3 Phase overcurrent
Over- and/or undervoltage
Over- and underfrequency
Reverse or forward power
For line-line or line-neutral
Adjustable trip level, time delay and hysteresis
Phase monitor (G3300)
Preset push button defines reference
Instant pick-up and delayed trip
Two separate contacts for pick-up and trip
LED based indication of relay status
Optional external reset with latch function
A single variant covers all voltages
Optional PC based configuration (RS232)
Flame retardant DIN rail enclosure
Data Sheet
SELCO G-Line
Generator Protection Relays
2
G2000
G2200
G2000
G2200
G3100
G3000
SELCO G-Line for
Land-based Applications
SELCO’s new G-Line Generator Protection Relays are mainly intended for use in
land-based applications. The G-Line range of relays provides an efficient solution in
applications where cost of materials is the main issue.
Despite a low cost, the G-Line relays still provide a number of ground-breaking
features not presently offered by the competing relays.
Installation
The SELCO G-Line Generator Protection
Relays are easy to install. The relays are
housed in a compact enclosure for DIN
rail mounting or fixation by two ordi-
nary screws. The design matches that of
the well proven SELCO T-Line product
range.
Configuration
Configuration and setup is easier than
ever. Despite the use of modern micro-
processor technology, adjustment dials
are maintained in order to make confi-
guration and test as easy as possible.
The reference current, voltage or frequen-
cy is easily set by briefly activating a
small push button (PRESET).
Indications and Relays
The state of the contact sets inside the re-
lay is clearly indicated by LEDs located
on the front plate. There is one LED for
power, one LED for pick-up (activates
when the set-point is exceeded) and one
LED to indicate the state of the trip relay.
The pick-up relay has one contact set
and the trip relay has two contact sets.
One relay covers all voltages
One variant covers all voltages (nominal
63 to 690V AC). An external supply of
+24V DC is required.
Advanced Configuration
The SELCO G-Line Generator Protection
Relays provide the optional feature of
advanced PC based configuration (using
a standard ANSI terminal). An optional
programming kit (G0100) will allow the
user to reconfigure the function of the
relay, as well as the minimum/maxi-
mum scales of the dials.
This makes the G-Line relays even
more flexible and versatile to customers
requirering adapted functionality. The
front plate of the relay can be custom-
ized as well.
Design
G-Line relays are single function units.
The single variant principle is an advan-
tage, as one version covers all voltages.
Figure 1: The connection of the G-Line Relays.
Generator 1 Generator 2
BUSBAR
However, it is possible to choose (using
the optional programming kit G0100)
whether the relay is for e.g. under-
current or overcurrent.
Features include a level preset function
(for reference definition), all optional
functions onboard (e.g. latching), PC
based configuration of scales, set points
etc.
3
G2200 Current Relay
Overcurrent
(Undercurrent)
8-36V DC/0.75W at 24V DC
5A CT, max. 10A
35 to 75Hz
50 to 140% (max. 10 to 150%)
1 to10% (max. 1 to 50%)
3 to 30sec.
(max. 1 to 360sec.)
380V AC, 5A, 1250VA
150V DC, 5A, 120W
ND (NE)
Non-latching
ND (NE)
Non-latching (latching)
Automatic
(manually by terminal 11)
± 5%
± 1%
RJ11-modular
-20° to 70° C
EN50263
50 hours before final test
Polycarbonate. Flame retardant
0.3kg
73 x 75 x 114mm (HxWxD)
35 DIN rail or two 4mm
(3/16”) screws
Function
Supply
Input voltage
Input current
Frequency
Trip level
Hysteresis
Delay
Relay rating
Pick-up relay
- Normal state
- Latching
Trip relay
- Normal state
- Latching
Overfrequency relay
- Normal state
- Latching
Underfrequency relay
- Normal state
- Latching
Reset
Accuracy
Repeatability
Serial link
Operating temperature
EMC
Burn-in
Enclosure material
Weight
Dimensions
Installation
G3000 Frequency Relay
Over- and Underfrequency
8-36V DC/0.75W at 24V DC
63 to 690V AC ± 30%
35 to 75Hz
OF: 85 to 115% (max. 75 to 125%)
UF: 85 to 115% (max. 75 to 125%)
1 to 10sec.
(max. 1 to 360sec.)
380V AC, 5A, 1250VA
150V DC, 5A, 120W
NE (ND)
Non-latching (latching)
NE (ND)
Non-latching (latching)
Automatic
(manually by terminal 11)
± 5%
± 1%
RJ11-modular
-20° to 70° C
EN50263
50 hours before final test
Polycarbonate. Flame retardant
0.3kg
73 x 75 x 114mm (HxWxD)
35 DIN rail or two 4mm
(3/16”) screws
G2000 Power Relay
Reverse Power
(Forward Power)
8-36V DC/0.75W at 24V DC
63 to 690V AC ± 30%
5A CT, max. 10A
35 to 75Hz
RP: 2 to 20% (max. 2 to 50%)
FP: 50 to 140% (max. 50 to 150%)
1 to 10% (max. 1 to 50%)
2 to 20sec.
(max. 1 to 360sec.)
380V AC, 5A, 1250VA
150V DC, 5A, 120W
ND (NE)
Non-latching
ND (NE).
Non-latching (latching)
Automatic
(manually by terminal 11)
± 5%
± 1%
RJ11-modular
-20° to 70° C
EN50263
50 hours before final test
Polycarbonate. Flame retardant
0.3kg
73 x 75 x 114mm (HxWxD)
35 DIN rail or two 4mm
(3/16”) screws
Specifications (Specifications in parentheses require setup by serial link)
The specifications are subject to change without notice.
4
G3600 Voltage Relay
Over- and Undervoltage
8-36V DC/0.75W at 24V DC
63 to 690V AC ± 30%
35 to 75Hz
80 to 120% (max. 70 to 130%)
80 to 120% (max. 70 to 130%)
1 to 10sec.
(max. 1 to 360sec.)
380V AC, 5A, 1250VA
150V DC, 5A, 120W
ND (NE)
Non-latching
NE (ND)
Non-latching (latching)
Automatic
(manually by term. 11)
± 5%
± 1%
RJ11-modular
-20° to 70° C
EN50263
50 hours before final test
Polycarbonate. Flame retardant
0.3kg
73 x 75 x 114mm (HxWxD)
35 DIN rail or two 4mm
(3/16”) screws
Function
Supply
Input voltage
Frequency
Trip level
- 1st trip level
- 2nd trip level
Hysteresis
Delay
Relay rating
Phase monitor
Pick-up (phase) relay
- Normal state
- Latching
Trip relay
- Normal state
- Latching
Overvoltage relay
- Normal state
- Latching
Undervoltage relay
- Normal state
- Latching
Reset
Accuracy
Repeatability
Serial link
Operating temperature
EMC
Burn-in
Enclosure material
Weight
Dimensions
Installation
G3300 Voltage Relay
3 Phase Overvoltage
(Undervoltage)
8-36V DC/0.75W at 24V DC
63 to 690V AC ± 30%
35 to 75Hz
100 to 120% (max. 1 to 130%)
1 to 10% (max. 1 to 50%)
1 to 10sec.
(max. 1 to 360sec.)
380V AC, 5A, 1250VA
150V DC, 5A, 120W
Phase failure, phase order & symmetry
ND (NE)
Non-latching
ND (NE)
Non-latching
Automatic
(manually by term. 11)
± 5%
± 1%
RJ11-modular
-20° to 70° C
EN50263
50 hours before final test
Polycarbonate. Flame retardant
0.5kg
73 x 75 x 114mm (HxWxD)
35 DIN rail or two 4mm
(3/16”) screws
Specifications (Specifications in parentheses require setup by serial link)
The specifications are subject to change without notice.
G3100 Voltage Relay
Overvoltage
(Undervoltage)
8-36V DC/0.75W at 24V DC
63 to 690V AC ± 30%
35 to 75Hz
100 to 120% (max. 70 to 130%)
1 to10% (max. 1 to 50%)
1 to 10sec.
(max. 1 to 360sec.)
380V AC, 5A, 1250VA
150V DC, 5A, 120W
ND (NE).
Non-latching
ND (NE)
Non-latching (latching)
Automatic
(manually by term. 11)
± 5%
± 1%
RJ11-modular
-20° to 70° C
EN50263
50 hours before final test
Polycarbonate. Flame retardant
0.3kg
73 x 75 x 114mm (HxWxD)
35 DIN rail or two 4mm
(3/16”) screws
5
Selco G-Line
Connections
SELCO’s product philosophy is to offer easy-to-install, serviceable and reliable modular system components for mounting on
switchboards and control consoles.
Systems based on such components provide high flexibility, easy troubleshooting and require very little maintenance and serv-
ice, which give our customers a low Total Cost of Ownership (TCO).
Dimensions.
G2200 Current Relay
G3300 Voltage Relay
G2000 Power Relay
G3100 Voltage Relay
G3000 Frequency Relay
G3600 Voltage Relay
75 114
60
7,5
50
73
10
Fixing holes
2 x ø 4,5 mm. Dimensions in mm.
Argentina
Australia
Austria
Belgium
Brazil
Bulgaria
China
Croatia
Czech Republic
Egypt
Finland
Main Office:
SELCO A/S
Betonvej 10
DK- 4000 Roskilde
Denmark
Phone: + 45 - 70 26 11 22
Fax: + 45 - 70 26 25 22
e-mail: selco.dk@selco.com
www.selco.com
SELCO Worldwide
Malaysia
Morocco
Netherlands
Norway
Pakistan
Philippines
Poland
Portugal
Romania
Russia
Singapore
South Africa
France
Germany
Greece
Hong Kong
Hungary
Iceland
India
Indonesia
Iran
Italy
Japan
Korea
Spain
Sweden
Taiwan
Thailand
Turkey
Ukraine
United Kingdom
U.S.A.
SELCO Denmark
SELCO subsidiary
SELCO representation
Area of supply
Q 1 0 0 3 -64 E
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Littelfuse:
G3100.0010 G3000.0010 G3300.0020 G2200.0010 G3600.0010