IEC Inlet Filters FN 9260 General Purpose Power Entry Module with Fuses n n n n n Rated currents up to 10A For one or two fuses Optional safety version (A type) Optional medical versions (B type) according to IEC/EN 60601-1 Snap-in versions (S type) Technical specifications Maximum continuous operating voltage: Operating frequency: Rated currents: High potential test voltage: Protection category: Temperature range (operation and storage): Design corresponding to: Flammability corresponding to: MTBF @ 40C/230V (Mil-HB-217F): Fuse holder: Approvals Typical electrical schematic 250VAC, 50/60Hz dc to 400Hz 1 to 10A @ 40C max. P -> PE 2000VAC for 2 sec (standard types) P -> PE 2500VAC for 2 sec (B types) P -> N 760VAC for 2 sec (standard types) P -> N 1700VDC for 2 sec (B types) IP40 according to IEC 60529 -25C to +85C (25/85/21) UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939 UL 94V-2 or better 2,200,000 hours 1 or 2 fuses (O5 x 20mm) FN 9260 (B types without Y-capacitors) Cx R 2xL 2xCy N N` PE PE P` P Line Load FN 261 Cx R 2xL 2xCy N N` PE PE P` P Line Features and benefits The FN 9260 power entry module combines n Exceptional conducted attenuation Load Typical applications n Portable electrical and electronic an IEC inlet, mains filter with excellent filter performance, based on chokes with high attenuation and fuses in a small form factor. saturation resistance and excellent thermal n Medical equipment behavior. n Small to medium-sized machines and Choosing FN 9260 product line brings you rapid availability of a standard filter associ- n B types comply with the requirements of ated with the necessary safety acceptances. IEC/EN 60601-1 for creepage and clea- Standard IEC connector filters are a practical rance, leakage current and high potential testing. solution helping you to pass EMI system approval in a short time. A wide selection n mounting possibilities and filters for medical applications are designed to offer you the desired solution. Versions up to 10A are available with fuse holder for one or two fuses. on amperage ratings, output connections, n equipment Custom-specific versions are available on request. household equipment n Single-phase power supplies, switch-mode power supplies n Test and measurement equipment > Components > FN 9260 Filter selection table Filter * Rated current @ 40C (25C) Leakage current* @ 230VAC/50Hz Inductance L Capacitance Cx Cy Resistance R Input/Output connections Fuses Weight [A] [A] [mH] [F] [nF] [k] [Qty] [kg] FN FN FN FN FN 9260x-1-06-y 9260x-2-06-y 9260x-4-06-y 9260x-6-06-y 9260x-10-06-y 1 (1.2) 2 (2.3) 4 (4.6) 6 (6.9) 10 (11.5) 373 373 373 373 373 5.3 2.7 1.0 0.3 0.2 0.1 0.1 0.1 0.1 0.1 2.2 2.2 2.2 2.2 2.2 1000 1000 1000 1000 1000 -06 -06 -06 -06 -06 2 2 2 2 2 55 55 55 55 55 FN FN FN FN FN 9260xA1-1-06-y 9260xA-2-06-y 9260xA-4-06-y 9260xA-6-06-y 9260xA-10-06-y 1 (1.2) 2 (2.3) 4 (4.6) 6 (6.9) 10 (11.5) 37 74 74 74 74 5.3 2.7 1.0 0.3 0.2 0.1 0.1 0.1 0.1 0.1 0.22 0.47 0.47 0.47 0.47 1000 1000 1000 1000 1000 -06 -06 -06 -06 -06 2 2 2 2 2 55 55 55 55 55 FN FN FN FN FN 9260xB-1-06-y 9260xB-2-06-y 9260xB-4-06-y 9260xB-6-06-y 9260xB-10-06-y 1 (1.2) 2 (2.3) 4 (4.6) 6 (6.9) 10 (11.5) 2 2 2 2 2 5.3 2.7 1.0 0.3 0.2 0.1 0.1 0.1 0.1 0.1 1000 1000 1000 1000 1000 -06 -06 -06 -06 -06 2 2 2 2 2 55 55 55 55 55 FN FN FN FN FN 261x-1-06-y 261x-2-06-y 261x-4-06-y 261x-6-06-y 261x-10-06-y 1 (1.2) 2 (2.3) 4 (4.6) 6 (6.9) 10 (11.5) 373 373 373 373 373 5.3 2.7 1.0 0.3 0.2 0.1 0.1 0.1 0.1 0.1 1000 1000 1000 1000 1000 -06 -06 -06 -06 -06 1 1 1 1 1 55 55 55 55 55 2.2 2.2 2.2 2.2 2.2 Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level. Product selector FN 9260xx-yy-yy-y Snap-in range for S version only 10: Snap-in range 0.6 to 1.5mm 20: Snap-in range 1.6 to 2.5mm 30: Snap-in range 2.6 to 3.5mm 06: Faston 6.3 x 0.8mm (spade/soldering) 1 to 10: Rated current Blank: Standard version A: Safety version B: Medical version (wihtout Y-capacitor) Blank: Standard housing with mounting flanges S: Snap-in version, snapper on vertical side For example: FN 9260-1-06-10, FN 9260SB-10-06-20, FN 261S-6-06-30 Typical filter attenuation Per CISPR 17; A = 50/50 sym; B = 50/50 asym; C = 0.1/100 sym; D = 100/0.1 sym FN 9260: 1 to 4A types FN 9260: 6 and 10A types FN 261: 1 to 4A types FN 261: 6 and 10A types > Components > FN 9260 Mechanical data FN 9260 / FN 261 FN 9260S / FN 261S B IEC plug type C14 6.3 x 0.8 B IEC plug type C14 6.3 x 0.8 S A C F H A J E D E F G I J D I G Panel cut out Installation T N R M C P Dimensions FN 9260 FN 261 FN 9260S FN 261S A 46 34 B 35 35 C 36 D 41 41 E 27.8 27.8 F 5.5 5.5 G 32 32 H O3.2 I 13.8 13.8 J 12.5 12.5 M R 3.5 R 3.5 N 33 33 P 29 29.5 R M3 S 90 T* 0.6 - 1.5 T* 1.6 - 2.5 T* 2.6 - 3.5 * Tolerances 0.3 0.3 0.3 0.3 +0.3/-0 0.3 +0.3/-0 0.1 0.3 +0.3/-0 0.3 For selecting the panel thickness, please refer to the filter selector table. All dimensions in mm; 1 inch = 25.4mm Tolerances according: ISO 2768-m / EN 22768-m Your local partner: To find your local partner within Schaffner's global network, please go to www.schaffner.com May 2011 Headquarters and global innovation and development center Schaffner Group Nordstrasse 11 4542 Luterbach Switzerland T +41 32 681 66 26 F +41 32 681 66 30 info@schaffner.ch www.schaffner.com Sales and application centers China Schaffner EMC Ltd. Shanghai Building 11, Lane 1365 East Kangqiao Road Shanghai 201319 T +86 21 6813 9855 F +86 21 6813 9811 cschina@schaffner.com www.schaffner.com Germany Schaffner Deutschland GmbH Schoemperlenstrasse 12B 76185 Karlsruhe T +49 721 56910 F +49 721 569110 germanysales@schaffner.com Finland Schaffner Oy Tynninkuja 7 08700 Lohja T +358 19 35 72 71 F +358 19 32 66 10 finlandsales@schaffner.com France Schaffner EMC S.A.S. 112, Quai de Bezons 95103 Argenteuil T +33 1 34 34 30 60 F +33 1 39 47 02 28 francesales@schaffner.com Italy Schaffner EMC S.r.l. Via Galileo Galilei, 47 20092 Cinisello Balsamo (MI) T +39 02 66 04 30 45/47 F +39 02 61 23 943 italysales@schaffner.com Japan Schaffner EMC K.K. Mitsui-Seimei Sangenjaya Bldg. 7F 1-32-12, Kamiuma, Setagaya-ku Tokyo 154-0011 T +81 3 5712 3650 F +81 3 5712 3651 japansales@schaffner.com www.schaffner.jp Sweden Schaffner EMC AB Turebergstorg 1, 6 19147 Sollentuna T +46 8 5792 1121 / 22 F +46 8 92 96 90 swedensales@schaffner.com Switzerland Schaffner EMV AG Nordstrasse 11 4542 Luterbach T +41 32 681 66 26 F +41 32 681 66 41 sales@schaffner.ch To find your local partner within Schaffner`s global network, please go to Singapore Schaffner EMC Pte Ltd. Blk 3015A Ubi Road 1 05-09 Kampong Ubi Industrial Estate T +65 6377 3283 F +65 6377 3281 singaporesales@schaffner.com (c) 2011 Schaffner EMC. Specifications subject to change without notice. All trademarks recognized. Spain Schaffner EMC Espana Calle Calendula 93, Miniparc III, Edificio E El Soto de la Moraleja, Alcobendas 28109 Madrid T +34 618 176 133 spainsales@schaffner.com Taiwan Schaffner EMV Ltd. 6th Floor, No 413 Rui Guang Road Neihu District Taipei City 114 T +886 2 87525050 F+886 2 87518086 taiwansales@schaffner.com Thailand Schaffner EMC Co. Ltd. Northern Region Industrial Estate 67 Moo 4 Tambon Ban Klang Amphur Muang P.O. Box 14 Lamphun 51000 T +66 53 58 11 04 F +66 53 58 10 19 thailandsales@schaffner.com UK Schaffner Ltd. 5 Ashville Way Molly Millars Lane Wokingham Berkshire RG41 2PL T +44 118 9770070 F +44 118 9792969 uksales@schaffner.com www.schaffner.uk.com USA Schaffner EMC Inc. 52 Mayfield Avenue Edison, New Jersey 08837 T +1 732 225 9533 F +1 732 225 4789 usasales@schaffner.com www.schaffner.com/us www.schaffner.com May 2011 Schaffner is an ISO-registered company. Its products are designed and manufactured under the strict quality and environmental requirements of the ISO 9001 and ISO 14001 standards. This document has been carefully checked. However, Schaffner does not assume any liability for errors or inaccuracies.