General data
Width 72 mm
Height 90 mm
Depth 61 mm
Net weight 0.3 kg
Operating voltage display Green LED
Efficiency > 87 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Degree of protection IP20
Protection class II
MTBF (IEC 61709, SN 29500) > 500000 h (IEC 61709)
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Can be aligned: horizontal 0 cm, vertical 3 cm
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise immunity EN 61000-6-2:2005
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204
Standard - Safety of transformers IEC 61558-2-17
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Shipbuilding approval Germanischer Lloyd (EMC 1), ABS, NK
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Standard – Protection against electric shock DIN 57100-410
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents EN 61000-3-2
Certificate CB Scheme