EX9PA050
Current Sensor
0 to 5 Amperes
Applications:
Current measurements and control
Power demand measurements
Current signature of motors
Load sensing
Ground fault sensing
Monitoring of process parameters
Status of lamps, heaters
Power failure
Loss of device
Features:
Low cost AC current sensing
Designed for easy electronic interface
Electrically isolated output
No external power requirements
Printed circuit board mounting
Extremely reliable
Fax toll-free to our Engineering
Hotline (1-800-355-5125) for assistance
in selecting the current transformer best
suited for your application.
BICRON’s “Modified Standard”
program lets us modify our standard electri-
cal and mechanical design specifications
without incurring significant engineering or
manufacturing setup charges. This is just one
of the many ways we can help optimize your
current transformer system at low cost and
with little delay.
.77
.50
.30
.15
.30
1.11
.48
1
23
4
3
2
.18
.15 Dia.
Window
Schematic
Ip
Specifications:
Turns Ratio . . . . . . . 200:1
DCR . . . . . . . . . . . . . . 1.6
Error . . . . . . . . . . . . . 5% max.
Frequency . . . . . . . . 47–400Hz
Current Range . . . . . 0 –5Arms
Overload Current . . 20Arms
Ambient . . . . . . . . . . -35°C to +80°C
Programmable
Burden (load)
Resistor (Rs) . . . . . . . User Supplied
Performance
per Equation . . . . . . Vs=(I
p)(Rs)/200
0
0.02
0.04
0.06
0.08
0.10
0.12
02.0 3.0 4.0 5.0
1.0
Buss Current Ip (Amps)
Output Voltage Vs (Volts)
20 8 4
Output Voltage vs. Buss Current
Data subject to change
Actual Size
2696 Certified ISO 9001