660VDC FERRULE FUSES /SPECIAL PURPOSE
G 33
660V DC
gRB FROM 0.8 TO 110A
SIZE: 27X60
SIZE CURRENT
RATING
IN(A)
INTERRUPTING
RATING CATALOG NUMBER REF. NUMBER
APPLICATIONS DATA
Minimum trip voltage: 20V
See Fuse Blocks and Fuse Holders.
27
x
60
0.8
1
1.5
2
3.15
4
5
6.3
8
10
12
16
20
25
32
40
50
63
80
100
110
WATTS LOSS
0.8 ININ
@ 660V DC
50kA
L/R = 15ms
0.25
0.25
0.35
0.4
0.6
0.6
0.7
0.8
1.2
1.3
1.4
1.9
2.4
2.8
3.5
4.7
4.8
5.6
6.4
7.4
7.7
0.4
0.4
0.6
0.7
1
1
1.1
1.3
2
2.3
2.4
3.3
4.1
4.7
6
8
8.3
9.6
11.2
12.9
13.7
CC 6,621 CPgRB 27x60/0.8
CC 6,621 CP gRB 27x60/1
CC 6,621 CP gRB 27x60/1.5
CC 6,621 CP gRB 27x60/2
CC 6,621 CP gRB 27x60/3.15
CC 6,621 CP gRB 27x60/4
CC 6,621 CP gRB 27x60/5
CC 6,621 CP gRB 27x60/6.3
CC 6,621 CP gRB 27x60/8
CC 6,621 CP gRB 27x60/10
CC 6,621 CP gRB 27x60/12
CC 6,621 CP gRB 27x60/16
CC 6,621 CP gRB 27x60/20
CC 6,621 CP gRB 27x60/25
CC 6,621 CP gRB 27x60/32
CC 6,621 CP gRB 27x60/40
CC 6,621 CP gRB 27x60/50
CC 6,621 CP gRB 27x60/63
CC 6,621 CP gRB 27x60/80
CC 6,621 CP gRB 27x60/100
CC 6,621 CP gRB 27x60/110
H098585
J098586
K098587
P098591
Q098592
R098593
T098595
Z098600
L076301
M076302
L075703
N076303
C077006
M075635
P076304
Q076305
R076306
P079961
S079964
T099400
S076307
Trip force: 4.5N at 0mm-2.5N at 7mm
Dimensions
60,3
Ø 27
Ø 5
7
G
1000V DC FERRULE FUSES /SPECIAL PURPOSE
G 34
DC Application Data Peak Arc voltage vs. working voltage
Time vs. current characteristics
Above: Curve indicates the maximum permissible value of time
constant L/R as a function of DC working voltage.
Max. AC voltage (50/60 Hz): 1500V with interrrupting
rating of 100kA. 1-L/R = 50ms
2-L/R = 25ms
3-L/R = 15ms
Above: Curves indicate for various time constants L/R the peak
arc voltage, which may appear across the fuse terminals, vs. DC
working voltage.
Above: Curves indicate, for each rated current, pre-arcing time vs. R.M.S. pre-arcing current.
9% tolerance for mean
pre-arcing current
+
-
0 100 300 500 700 900
0
200
400
600
800
1000
1400
1600
1800
2000
1200
L/R (ms)
90
80
70
60
50
40
30
20
10
0
700
800
900
1000
1100
1200
Um (V)
a=130
A2=0.6
B1=1.25
B2=0.6
Cf3=0.8
10 2
10 3
10 4
10 4
10 3
10 2
10
1
10-1
10-2
10-3
10-4
1
t (s)
U(V)
10 I(A)
6
8
10
12
16
20
25
32
40
50
63
1500V DC FERRULE FUSES /SPECIAL PURPOSE
G 35
1500V DC
gRB-gRD FROM 0.8 TO 25A
SIZE: 20X127
SIZE CURRENT
RATING
IN(A)
INTERRUPTING
RATING CATALOG NUMBER REF.
NUMBER
APPLICATIONS DATA
Minimum trip voltage: 50V
(1) Fuses CC 1551 CP gRB 20x...D150 gRB...UL Recognized
See Fuse Blocks and Fuse Holders, and Medium Voltage fuse clips
20
x
127
0.8
1
1.5
2
3.15
4
5
0.8
1
1.5
2
3.15
4
5
6
8
10
12
16
20
25
WATTS LOSS
0.8 ININ
@ 1000V DC
100kA
L/R = 100ms
@ 1000V DC
30kA
L/R = 30ms
@ 1500V DC
30kA
L/R = 55ms
0.5
0.5
0.8
0.9
1.2
1.3
1.4
0.5
0.5
0.8
0.9
1.2
1.3
1.4
3.4
3.3
3.5
3.9
5
5.3
6.6
0.9
0.9
1.4
1.6
2.1
2.1
2.3
0.9
0.9
1.4
1.6
2.1
2.1
2.3
6.3
6.0
6.1
6.8
8.9
9.6
12
CC 1551 CP gRB 20x127/0.8 D 150 gRB 0.8 VI(1)
CC 1551 CP gRB 20x127/1 D 150 gRB 001 VI(1)
CC 1551 CP gRB 20x127/1.5 D 150 gRB 01.5 VI(1)
CC 1551 CP gRB 20x127/2 D 150 gRB 002 VI(1)
CC 1551 CP gRB 20x127/3.15 D 150 gRB 3.15 VI(1)
CC 1551 CP gRB 20x127/4 D 150 gRB 004 VI(1)
CC 1551 CP gRB 20x127/5 D 150 gRB 005 VI(1)
CC 1500 CP gRB 20x127/0.8 D 150 gRB 0.8 V
CC 1500 CP gRB 20x127/1 D 150 gRB 001 V
CC 1500 CP gRB 20x127/1.5 D 150 gRB 01.5 V
CC 1500 CP gRB 20x127/2 D 150 gRB 002 V
CC 1500 CP gRB 20x127/3.15 D 150 gRB 3.15 V
CC 1500 CP gRB 20x127/4 D 150 gRB 004 V
CC 1500 CP gRB 20x127/5 D 150 gRB 005 V
CC 1500 CP gRD 20x127/6 D 150 gRB 006 V
CC 1500 CP gRD 20x127/8 D 150 gRB 008 V
CC 1500 CP gRD 20x127/10 D 150 gRB 010 V
CC 1500 CP gRD 20x12712 D 150 gRB 012 V
CC 1500 CP gRD 20x127/16 D 150 gRB 016 V
CC 1500 CP gRD 20x127/20 D 150 gRB 020 V
CC 1500 CP gRD 20x127/25 D 150 gRB 025 V
E075743
E075744
G075745
B088367
H075746
J075747
C088368
J081842
R079894
K081843
Y099243
L081844
Z099244
A099245
E082804
Z080867
F081655
B080593
Q081457
D082803
A080431
Trip force: 4.5N at 0mm-2.5N at 7mm
Dimensions
PACK
3
and
10
pieces
127 7 mini
CC 1551......
Weight: 87g
Weight: 87g
20.6 5
8
G
1500V DC FERRULE FUSES/SPECIAL PURPOSE
G 36
DC Application Data Peak Arc voltage vs. working voltage
Time vs. current characteristics
Above: Curves indicate maximum permissible value of time
constant L/R as a function of DC working voltage.
Max. AC voltage (50/60 Hz): 2500V with interrrupting
rating of 50kA.
Curve 1: gRD @ L/R = 30ms
Curve 2: gRB @ L/R = 60ms
Curve 3: gRD @ L/R = 15ms
Curve 4: gRB @ L/R = 30ms
Above: Curves indicate for various time constants L/R peak arc
voltage, which may appear across the fuse terminals, vs. DC
working voltage.
Above: Curves indicate, for each rated current, pre-arcing time vs. R.M.S. pre-arcing current. 9% tolerance for mean
pre-arcing current
+
-
gRB without trip indicator gRB with indicator gRB without trip indicator
U (V)
90
80
70
60
50
40
30
20
10
0
1000
1400
1800
2200
2600
L/R (ms)
4000
3000
2000
1000
0
500
1000
1500
2000
a=130
A2=0.6
B1=1.25
B2=0.6
Cf3=0.8
10 2
10 3
10 4
10 3
10 2
10
1
10-1
10-2
10-3
10-4
1
t (s)
a=130
A2=0.6
B1=1.25
B2=0.6
Cf3=0.8
a=130
A2=0.6
B1=1.25
B2=0.6
Cf3=0.8
10 10 210 3
1 10 10 210 3
1 10
0.8
1
1.5
2
3.15
4
5
0.8 1
1.5
2
3.15
4
5
6
8
10
12
16
20
25
I (A)
1500V DC FERRULE FUSES /SPECIAL PURPOSE
G 37
1500V DC
gRC FROM 6 TO 32A
SIZE: 20X190
SIZE CURRENT
RATING
IN(A)
INTERRUPTING
RATING CATALOG NUMBER REF.
NUMBER
APPLICATIONS DATA
Minimum trip voltage: 90V
See Fuse Blocks and Fuse Holders, and Medium Voltage fuse clips
20
x
190
6
8
10
12
16
20
25
32
6
8
10
12
16
20
25
32
WATTS LOSS
0.8 ININ
@ 1500V DC
60kA
L/R = 40ms
4.8
5.3
6.5
7.0
8.0
9.5
12
16
4.8
5.3
6.5
7.0
8.0
9.5
12
16
7.8
8.8
10.5
11.5
13
15
19.5
26
7.8
8.8
10.5
11.5
13
15
19.5
26
CC 1591 CP gRC 20x190/6
CC 1591 CP gRC 20x190/8
CC 1591 CP gRC 20x190/10
CC 1591 CP gRC 20x190/12
CC 1591 CP gRC 20x190/16
CC 1591 CP gRC 20x190/20
CC 1591 CP gRC 20x190/25
CC 1591 CP gRC 20x190/32
CC 1500 CP gRC 20x190/6
CC 1500 CP gRC 20x190/8
CC 1500 CP gRC 20x190/10
CC 1500 CP gRC 20x190/12
CC 1500 CP gRC 20x190/16
CC 1500 CP gRC 20x190/20
CC 1500 CP gRC 20x190/25
CC 1500 CP gRC 20x190/32
D083102
V083738
G087245
Y080429
N088378
Q087345
Z080430
G085911
Z089469
A089470
B089471
C089472
D089473
E089474
F089475
G089476
Trip force: 4.5N at 0mm - 2.5N at 7mm
Dimensions
PACK
10
pieces
190
20.6 CC 1591
Weight: 176 g
7 mini
5
Weight: 176 g
CC 1500
G
AMP-TRAP®
1500V DC FERRULE FUSES /SPECIAL PURPOSE
G 38
DC Application Data Peak Arc voltage vs. working voltage
Time vs. current characteristics
Above: Curve indicates maximum permissible value of time
constant L/R as a function of DC working voltage.
Max. AC voltage (50/60 Hz): 2500V with interrrupting
rating of 50kA.
1-L/R = 45ms
2-L/R = 15ms
Above: Curves indicate for various time constants L/R peak arc
voltage, which may appear across the fuse terminals, vs. DC
working voltage.
Above: Curves indicate, for each rated current, pre-arcing time vs. R.M.S. pre-arcing current.
7% tolerance for mean
pre-arcing current
+
-
90
80
70
60
50
40
30
20
10
0
1000
1200
1400
1600
1800
2000
L/R (ms)
U (V)
4500
3000
1500
0
0
500
1000
1500
2000
U (V)
Um (V)
1
2
a=130
A2=0.6
B1=1.25
B2=0.6
Cf3=0.8
10 2
10 3
10 4
10 3
10 2
10
1
10-1
10-2
10-3
10-4
10
t (s)
6
810
12
16
20
25
32
10 4I (A)