Surge Arrester N81-A230XG
2-Electrode-Arrester Ordering code: B88069X4960T502
AB E / AB PM Issue 02, 26.04.2002
Page 1 of 2
DC spark-over voltage 1) 2)
230
± 20
V
%
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs - for 99 % of measured values
- typical values of distribution
< 500
< 450
< 700
< 600
V
V
V
V
Nominal impulse discharge current (wave 8/20 µs)
Single impulse discharge current (wave 8/20 µs)
10
12
kA
kA
Nominal alternating discharge current (50 Hz, 1 s)
Alternating discharge current (50 Hz, 9 cycles)
10
65
A
A
Insulation resistance at 100 Vdc > 10 GΩ
Capacitance at 1 MHz < 1.5 pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 15
~ 0.5
~ 60
V
A
V
Weight ~ 1.5 g
Operation and storage temperature -40 ... +90 °C
Climatic category (IEC 60068-1) 40/ 90/ 21
Marking, red
230 YY O
230 - Nominal voltage
YY - Year of production
O - Non radioactive
1) At delivery AQL 0.65 level II, DIN ISO 2859
2) In ionized mode
Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845