2Specifications are subject to change without notice (28.09.99)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
General Specifications
Power ON delay Typ. 2 s
Indication for
Supply ON LED, green
Dupline®carrier LED, yellow
Environment
Operating temperature
-20° to +50°C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 - 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions Open PCB 74 x 59 mm
4 pcs. of nylon PA6 snap
locks are included for mount-
ing the PCB in ø 4.8 holes
Weight 100 g
Mode of Operation
Pin Allocation
Terminal
DUP
GND
+24 IN
+24 OUT
I 1
I 2
I 3
I 4
O 1
O 2
O 3
O 4
Input/Output
Dupline®signal
Dupline®+ supply GND
Supply IN
DC for output loads
Input 1
Input 2
Input 3
Input 4
Output 1
Output 2
Output 3
Output 4
Wiring Diagrams
Accessories
Aluminium bracket for
DIN mounting 8047 - bracket
DIN-rail FMD 411
G 2140 55.0 700
The I/O-units use three wires
for the communication with
all the other I/O-units of an
installation, for the supply of
the I/O-units and for the
loads connected to the out-
puts of the units. This
implies, that the “common”
of the communication signal
is identical to the “minus” of
the supply. The DC-supply
voltage must connect to the
system through a G 2196
0000 700, which also per-
forms the channel generator
function and the RS485 com-
munication link to elevator
controller (please refer to the
data sheet for G 2196 0000
700 for details).
Each I/O-unit has 4 inputs
(NPN/contact) and 4 outputs
(NPN or PNP). Every input
an output is given its indi-
vidual address with the cod-
ing unit GAP 1605 (please
refer to the respective data
sheet for details). The
ON/OFF-signal that is
applied to the input of an
I/O-unit is associated to the
address given to that input.
Any output of an I/O-unit
that is given the identical
address will now follow that
input signal and switch its
output signal ON or OFF.
This means that a signal
which is input at one loca-
tion (for example as an out-
put from the lift controller)
may be output wherever
required and as many times
as required.
An input pulse stretcher is
used on every input to
assure that the changes of
input signals (even extreme-
ly short ones) are communi-
cated by the system.
The output status of all out-
puts of an I/O-unit may be
pre-defined for cases like
loss of power and loss of
communication. Please refer
to the paragraph “Output
status setting” of the data
sheet for the GAP 1605 to
change the default setting
(all outputs OFF).