2Specifications are subject to change without notice (14.12.99)
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage (IEC 60038)
through term. A1 & A2 T23 115-230 VAC, -10/+15%
frequency 50/60 Hz, -5/+5 Hz
through term. A2 & A3 T23 24 VAC/DC, -10/+15%
frequency 50/60 Hz, -5/+5 Hz
Voltage interruption ≤40 ms
Dielectric voltage none
Rated impulse withstand
voltage 4 kV (1.2/50 µs)
Rated operational current 20 mA @ 24 VDC
40 mA @ 24 VAC
20 mA @115 VAC
40 mA @ 230 VAC
General Specifications
EMC Electromagnetic
Compatibility
Immunity acc. to IEC 60801-4 (level 3)
acc. to IEC 60801-5 (level 3)
Power ON delay ≤200 ms
Power OFF delay ≥200 ms
Indication for
Power supply ON LED, green
Output ON LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature -20 to +50°C (-4 to +122°F)
Storage temperature
-50 to +85°C (-58 to +185°F)
Weight 125 g
Screw terminals
Tightening torque
Max. 0.5 Nm acc. to IEC 947
CE-marking Yes
EAM
Mode of Operation
The delay period begins when
power supply is applied. At the end of the set delay, the
relay will operate and will not
release until power supply is
interrupted for at least 200 ms.
If power supply is interrupted
for at least 200 ms before the
relay operates, the time cir-
cuit is reset to zero, and the
relay is ready for a new time
period.
Operation Diagram
Power supply
Relay ON
Wiring Diagram
µ
N
L
24 V ~
115-230 V ~
Time Setting
Selection of time ranges
Upper knob:
3-position rotary switch.
Selection of scale
Centre knob:
2-position rotary switch.
Time setting
Lower knob:
Knob-adjustable on relative
scale 1-10.