SITOP modular
6EP1436-3BA00 (24V/20A)
6EP1437-3BA00 (24V/40A)
Betriebsanleitung (kompakt)
Operating Instructions (compact)
Instrucciones de servicio (resumidas)
操作说明 (精简版)
Notice de service (compacte)
Istruzioni operative (descrizione sintetica)
Руководство по эксплуатации (компактное)
https://support.industry.siemens.com
1: Ansicht Geräte
1: View of the units
1: Vista del aparato
1: 设备外观
1: Vue des appareils
1: Vista degli apparecchi
1: Внешний вид устройств
Die SITOP-Stromversorgungen 24 V/20 A und 40 A
sind Einbaugeräte, Schutzart IP20, Schutzklasse I.
Primär getaktete Stromversorgungen zum Anschluss
an 3-phasiges Wechselstromnetz (TN-, TT- oder IT-
Netz nach VDE 0100 T 300 / IEC 364-3) mit Nenn-
spannungen 400 - 500 V (IT-Netz: 400 - 460 V),
50 - 60 Hz; Ausgangsspannung +24 V DC, potenzial-
frei, kurzschluss- und leerlauffest.
Bild 1 Ansicht Geräte (Seite 1)
Der einwandfreie und sichere Betrieb dieses
Gerätes/Systems setzt sachgemäßen Transport,
sachgemäße Lagerung, Aufstellung und Montage
sowie sorgfältige Bedienung und Instandhaltung
voraus.
Dieses Gerät/System darf nur unter Beachtung der
Instruktionen und Warnhinweise der zugehörigen
Technischen Dokumentation eingerichtet und
betrieben werden.
Nur qualifiziertes Personal darf das Gerät/System
installieren und in Betrieb setzen.
Das Gerät erfüllt die ATEX Richtlinie 2014/34/EU;
SPANNUNGSEINSTELLUNG ODER
SCHALTERBETÄTIGUNG NUR IN NICHT-
EXPLOSIVER UMGEBUNG DURCHFÜHREN!
Montage auf Normprofilschiene TH35x7,5/15 (20 A) bzw.
TH35x15 (40 A) (EN60715)
Das Gerät ist so zu montieren, dass die Eingangs- und
Ausgangsklemmen unten sind.
Unterhalb und oberhalb des Gerätes muss mindestens
ein Freiraum von je 50 mm eingehalten werden.
Bei Installation des Gerätes in explosionsgefährdeter
Umgebung (II 3G Ex nA nC IIC T3 Gc) ist dieses in
einen Verteilerkasten mit Schutzart IP54 oder höher
einzubauen. Dieser Verteilerkasten muss den Anforde-
rungen der EN 60079-15 entsprechen.
Bild 2 Aufbau (Seite 2)
Vor Beginn der Installations- oder
Instandhaltungsarbeiten ist der Hauptschalter der
Anlage auszuschalten und gegen Wiedereinschalten
zu sichern. Bei Nichtbeachtung kann das Berühren
spannungsführender Teile Tod oder schwere
Körperverletzung zur Folge haben.
Die Betätigung des Potenziometers ist nur mittels
isoliertem Schraubendreher zulässig.
The 24 V/20 A and 40 A SITOP power supplies are
built-in units, IP20 degree of protection, protection
class I.
Primary switched-mode power supplies for connection
to a 3-phase AC line supply (TN, TT or IT line supply
according to VDE 0100 T 300 / IEC 364-3) with rated
voltages 400 - 500 V (IT line supply:
400 - 460 V), 50 - 60 Hz; output voltage +24 V DC,
isolated, short-circuit and no-load proof.
Image 1 View of the units (Page 1)
Appropriate transport, proper storage, mounting, and
installation, as well as careful operation and service,
are essential for the error-free, safe and reliable
operation of the device/system.
Setup and operation of this device/system are
permitted only if the instructions and warnings of the
corresponding documentation are observed.
Only qualified personnel are allowed to install the
device/system and set it into operation.
The device complies with ATEX directive 2014/34/EU;
OPERATE VOLTAGE ADJUSTMENT OR
SWITCHES IN NON-HAZARDOUS AREAS ONLY!
Mounted on a standard mounting rail TH35x7.5/15
(20 A) or TH35x15 (40 A) (EN60715)
The device must be mounted in such a way that the
input and output terminals are at the bottom.
A clearance of at least 50 mm must be maintained
above and below the device.
If the device is to be used in a hazardous zone (II 3G
Ex nA nC IIC T3 Gc) it must be installed in an enclo-
sure with degree of protection IP54 or higher. This
enclosure must comply with the requirements of EN
Image 2 Design (Page 2)
Before installation or maintenance work can begin,
the main system switch must be opened and
measures taken to prevent it from being reclosed. If
this instruction is not observed, touching live parts
can result in death or serious injury.
It is only permissible to use an insulated screwdriver
when actuating the potentiometer.
Las fuentes de alimentación SITOP de 24 V/20 A y 40 A
son aparatos empotrables con grado de protección IP20 y
clase de protección I.
Fuentes de alimentación conmutadas en primario para la
conexión a la red alterna trifásica (red TN, TT o IT según
VDE 0100 T 300 / IEC 364-3) con tensiones nominales 400
- 500 V (red IT: 400 - 460 V), 50 - 60 Hz; tensión de salida
+24 V DC, con aislamiento galvánico, resistente a cortocir-
Figura 1 Vista del aparato (Página 1)
El funcionamiento correcto y seguro de este
aparato/sistema presupone un transporte, un
almacenamiento, una instalación y un montaje
conformes a las prácticas de la buena ingeniería,
así como un manejo y un mantenimiento rigurosos.
Este aparato/sistema debe ajustarse y utilizarse
únicamente teniendo en cuenta las instrucciones y
advertencias de la documentación técnica
correspondiente.
La instalación y puesta en marcha del
aparato/sistema debe encomendarse
exclusivamente a personal cualificado.
El aparato cumple la directiva ATEX 2014/34/UE;
¡AJUSTAR LA TENSIÓN O ACCIONAR
INTERRUPTORES SÓLO EN ENTORNOS NO
EXPLOSIVOS!
Montaje en perfil normalizado TH35x7,5/15 (20 A) o
bien TH35x15 (40 A) (EN60715)
El aparato debe montarse de modo que los bornes de
entrada y salida queden abajo.
Por encima y por debajo del aparato debe dejarse un
espacio libre de al menos 50 mm.
Si se va a instalar el aparato en una atmósfera poten-
cialmente explosiva (II 3G Ex nA nC IIC T3 Gc), deberá
montarse en una caja con grado de protección IP54 o
superior. Esta caja debe cumplir los requisitos de EN
Figura 2 Diseño (Página 2)
Antes de comenzar los trabajos de instalación o
mantenimiento, se deberá abrir el interruptor
principal del cuadro/tablero y protegerlo para evitar
su cierre. Si no se observa esta medida, el contacto
con piezas bajo tensión puede provocar la muerte o
lesiones graves.
El potenciómetro solo deberá girarse usando un
destornillador aislado.
SITOP 电源 24 V/20 A 和 40 为内置设备,防护方式为
IP20,防护等级为 I。
本设备为主时钟电源,用于连接标称电压为
400 - 500 V(IT 电网为 400 - 460 V),50 - 60 Hz 的三
相交流供电系统(符合VDE 0100 T 300 / IEC 364-3标
准的 TN、TT 或 IT 电网)输出电压 +24 V DC,电位隔
离,具有短路保护和空载保护功能。
参见 图 1 设备外观 (页 1)
存放、装配、安装作业以及仔细谨慎的操作和维护。
请务必阅读并遵守本设备/系统技术文档中包含的规定
和警示,否则禁止安装和运行本设备。
本设备/系统仅允许由专业技术人员安装和调试。
本设备符合 ATEX 指令 2014/34/EU、EN 60079-0、
仅允许在无爆炸危险的环境下执行调压和开关操作!
安装到凹顶导轨 TH35x7.5/15 (20 A) 或 TH35x15 (40 A)
(EN60715)
安装设备时应使出线端子和入线端子位于下方。
设备的上方和下方必须至少保留 50 mm 的通风空间。
设备安装在有爆炸危险的环境 (II 3G Ex nA nC IIC T3
Gc) 中时 ,必须安装在防护方式符合 IP54 或满足更高
要求的配电箱中。该配电箱必须符合 EN 60079-15 规定
的要求。
参见 图 2 结构 (页 2)
开始安装或维护工作前应该关闭设备的主开关,防止
设备再次被接通。违反该规定可能会导致作业人员接
触到带电零部件,从而导致严重的人身伤害甚至死
亡。
电位计只允许使用绝缘螺丝刀进行操作。