https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://download.phoenixcontact.com) MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection, input signal: 0 ... 10 V/10 V, output signal: 0 ... 10 V/10 V Product description The 6.2 mm wide standard signal 3-way isolating amplifier MINI MCR-SL-U-U(-SP) is used for electrical isolation, amplification and filtering of standard signals. On the input and output side, the analog standard signals 0...10 V or 10 V are available, electrically isolated. Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector. Product Features Power supply possible via the foot element (T-connector) Low power consumption Entry-level alternative to configurable signal conditioners Fixed signal combinations Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals 3-way isolation Key commercial data Packing unit 1 pc Weight per Piece (excluding packing) 71.0 GRM Custom tariff number 85437090 Country of origin Germany Technical data Note: Utilization restriction EMC: class A product, see manufacturer's declaration in the download area Dimensions 04/20/2014 Page 1 / 7 https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Technical data Dimensions Width 6.2 mm Height 93.1 mm Depth 102.5 mm Ambient conditions Ambient temperature (operation) -20 C ... 65 C Ambient temperature (storage/transport) -40 C ... 85 C Degree of protection IP20 Input data Configurable/programmable No Voltage input signal 0 V ... 10 V -10 V ... 10 V Max. input voltage 30 V Input resistance of voltage input approx. 100 k Output data Configurable/programmable No Voltage output signal 0 V ... 10 V -10 V ... 10 V Max. output voltage 12.5 V Short-circuit current approx. 2 mA Load/output load voltage output 10 k Power supply Nominal supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) Max. current consumption < 20 mA Power consumption < 240 mW (at 24 V DC) Connection data Connection method Screw connection Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 2.5 mm Conductor cross section AWG/kcmil min. 26 Conductor cross section AWG/kcmil max 12 Conductor cross section stranded min. 0.2 mm Conductor cross section stranded max. 2.5 mm Stripping length 12 mm 04/20/2014 Page 2 / 7 https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Technical data Connection data Screw thread M3 General No. of channels 1 Maximum transmission error 0.1 % (of final value) Maximum temperature coefficient < 0.01 %/K Temperature coefficient, typical < 0.002 %/K Limit frequency (3 dB) approx. 100 Hz Step response (10-90%) approx. 3.2 ms Protective circuit Transient protection Electrical isolation Basic insulation according to EN 61010 Surge voltage category II Pollution degree 2 Rated insulation voltage 50 V AC/DC Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.) Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC Noise emission EN 61000-6-4 Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations. Color green Housing material PBT Mounting position any Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. Conformance CE-compliant ATEX II 3 G Ex nA IIC T4 Gc X UL, USA / Canada UL 508 Recognized Class I, Div. 2, Groups A, B, C, D T5 GL GL EMC 2 D EMC data Designation Electromagnetic RF field Standards/regulations EN 61000-4-3 Typical deviation from the measuring range final value 15 % Designation Fast transients (burst) Standards/regulations EN 61000-4-4 Typical deviation from the measuring range final value 15 % Designation Conducted interferences Standards/regulations EN 61000-4-6 04/20/2014 Page 3 / 7 https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Technical data EMC data Typical deviation from the measuring range final value 15 % Classifications eCl@ss eCl@ss 4.0 27210120 eCl@ss 4.1 27210120 eCl@ss 5.0 27210120 eCl@ss 5.1 27210120 eCl@ss 6.0 27210120 eCl@ss 7.0 27210120 eCl@ss 8.0 27210120 ETIM ETIM 2.0 EC001485 ETIM 3.0 EC001485 ETIM 4.0 EC001485 ETIM 5.0 EC001485 UNSPSC UNSPSC 6.01 30211506 UNSPSC 7.0901 39121008 UNSPSC 11 39121008 UNSPSC 12.01 39121008 UNSPSC 13.2 39121008 Approvals Approvals Approvals UL Recognized / cUL Recognized / GL / cULus Recognized Ex Approvals UL Listed / cUL Listed / ATEX / cULus Listed 04/20/2014 Page 4 / 7 https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Approvals Approvals submitted Approval details UL Recognized cUL Recognized GL cULus Recognized Accessories Accessories DIN rail connector Electronic housing - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728 DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos. Marking material Transparent cover - MINI MCR DKL - 2308111 Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack marker strip 6.2 mm 04/20/2014 Page 5 / 7 https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Accessories Marking label - MINI MCR-DKL-LABEL - 2810272 Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL Power module Power terminal block - MINI MCR-SL-PTB - 2864134 MCR power terminal block for supplying several MINI Analog modules via the T-connector, with screw connection, maximum current consumption of up to 2 A Power terminal block - MINI MCR-SL-PTB-SP - 2864147 MCR power terminal block for supplying several MINI Analog modules via the T-connector, with spring-cage connection, maximum current consumption of up to 2 A Power supply Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983 DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A Power supply unit - MINI-PS-100-240AC/24DC/1.5/EX - 2866653 DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A, ATEX approval 04/20/2014 Page 6 / 7 https://www.phoenixcontact.com/us/products/2864684 Signal conditioner - MINI MCR-SL-U-U - 2864684 Accessories Drawings Block diagram Dimensioned drawing 93,1 1 + 1 IN U OUT U 5 + 5 active 4-wire GND 2 - 2 + 3 - 4 passive GND 2 GND 1 6 - +24V +24V GND 3 6,2 PLC / DCS 6 7 + GND 3 8 - 102,5 OUT U US OUT IN Sensor / Field +24V GND 3 Zone 2 Div. 2 Phoenix Contact 2014 (c) - all rights reserved http://www.phoenixcontact.com 04/20/2014 Page 7 / 7