https://www.phoenixcontact.com/us/products/2864684
04/20/2014Page3/7
Signal conditioner-MINI MCR-SL-U-U-2864684
Technical data
Connection data
Screw thread M3
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Limit frequency (3 dB) approx. 100 Hz
Step response (10-90%) approx. 3.2 ms
Protective circuit Transient protection
Electrical isolation Basic insulation according to EN 61010
Surge voltage category II
Pollution degree 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance CE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL GL EMC 2 D
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 15 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 15 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6