4) 2 - 14 400-6 2-10 B, C 300 300 200 100 60 30 100,000 A
1433552 3 250-1/0 4-10 G, H, I 150 150 100 30 60 30 100,000 A
400-3/0 2-8 B, C 500 500 400 200 60 30 100,000 A
400-6 2-10 B, C 350 350 200 100 60 30 100,000 A
250-1/0 4-10 G, H, I 150 150 100 30 60 30 100,000 A
1431554 1 350-3/0 2/0-3 B, C 450 450 400 200 60 30 100,000 A
1432554 2 310 (1) 350 - 6 (2) 2/0 - 14 350-6 2/0-6 B, C 300 300 200 100 60 30 100,000 A
1433554 3 250-1/0 1-6 G, H, I 150 150 100 30 60 30 100,000 A
1431555 1 2/0-2 4-8 B, C 400 400 400 100 60 30 100,000 A
1432555 2 350 (2) 2/0 - 14 (6) 4 - 14 2/0-6 4-8 B, C 350 350 200 100 60 30 100,000 A
1433555 3 1-6 6-14 G, H, I 150 150 100 30 60 30 100,000 A
1431559 1 350-4 350-4 B, C 400 400 400 100 60 30 65,000 A
1432559 2 310 (1) 350 - 6 250-1/0 250-1/0 G, H, I 300 300 200 100 60 30 65,000 A
1433559 3
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
(1) 3/8 - 16 x
1 1/8
1431553
1432553
1433553 335 (1) 400 - 6 (6) 2 - 14
1
2
3
High SCCR with Fuse Protection
UL 1059
XCFR2 - E62806
Configuration
Wire
Line Load Line Load Line Load Class J T RK1 RK5 G CC
1431587 1 (3) 2 - 14 500-3/0 350-6 B, C 500 500 400 200 60 30 100,000 A
1432587 2 380 (1) 500 - 4 500-4 350-10 B, C 200 200 200 100 60 30 100,000 A
1433587 3 (1) 350 - 6 350-2 250-1/0 G, H, I 150 150 100 30 60 30 100,000 A
350-2 4-10 G, H, I 150 150 100 30 60 30 100,000 A
1431953 1 500-3/0 2-8 B, C 400 400 400 200 60 30 100,000 A
1432953 2 380 (1) 500 - 4 (6) 2 - 14 500-4 2-10 B, C 300 300 200 100 60 30 100,000 A
1433953 3 250-1/0 4-10 G, H, I 150 150 100 30 60 30 100,000 A
1431955 1 2/0-2 4-8 B, C 400 400 400 100 60 30 100,000 A
1432955 2 350 (2) 2/0 - 14 (6) 4 - 14 2/0-6 4-8 B, C 350 350 200 100 60 30 100,000 A
1433955 3 4-10 10-14 G, H, I 150 150 100 30 60 30 100,000 A
1441551 1 500-3/0 2-8 B, C 500 500 400 200 60 30 100,000 A
1442551 2 380 (1) 500 - 4 (6) 2 - 14 500-4 2-10 B, C 200 200 200 100 60 30 100,000 A
1443551 3 350-2 4-14 G, H, I 150 150 100 30 60 30 100,000 A
1441560 1 400-3/0 2-8 B, C 400 400 400 200 60 30 100,000 A
1442560 2 335 (1) 400 - 6 (8) 2 - 14 400-6 2-10 B, C 200 200 200 100 60 30 100,000 A
1443560
3
250-1/0
4-14
G, H, I
150
150
100
30
60
30
100,000 A
HIGH SCCR CONDITIONS
Overcurrent Protection Fuse Required
Class/Max Amp Rating
(3)
POWER BLOCK DESCRIPTION
Rated Wire Range Suitable Conductors
SCCR, RMS
SYM Amps (1)
(kcmil/AWG)
(2)
Marathon
Catalog # Poles Amps
(openings) kcmil/AWG
1443560
3
250-1/0
4-14
G, H, I
150
150
100
30
60
30
100,000 A
1441557 1 600-2 600-2 B, C 600 600 - - - - 50,000 A
1442557 2 420 (1) 600 - 4 (1) 600 - 4 600-2 600-2 B, C 400 400 400 200 60 30 100,000 A
1443557 3 350-2 350-2 G, H, I 400 400 400 200 60 30 100,000 A
1451129 1 350-4 350-4 B, C 450 450 400 200 60 30 100,000 A
1452129 2 620 (2) 350 - 4 (2) 350 - 4 350-4 350-4 B, C 600 600 - - - - 50,000 A
1453129 3 250-2 250-2 G, H, I 600 600 - - - - 50,000 A
250-2 250-2 G, H, I 450 450 400 200 60 30 100,000 A
1451301 1 500-4 500-4 B, C 500 500 400 200 60 30 100,000 A
1452301 2 760 (2) 500 - 4 (2) 500 - 4 350-2 350-2 G, H, I 500 500 400 200 60 30 100,000 A
1453301 3
1451552 1 500-3/0 2-6 B, C 400 400 400 200 60 30 100,000 A
1452552 2 380 (1) 500 - 4 (12) 2 - 14 500-4 2-10 B, C 250 250 200 100 60 30 100,000 A
1453552 3 350-2 4-6 G, H, I 400 400 400 200 60 30 100,000 A
350-2 4-10 G, H, I 250 250 200 200 60 30 100,000 A
1451579 1 500-3/0 2/0-6 B, C 400 400 400 100 60 30 100,000 A
1452579 2 380 (1) 500 - 4 (6) 2/0 - 14 500-4 2/0-10 B, C 200 200 200 100 60 30 100,000 A
1453579 3 350-2 1-6 G, H, I 400 400 400 100 60 30 100,000 A
350-2 1-10 G, H, I 250 250 200 100 60 30 100,000 A
1451586 1 500-250 2/0-4 B, C 600 600 400 200 60 30 100,000 A
1452586 2 760 (2) 500 - 4 (8) 2/0 - 14 500-4 2/0-10 B, C 350 350 200 100 60 30 100,000 A
1453586 3 350-250 1-4 G, H, I 600 600 400 200 60 30 100,000 A
350-4 6-10 G, H, I 350 350 200 200 60 30 100,000 A
1451592 1 500-250 4-8 B, C 400 400 400 100 60 30 100,000 A
1452592
2
760 (2) 500 - 4 (12) 4 - 14 500-4 4-10 B, C 350 350 200 100 60 30 100,000 k
1453592
3
350-250 6-8 G, H, I 400 400 200 100 60 30 100,000 k
350-4 6-10 G, H, I 350 350 200 100 60 30 100,000 k
1451594 1 500-3/0 2-8 B, C 500 500 400 200 60 30 100,000 A
1452594 2 380 (1) 500 - 4 (8) 2 - 14 500-4 2-10 B, C 300 300 200 100 60 30 100,000 A
1453594 3 350-3/0 4-8 G, H, I 500 500 400 200 60 30 100,000 A
350-2 4-10 G, H, I 300 300 200 100 60 30 100,000 A
1451599 1 500-4/0 500-4/0 B, C 600 600 400 200 60 30 100,000 A
1452599 2 760 (2) 500 - 4 500-4 500-4 B, C 400 400 400 100 60 30 100,000 A
1453599 3 350-4/0 350-4/0 G, H, I 600 600 400 200 60 30 100,000 A
350-2 350-2 G, H, I 400 400 400 100 60 30 100,000 A
1451986 1 500-250 2/0-4 B, C 500 500 400 200 60 30 100,000 A
1452986 2 500-4 2/0-6 B, C 450 450 400 200 60 30 100,000 A
1453986 3 760 (2) 500 - 4 (8) 2/0 - 14 350-250 1-4 G, H, I 500 500 400 200 60 30 100,000 A
350-2 1-6 G, H, I 450 450 400 200 60 30 100,000 A
1451992 1 500-4 2-10 B, C 400 400 400 200 60 30 100,000 A
(2) 3/8 - 16 x
1 5/16
1452992
2
760 (2) 500 - 4 (12) 2 - 14 500-250 2-8 B, C 600 600 - - - - 50,000 A
1453992
3
350-2 4-10 G, H, I 400 400 400 200 60 30 100,000 A
350-250 4-8 G, H, I 600 600 - - - - 50,000 A
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
High SCCR with Fuse Protection UL 1059
XCFR2 - E62806
Configuration
Wire
Line Load Line Load Line Load Class J T RK1 RK5 G CC
250-1/0 250-1/0 B, C 400 400 400 200 60 30 100,000 A
250-1/0 250-1/0 B, C 600 600 - - - - 50,000 A
EPBAP71 1 (2) 250 - 6 (2) 250 - 6 250-6 250-6 B, C 400 400 400 100 60 30 100,000 A
250-1/0 250-1/0 G, H, I 300 300 200 100 60 30 100,000 A
(1) 400 - 6 400-3/0 2-8 B, C 400 400 400 200 60 30 100,000 A
EPBAP74 400-6 2-10 B, C 200 200 200 100 60 30 100,000 A
(1) 2/0 - 14 400-6 2-10 G, H, I 300 300 200 100 60 30 100,000 A
250-1/0 250-1/0 B, C 400 400 400 200 60 30 100,000 A
250-1/0 250-1/0 B, C 600 600 - - - - 50,000 A
EPBCP71 1 (2) 250 - 6 (2) 250 - 6 250-6 250-6 B, C 400 400 400 100 60 30 100,000 A
250-1/0 250-1/0 G, H, I 300 300 200 100 60 30 100,000 A
(1) 400 - 6 400-3/0 2-8 B, C 400 400 400 200 60 30 100,000 A
400-6
2-10
B, C
200
200
200
100
60
30
100,000 A
Marathon
Catalog # Poles Amps (openings) kcmil/AWG
Suitable Conductors
335
510
(8) 2 - 14
HIGH SCCR CONDITIONS
Overcurrent Protection Fuse Required
Class/Max Amp Rating
(3)
SCCR, RMS SYM
Amps (1)
(kcmil/AWG)
(2)
510
335
POWER BLOCK DESCRIPTION
Rated Wire Range
1 (8) 2 - 14
EPBCP74
400-6
2-10
B, C
200
200
200
100
60
30
100,000 A
(1) 2/0 - 14 400-6 2-10 G, H, I 300 300 200 100 60 30 100,000 A
SCCR, RMS
SYM Amps
(1)
Line Load L J T RK1 RK5
BFPB 2 750 - 350 kcmil 1200 600 1200 600 600 100,000 A
3 Lugs 10x100x1 - 4x32x1 1200 600 1200 600 600 100,000 A
4 1605 or 750 - 350 kcmil No Over-Protection Device Required 35,000 A
5 Flexibar 10x100x1 - 4x32x1 No Over-Protection Device Required 35,000 A
6 Applicable lugs/Flexibar No Over-Protection Device Required 10,000
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
(8) 2 - 14
Class/Max Amp Rating
(3)
(kcmil/AWG)
(2)
Overcurrent Protection Fuse RequiredSuitable Conductors
335
EPBCP74
High SCCR with Circuit Breaker Protection
UL 1059
XCFR2 - E62806
Marathon Volts SCCR, RMS
Catalog #
Poles
Max
SYM Amps
(1)
Line Load
1321580 1 2/0-10 4-10 Square D JJL36250 600 480 65,000
1322580 2 2/0-10 4-10 Square D JJL36250 600 600 25,000
1323580 3 18,000
35,000
1402401 2 65,000
1403401 3 65,000
18,000
18,000
35,000
1411300 1 65,000
1412300 2 65,000
1413300 3 18,000
1414300 4 35,000
65,000
65,000
2 - 10 10-14 25,000
22,000
POWER BLOCK DESCRIPTION HIGH SCCR CONDITIONS
Overcurrent Protection
Circuit Breaker Required
Suitable Conductors
(kcmil/AWG)
(2)
Max AmpMfr Type
JGL36250
JLL36250
480
HLL36100
140U-H3C3
125
140U-H6C3
(1) 2/0-6 (6) 4-10
Square D
Square D
(1) 2-6
HGL36100
HJL36100
HDL36100
JGL36250
JJL36250
480
480
480
Allen Bradley
250
100
JDL36250
250
JJL36250
JLL36250
(1) 2-6
(1) 8-10 (1) 8-10
JDL36250
JDL36250
Square D
22,000
2-10 10-12 140G-H3I3 25,000
1411400 1 18,000
1412400 2 35,000
1413400 3 65,000
1414400 4 65,000
18,000
35,000
65,000
65,000
35,000
1421121 1 65,000
1422121 2 65,000
1423121 3 18,000
2/0-1 4-10
2-4 4-10
2-6 4-12 30,000
1421570 1 6 14 22,000
1422570 2 2/0-6 4-12 35,000
1423570 3 2/0-6 4-14 35,000
2/0-4 4-10 35,000
480 35,000
480 65,000
480 65,000
600 25,000
480 18,000
Allen Bradley 140G-H3C3
140G-H6C3
(1) 2/0-10
18,000
JDL36250
480
480
100
480
250
250
(4) 4-10
(4) 14 480
JLL36250
JLL36250
140U-J3D3
125
HDL36100
140G-J6D3
(1) 1/0-8(1) 1/0-8 Square D 250
JGL36250
140U-H6C3 125
Square D
125
250
250
JDL36250
HGL36100
140U-J6D3
JGL36250
JJL36250
140U-H3C3
JJL36250
JJL36250
(1) 8-10
(1) 2-6 (4) 10
(1) 8-10 (4) 14
Square D
125
125
140U-H6C3
JGL36250
JJL36250
JLL36250
HLL36100
HJL36100
Allen Bradley
Square D
JDL36250
480
1421970 1 35,000
1422970 2 (1) 2/0-8 (4) 4-8 480 65,000
1423970 3 65,000
35,000
1431552 1 65,000
1432552 2 65,000
1433552 3 18,000
1431553 1
1432553 2 400-3/0 2-8 400 35,000
1433553 3 4/0-4 2-10 250 35,000
(1) 2/0-6 (6) 2-10 JGL36250 250 480 35,000
JJL36250 250 480 65,000
JLL36250 250 480 65,000
JDL36250 250 480 18,000
400-6 4-8 LJL36600 600 480 65,000
400-6 2-8 LJL36600 600 600 25,000
350-6 2-10 JJL36250 600 600 25,000
35,000
1431555 1 65,000
1432555 2 65,000
1433555 3 18,000
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
JLL36250
140G-J6D3
Allen-Bradley
JJL36250
JLL36250
JDL36250
JJL36250
(2) 1/0-8 (6) 4-10
400-3/0 2-8
4/0-4 2-12
Square D
480250
JGL36250
JLL36250
Square D
JDL36250
JJL36250
65,000
25,000
140U-K3X3 400
250
140U-K6X3
140U-J6X3
140U-J3X3 480
140G-K3I3
(1) 2/0-4 (4) 2-8 480Square D 250
JGL36250
Square D JGL36250 250
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
High SCCR with Circuit Breaker Protection
UL 1059
XCFR2 - E62806
Marathon Volts SCCR, RMS
Catalog # Poles Max
SYM Amps
(1)
Line
Load
2/0-4 2-8 JDL36250 18,000
1431953 1 JGL36250 35,000
1432953 2 JJL36250 65,000
1433953 3 JLL36250 65,000
500-4 2-10 LJL36600 600 480 65,000
2-8 LJL36600 600 600 25,000
35,000
65,000
1431955 1 65,000
1432955 2 18,000
1433955 3 35,000
65,000
65,000
18,000
2/0-6 2-10 JGL36250 250 480 35,000
1441560 1 JJL36250 250 480 65,000
1442560 2 JLL36250 250 480 65,000
1443560
3
JDL36250
250
480
18,000
250 480
Square D
Square D
250
175
480
250
175
480
JJL36175
JLL36175
JLL36250
JGL36175
JDL36175
(2) 2/0-2 (6) 4-8 Square D
(2) 4-6 (6) 10-12
JDL36250
(kcmil/AWG)
(2)
Square D
JGL36250
Max AmpMfr Type
JJL36250
POWER BLOCK DESCRIPTION HIGH SCCR CONDITIONS
Overcurrent Protection
Circuit Breaker Required
Suitable Conductors
1443560
3
JDL36250
250
480
18,000
400-6 2-8 LJL36600 600 600 65,000
350-4 2-10 Allen Bradley 140U-J3D3 250 480 35,000
500-2 2-6 140G-K3I3 400 480 35,000
1451552 1 350-4 2-10 140G-J3D3 250 480 35,000
1452552 2 500-4 2-6 140U-K3D3 400 480 35,000
1453552 3 (1) 2/0-4 (12) 2-8 35,000
65,000
65,000
18,000
35,000
1451579 1 65,000
1452579 2 65,000
1453579 3 18,000
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
Square D 250 480
JLL36250
JDL36250
JLL36250
JJL36250
JGL36250
JGL36250
JJL36250 250 480Square D(1) 2/0-4 (6) 8
JDL36250
Listed Power Blocks
UL 1059
XCFR2 - E62806
Marathon SCCR, RMS Volts
Catalog # Poles
SYM Amps
(1)
Max
Line
Load
J
T
RK1
RK5
G
CC
FPB23570 3 2/0-6 4-10 200 200 200 100 60 30 100,000 600
FPB23572 3 2/0-6 2/0-6 200 200 200 100 60 30 100,000 600
2/0-6 2/0-6 200 200 200 100 60 30
FPB23574 3 100,000 600
2/0-10 2/0-10 100 100 100 30 60 30
FPB23580 3 2/0-6 4-10 200 200 200 100 60 30 100,000 600
400-3/0 2-8 400 400 400 100 60 30
FPB33553 3 100,000 600
2/0-2 2-14 200 200 200 100 60 30
600-3/0 1/0-8 450 450 400 100 60 30
FPB33588 3 100,000 600
600-2
1/0-10
200
200
200
100
60
30
(kcmil/AWG)
(2)
POWER BLOCK DESCRIPTION HIGH SCCR CONDITIONS
Overcurrent Protection Fuse Required
Class/Max Amp Rating
(3)
Suitable Conductors
600-3/0 4-8 450 450 400 100 60 30
FPB33595 3 100,000 600
600-2 4-10 200 200 200 100 60 30
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR
Marathon SCCR, RMS Volts
Catalog # Poles
SYM Amps
Max
Line
Load
2/0-2 4-8 JLL36250 250 65,000 480
2/0-4 4-8 140U-J6 250 50,000 480
FPB23570 3 2/0-4 4-8 140U-J0 250 50,000 480
1/0-6 4-10 140U-H6 125 50,000 480
1/0-6 4-10 140U-H0 125 50,000 480
2/0-2 4-8 JLL36250 250 65,000 480
2/0-6 4-12 140U-H6 125 50,000 480
FPB23580 3 2/0-6 4-12 140U-H0 125 50,000 480
2/0-4 4-8 140U-J6 250 35,000 480
2/0-4 4-8 140U-J0 250 35,000 480
FPB23572 3 2/0-2 2/0-2 JLL36250 250 65,000 480
Square D
Square D
Allen Bradley
Allen Bradley
Allen Bradley
Allen Bradley
Square D
Max Amp
Circuit Breaker Allowed
Mfg Type
Allen Bradley
POWER BLOCK DESCRIPTION HIGH SCCR CONDITIONS
Suitable Conductors Maximum Overcurrent Protection
Copper (kcmil/AWG)
Allen Bradley
Allen Bradley
Allen Bradley
FPB23574 3 2/0-2 2/0-2 JLL36250 250 65,000 480
18,000
35,000
65,000
65,000
400-3 2-3 35,000
350-4 2-8 50,000
50,000
18,000
35,000
65,000
65,000
600-2 1/0-4 35,000
350-2 1/0-8 50,000
50,000
18,000
35,000
65,000
65,000
600-2 4 30,000
350-2 4-8 50,000
50,000
140U-J0
140U-J6 250
140U-J0
480
JGL36250
JJL36250
JLL36250
JDL36250
JLL36250
2/0-2 2-8 Square D
JDL36250
250
Allen Bradley 140U-K6 400
140U-J6 250
400
140U-J6
Allen Bradley 250
FPB33595 3
2/0-2 4-10 Square D
3
Square D JDL36250
JGL36250 250
JLL36250
JJL36250
3FPB33553
FPB33588
480
140U-J0
JJL36250
2/0-6 2-10 Square D
140U-K6
Allen Bradley 140U-K6 400
250
480
JGL36250
Listed Power Distribution Blocks
UL 1953
QPQS.E309401
Configuration Wire
Line Load Line Load Line Load Class J T RK1 RK5 G CC
2-14 2-14 B, C 175 225 100 60 60 30 100,000 A
1 (1) 2 - 14 (1) 2 - 14 4 - 14 (class G,H,I,K) 4 - 14 (class G,H,I,K) G, H, I 300 300 200 100 60 30 100,000 A
2 - 10 10 - 14 B, C 125 200 100 30 60 30 65,000 A
1(1) 2 - 14 (4) 10 - 14 4- 10 (class G,H,I,K) 10 - 14 (class G,H,I,K) G, H, I 125 200 100 100 60 30 65,000 A
EPBAD42 3/0-8 3/0-8 B, C 225 225 200 60 60 30 100,000 A
EPBAP42 1 175 (1) 3/0 - 14 (1) 3/0 - 14 2/0-8 2/0-8 G, H, I 300 300 200 100 60 30 100,000 A
EPBCD42
EPBCP42
EPBAD45 3/0-8 2-8 B, C 225 225 200 60 60 30 100,000 A
EPBAP45 1 175 (1) 3/0 - 14 (4) 2 - 14 3/0-8 8-14 B, C 100 110 100 30 60 30 100,000 A
EPBCD45 2/0-8 4-8 G, H, I 225 225 200 60 60 30 100,000 A
EPBCP45 2/0-8 8-12 G, H, I 100 110 100 30 60 30 100,000 A
1351701 1 750-1/0 750-1/0 B, C 600 1200 600 400 60 - 100,000 A
1352701
2
475
750 - 1/0
750 - 1/0
535-1/0
535-1/0
G, H, I
600
700
600
200
60
-
100,000 A
POWER BLOCK DESCRIPTION HIGH SCCR CONDITIONS
Overcurrent Protection Fuse Required
Class/Max Amp Rating
(3)
Suitable Conductors
(kcmil/AWG)
(2)
Marathon Catalog
# Poles SCCR, RMS
SYM Amps (1)
115EPBAD24
115EPBAD21
Rated Wire Range
(openings) kcmil/AWG
Amps
1352701
2
475
750 - 1/0
750 - 1/0
535-1/0
535-1/0
G, H, I
600
700
600
200
60
-
100,000 A
1353701 3
1351702 1 750-1/0 750-1/0 B, C 600 1200 600 400 60 - 100,000 A
1352702 2 950 (2) 750 - 1/0 (2) 750 - 1/0 535-1/0 535-1/0 G, H, I 600 700 600 200 60 - 100,000 A
1353702 3
1351703 1 750-1/0 250-2 B, C 600 700 600 200 60 - 100,000 A
1352703 2 950 (2) 750 - 1/0 (6) 250 - 6 750-1/0 250-6 B, C 300 300 200 100 60 - 100,000 A
1353703 3 535-1/0 3/0-2 G, H, I 600 700 600 200 60 - 100,000 A
535-1/0 3/0-6 G, H, I 300 300 200 100 60 - 100,000 A
1351704 1 750-1/0 2/0-2 B, C 600 700 600 200 60 - 100,000 A
1352704 2 950 (2) 750 - 1/0 (10) 2/0 - 6 750-1/0 2/0-6 B, C 300 300 200 100 60 -100,000 A
1353704 3535-1/0 1-2 G, H, I 600 700 600 200 60 - 100,000 A
535-1/0 1-6 G, H, I 300 300 200 100 60 - 100,000 A
750-1/0 250-2 B, C 600 700 600 200 60 - 100,000 A
1351705 1 750-1/0 250 - 6 B, C 300 300 200 100 60 - 100,000 A
1352705 2 950 (2) 750 - 1/0 (3) 250 - 6 750-1/0 2 - 6 (#2 opening) B, C 300 300 200 100 60 - 100,000 A
1353705 3 (12) 2 - 14 535-1/0 3/0-2 G, H, I 600 700 600 200 60 - 100,000 A
535-1/0 3/0-6 G, H, I 300 300 200 100 60 - 100,000 A
535-1/0 4 - 6 (#2 opening) G, H, I 300 300 200 100 60 - 100,000 A
750-1/0 250-2 B, C 600 600 600 200 60 - 100,000 A
1351706 1 750-1/0 250 - 6 B, C 300 300 200 100 60 - 100,000 A
1352706 2 950 (2) 750 - 1/0 (5) 250 - 6 750-1/0 2 - 6 (#2 opening) B, C 300 300 200 100 60 - 100,000 A
1353706 3 (4) 2 - 14 535-1/0 3/0-2 G, H, I 600 600 600 200 60 - 100,000 A
535-1/0 3/0-6 G, H, I 300 300 200 100 60 - 100,000 A
535-1/0 4 - 6 (#2 opening) G, H, I 300 300 200 100 60 - 100,000 A
750-1/0 3/0-2 B, C 600 700 600 200 60 - 100,000 A
1351707 1 750-1/0 3/0 - 6 B, C 300 300 200 100 60 - 100,000 A
1352707 2 950 (2) 750 - 1/0 (4) 3/0 - 6 750-1/0 2 - 6 (#2 opening) B, C 300 300 200 100 60 - 100,000 A
1353707 3 (12) 2 - 14 535-1/0 2/0-2 G, H, I 500 500 400 200 60 - 100,000 A
535-1/0 2/0-6 G, H, I 300 300 200 100 60 - 100,000 A
535-1/0 4 - 6 (#2 opening) G, H, I 300 300 200 100 60 - 100,000 A
1351708 1 750-1/0 3/0-2 B, C 600 700 600 200 60 - 100,000 A
1352708 2 950 (2) 750 - 1/0 (8) 3/0 - 6 750-1/0 3/0 - 6 B, C 300 300 200 100 60 - 100,000 A
1353708 3 535-1/0 3/0-2 G, H, I 500 500 400 200 60 -100,000 A
535-1/0 2/0-6 G, H, I 300 300 200 100 60 - 100,000 A
(1) Short-circuit current ratings may be marked on the block or instructions provided with the terminal block
(2) Size range of conductors suitable to maintain noted SCCR
(3) Maximum size of line side overcurrent protection to provide noted SCCR