IAL/CEL/LEL Series Magnetic Circuit Protectors Introduction * 147 Poles * 148 Handles * 150 Configurations * 154 Operating Characteristics * 157 Delay Curves * 159 Specifications * 163 Decision Tables * 165 IAL/CEL/LEL Series Hydraulic Magnetic Circuit Protectors INTRODUCTION IAL/IUL/IEL/LEL magnetic circuit protectors provide low-cost power switching, reliable circuit protection and accurate circuit control for equipment in the international marketplace. the LEL models are UL listed under the conditions of UL 489. Both are CSA certified and CCC Approved. The IEL is CSA certified as a supplementary protector per CSA C22.2-No. 235. IAL models are for those applications where the unit's inherent attributes are desired, but compliance with the various standards is not required. The CEL model has achieved two new enhancements, including a single pole, 125 amp rating with TUV approval, and a parallel 4-pole version with 400 amp rating. IUL models have been tested and approved in accordance with UL 1077 requirements for UL recognition. AirpaxTM IAL/CEL/LEL circuit protectors are available in a wide variety of configurations, including series, series with auxiliary switch, shunt and relay with choice of delays and ratings in DC and/or 50/60Hz or 400Hz versions. Single or multi-pole versions are available with a variety of pole arrangements to meet your specifications. Please see the appropriate product specification table for ratings and limitations. IEL/LEL models are VDE approved to VDE 0660, part 101. They meet IEC spacing requirements, mandatory for equipment which must comply with IEC specifications 601 and 950, and VDE specifications 0804 and 0805. In addition, the IEL models are UL recognized to UL 1077 as supplementary protectors and 147 IAL Series - Introduction http://airpax.sensata.com IAL Series SINGLE POLE, STANDARD STUD TERMINAL (SEE TABLE) .281 [7.14] STUD TERMINAL TYPES .140 [3.56] (SEE TABLE) Screw Stud Thread Dimension "A" Dimension "B" M6 .510 .045 [12.95 1.14] .652 .035 [16.56 0.89] 1/4 -20 .545 .045 [13.84 1.14] .687 .035 [17.45 0.89] M5 .510 .045 [12.95 1.14] .652 .035 [16.56 0.89] 10-32 .545 .045 [13.84 1.14] .687 .035 [17.45 0.89] ON 1.940 [49.28] .142 [3.61] OFF 1.859 [47.22] .690 [17.53] Single Pole Mounting Detail .755 [19.18] 2X 6-32 THREAD .140 [3.56] DEEP M3 ISO THD. OPTIONAL .402 [10.21] 1.438 [36.53] .220 [5.59] 1.448 [36.78] 2.060 [52.32] Panel Mounting Detail Tolerance .005 [.13] unless noted. 2.060 [52.32] .432 [10.98] 2.490 [63.24] 2X y .156 [3.96] .750 [19.05] Screw Terminal .281 [7.13] .281 [7.13] 1.940 [49.28] .142 [3.61] Bullet Terminal Clip Terminal y .250 MAX. [6.35] .967 [24.57] 1.940 [49.28] .375 [9.53] .392 [9.96] .592 [15.04] Notes: Tolerance .015 [.39] unless noted. Dimensions in brackets [ ] are millimeters. A Terminal protrusion dimensions are referenced from back of mounting panel. B Each screw terminal is supplied with a 10-32x.312 [7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. C Stud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A) (<=50A for LEL),1/4-20 or M6 hex nut (>70A)(>50A for LEL). Bullet terminal receptacle should be .312 .001 diameter hole not less than .250 depth. Contact Sensata for other bullet sizes. Note: Each outer terminal is supplied with a flatwasher, tooth lockwasher and a hex nut. IAL Series - Poles 148 MULTI-POLE CIRCUIT PROTECTORS Multi-pole units are combined in an assembly with the trip mechanisms internally coupled. A fault in any protected circuit opens all poles simultaneously. Applications include use in polyphase circuits, single-phase three-wire systems, or in two or more related but electrically isolated circuits. A mix of delays, ratings and configurations are offered. The auxiliary switch is offered with either gold or silver contacts and is available when a series construction pole is specified. Two Pole Two Pole Units An assembly consisting of two single pole units, having their trip mechanisms internally coupled, is available with either a single toggle handle or with a handle per pole. Please see decision one of the part number decision tables. Individual poles may vary in ratings, delays and internal configurations. If the poles are of series construction, an auxiliary switch may be included in either or both poles, allowing you to mix SELV and hazardous voltages. (SEE TABLE) .281 [7.14] IEL11 IELH11 .140 [3.56] (SEE TABLE) .402 [10.21] .220 [5.59] 4X 6-32 THREAD .140 [3.56] DEEP M3 ISO THD. OPTIONAL ON 1.438 [36.53] 1.940 [49.28] 2.060 [52.32] .142 [3.61] OFF .690 [17.53] 1.859 [47.22] 1.515 [38.48] MAX. 1.515 [38.48] MAX. 2.490 [63.24] Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. Two Pole* M6 .510 .652 1/4 - 20 .545 .687 M5 .510 .652 10 - 32 .545 .687 Screw stud thread Dim. iAi ( .045) Dim. iBi ( .035) Note: Each outer terminal is supplied with a flatwasher, tooth lockwasher and a hex nut. 4X y .156 [3.96] Two Pole* 1.530 [38.86] 1.448 [36.78] .432 [10.97] 2.060 [52.32] .750 [19.05] .750 [19.05] Panel Mounting Detail Tolerance .005 [.13] unless noted. Note: A Terminal protrusion dimensions are referenced from back of mounting panel. B Each screw terminal is supplied with a 10-32x.312 [7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. C Stud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A), 1/4 -20 or M6 hex nut (>70A). 149 IAL Series - Poles http://airpax.sensata.com IAL Series Three Pole and Four Pole Units BX - FLAT ROCKER HANDLE The three pole structure consists of three single pole units assembled with an internal mechanical interlock which actuates all units simultaneously. The units are available with either a single toggle handle or with a handle per pole. Units with four pole construction operate with a minimum of two center toggle handles or with a handle per pole. Please see decision one of the part number decision tables. Mixing of delays, ratings and configurations is available in each individual pole. The auxiliary switch is offered in any series trip pole. The innovative new design of our IAL/CEL/LEL BX Style circuit protectors features a flat rocker that will satisfy your aesthetic needs while guarding against accidental actuation, providing the highest degree of circuit protection and quality. Only Airpax offers this new standard in user interface. Available on a variety of versions with a full range of agency approvals, the IEL BX style circuit protectors meet or exceed all current performance specifications, including interrupting capacities up to 50,000 amperes. Breaker poles are numbered consecutively when viewed from the terminal side, with the ON position up, starting with pole #1 on the left side and proceeding to the right. Three Pole IEL111 2.173 MAX. [55.19] Mounting Detail* .387 REF. [9.84] .125 [3.17] 1.859 [47.22] .768 [19.49] 1.395 [35.43] 2.490 MAX. [63.25] 2.265 [57.53] MAX. Three Pole IELH111 .750 [19.05] .750 [19.05] 1.239 [31.47] Mounting Detail* .314 [7.98] 6-32 THD. MOUNTING M3 ISO THD. OPTIONAL .750 MAX. [19.05] 2.265 [57.53] MAX. Four Pole IEL1111 .750 [19.05] 2.280 [57.91] O .750 [19.05] 1.660 [42.16] OPTIONAL GUARD (SEE DETAIL iCi) Four Pole IELH1111 .750 [19.05] 1.660 [42.16] 3.030 [76.96] PUSH TO RESET HANDLE POSITION "OFF" GUARD WITH NO ACTUATE OFF FEATURE (SIXTH DECISION, X) HANDLE POSITION "ON" WITH GUARD (SIXTH DECISION, G) ON I PUSH TO RESET HANDLE POSITION "ON" GUARD WITH NO ACTUATE OFF FEATURE (SIXTH DECISION, X) 1.260 [32.00] Mounting Detail* 2X y.156 [3.96] HANDLE POSITION "OFF" WITH GUARD (SIXTH DECISION, G) ON I SINGLE POLE .750 [19.05] .750 [19.05] OFF ACTUATION ACCESS (SEE NOTE) Mounting Detail* .750 [19.05] O OFF 1.530 [38.86] 3.015 [76.58] MAX. ON I ON I .200 [5.08] Panel Mounting Detail Mounting Detail Tolerance: .005 [.13] unless noted ON I O OFF HANDLE POSITION "OFF" WITHOUT GUARD ON I O OFF HANDLE POSITION "ON" WITHOUT GUARD DETAIL "A" NOTE: ACCESS IS LIMITED TO A DEVICE SMALLER THAN THE UNDERWRITERS LABORATORY "ARTICULATED PROBE" DEFINED IN UL-489 FIG. 11.1.7.2.1. 3.015 [76.58] MAX. Panel Mounting Detail Tolerance .005 [.13] unless noted. .750 [19.05] .750 [19.05] .750 [19.05] Note: Tolerance .015 [.39] unless noted. Dimensions in brackets [ ] are millimeters. *See Single Pole Mounting Detail for Hole Sizes and Locations. IAL Series - Handles 150 LELHP/CELHP CIRCUIT PROTECTORS The AirpaxTM LELHP/CELHP high current magnetic circuit protector compliments our entire series of LEL circuit protectors. Its unique, parallel current sensing design provides precise current overload protection and reliability in the compact size of a two pole LEL. The unit is ideal for high power DC applications such as drive motor systems and telecommunication power systems. LEL is available in series and series with auxiliary switch configurations with a choice of delays for DC ratings of 125, 150, 175 and 200 amperes. The CEL has been enhanced to include these same ratings plus a 4-pole, parallel 400 amp rating for UL489A. The LELHP is UL listed under the conditions of UL489 and CSA certified. The CELHP is UL listed under the conditions of UL489A. Mid-trip handle indication, voltage trip and remote operator options complete the LELHP/CELHPcircuit breaker series. Please see the individual product tables for approved ratings. Two Pole 1.515 MAX [38.48] .687 [17.45] .281 [7.14] .545 [13.84] 1.047 [26.59] 1.940 [49.28] .640 [16.26] .740 [18.80] (Note E) .140 [3.56] 2X 6-32 THREAD .140 [3.56] DEEP M3 ISO THD OPTIONAL .220 .402 [10.21] ON [5.59] 2.490 [63.25] 1.438 [36.53] 1.282 [32.56] 2.060 [52.32] OFF 1/4-20 STUD (M6 x 1.0 STUD OPTION) Series Parallel 1.859 [47.22] .690 [17.53] .750 [19.05] Three Pole (Note D) .740 [18.80] (Note E) Series Parallel with optional 1REC4 Auxiliary switch .740 [18.80] (Note E) .740 [18.80] (Note E) .220 [5.59] .740 [18.80] (Note E) C .402 [10.21] .402 [10.21] 1.438 [36.53] 1.438 [36.53] .220 [5.59] NO NC BREAKER IN OFF POSITION -REC4 2.490 [63.25] OFF OFF OFF OFF 2.060 [52.32] 2.060 [52.32] 2.490 [63.25] 175/200 Parallel Pole 2.265MAX. 2.265MAX. [57.53] [57.53] .110 [2.79] 2.438 MAX [61.93] (SEE NOTE 1) Four Pole (CEL _ _ P and CML _ _ P only) DIM. "H" (SEE TABLE) .260 [6.60] DIM. "H" (SEE TABLE) Notes: Tolerance .015 [.39] unless noted. Dimensions in brackets [ ] are millimeters. A Terminal protrusion dimensions are referenced from back of mounting panel. B Each screw terminal is supplied with a 10-32x.312[7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. CStud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A), 1/4 -20 or M6 hex nut (>70A). DUnits are supplied without bus bars must have a minimum copper strap (1 31/32 x 1/2 x 1/16 ) of appropriate length to accommodate connections tying each set of terminals together. E Other spacing available upon request. Contact factory for assistance. 151 OFF OFF IAL Series - Handles DIM. "H" (SEE TABLE) 6X 6-32 THREAD 6X 6-32 THREAD .140 [3.56] DEEP .140 [3.56] DEEP M3 ISO THDM3 OPTIONAL ISO THD OPTIONAL 8X 6-32 THREAD .140 [3.56] DEEP M3 ISO THD OPTIONAL .402 10.21 .220 5.59 2.490 63.25 1.438 36.53 O FF OFF O FF O FF 2.060 52.32 3.005 MAX [76.33] http://airpax.sensata.com IAL Series IALN/IULN PANEL SEAL CIRCUIT PROTECTORS .130 [3.30] The lALN/IULN family is a sealed toggle version of the IAL/IUL family. The silicone rubber seal around the handle assures panel seal integrity and makes this style a natural for harsh environments. 6-32 MTG. SCREW FOR HIGH SHOCK MTG. LOCKWASHER ON This sealed toggle family is available in one to three pole models with ratings of .050 to 100 amperes. OFF 1/2-32 HEX NUT .142 [3.61] Single Pole KEYWAY .060 [1.52]-.065 [1.65] WIDE .030 [.76]-.035 [.89] DEEP .750 [19.05] 2.040 [51.82] Two Pole .625 [15.88] .750 [19.05] Three Pole 2.265 [57.53] MAX. 1.515 [38.48] MAX. 1.375 [34.92] 2.490 [63.25] .656 [16.66] (OPTIONAL, HANDLE (Optional MAY BEhandle IN POLEmay 2 be in INSTEAD OF POLE 1) pole 2 instead of pole 1.) Panel Mounting Details: Tolerance .005 [.13] Unless noted. Single Pole .656 [16.66] Two Pole* y.156 [3.96] .750 [19.05] MAX. Three Pole* .750 [19.05] MAX. .750 [19.05] MAX. y.515 [13.08] Optional handle *See Single Pole Mounting Detail for Hole Sizes and Locations. Notes: A Terminal protrusion dimensions are referenced from back of mounting panel. B Each screw terminal is supplied with a 10-32x.312[7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. CStud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A), 1/4 -20 or M6 hex nut (>70A). IAL Series - Handles 152 IALX/IULX/IELX ROCKER HANDLE The rocker style is available in one to four poles. Choose either vertical or horizontal mounting with ON-OFF, international markings or a combination of both. 1.859 [47.22] 2.490 [63.25] Five front panel enhancing colors including black, white, red, grey and orange are available. 1.375 [34.92] 1.940 [49.28] [3.61] 2.249 [57.12] .419 [10.65] Single Pole 2X 6-32 THD. (TYP.) M3 ISO THD. OPTIONAL Two Pole Three Pole Panel Mounting Detail* Single,Two & Three Pole Four Pole Four Pole** .750 [19.05] 1.510 [38.35] 2.361 1.972 [50.09] ON 1.660 [42.16] ON ON ON ON OFF OFF OFF OFF 1.260 [32.00] .750 [19.05] 1.499 [38.07] MAX. .735 [18.67] (HANDLE WIDTH) 1.260 [32.00] 1.660 [42.17] OFF 3.015 [76.58] MAX. 2.249 [57.12] MAX. 2X y .156 [3.96] .200 [5.08] .750 [19.05] (Optional handle may be in Pole 2 instead of Pole 1.) Note: A Terminal protrusion dimensions are referenced from back of mounting panel. BEach screw terminal is supplied with a 10-32x.312[7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. CStud terminals are supplied with a flatwasher, external tooth lock washer and a 10-32 or M5 hex nut (<=70A), -20 or M6 hex nut (>70A). 2.173 MAX. [55.19] 1.859 [47.22] *Mounting detail tolerance .005 [.13] Unless noted. **See single mounting detail for hole sizes and locations. .420 REF [10.67] .750 MAX. [19.05] .201 [5.11] IALZX/IULZX/IELZX ROCKER HANDLE .772 [19.62] The IALZX/IULZX/IELZX style adds our rocker handle options of 2.490 MAX. contrasting dual color rocker actuators, affording a clear visual [63.25] indication of the handle position and integrated handle guards, to 1.395 help [35.43] prevent accidental turn-on and turn-off of the unit. Available with a black rocker and white, red or green indicator color for 1.660 [42.16] either ON or OFF indication. ON 1.239 [31.47] .314 [7.98] 2.173 MAX. [55.19] .506 [12.85] 2X 6-32 THD. M3 ISO THD. OPTIONAL Panel Mounting Detail .420 REF [10.67] 1.859 [47.22] OFF OPTIONAL HANDLE GUARDS .750 MAX. [19.05] .201 [5.11] .772 [19.62] .750 [19.05] 1.395 [35.43] 2.490 MAX. [63.25] ON 1.239 [31.47] .314 [7.98] .506 [12.85] OPTIONAL HANDLE GUARDS 1.660 [42.16] OFF 2X 6-32 THD. M3 ISO THD. OPTIONAL 153 1.660 [42.17] 2X y .156 [3.96] 1.260 [32.00] .200 [5.08] Panel Mounting Detail Tolerance .005 [.13] unless noted. Note: Tolerance .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. IAL Series - Handles Panel Mounting Details Mounting Detail Tolerance: .005 [.13] Unless Noted. .750 [19.05] http://airpax.sensata.com IAL Series Series and Switch Only CONFIGURATIONS .281 [7.13] Series Trip The most popular configuration for magnetic protectors is the series trip where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional overcurrent protection, it's simultaneously used as an on-off switch. Dimension B (See Table) SERIES 1.940 [49.28] SWITCH ONLY Dimension A (See Table) Series with Auxiliary Switch Shunt Trip The shunt trip is designed for controlling two separate loads with one assembly. The control is established by providing overload protection for the critical load. When the current through this load becomes excessive and reaches the trip point, the protector will open and remove power from both loads simultaneously. The total current rating of both loads must not exceed the maximum contact rating. .648 [16.46] C NO NC 1.055 [26.80] 1.290 [32.77] BREAKER IN OFF POSITION STUD TERMINAL TYPES Dual Coil By combining two electrically independent coils on a common magnetic circuit, it is possible to provide contact opening when either an over-current or trip voltage is applied to the respective coils. One coil will be a current trip coil with standard specifications. The second, or dual coil, can be used to provide a control function permitting contact opening from a remote interlock or other transducer functions. Standard coils are 6, 12, 24, 48, 120 and 240 volts. Tripping is instantaneous and must be removed (usually self-interrupting) after trip. Auxiliary Switch (Applies to Series Trip Only) This is furnished as an integral part of a series pole in single or multi-pole assemblies. Isolated electrically from the protector's circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector's on-off status. Auxiliary switch contacts actuate simultaneously with the main breaker contacts, and will open regardless of whether the breaker contacts are opened manually or electrically. For auxiliary switch ratings below 6Vac or 5Vdc, an auxiliary switch with gold contacts, designated as REG is available. Gold contacts are not recommended for load current above 100 milliamps. Note: Terminal protrusion dimensions are referenced from back of mounting A panel. B Each screw terminal is supplied with a 10-32x.312[7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. CStud terminals are supplied with a flatwasher, external tooth lock washer and a 10-32 or M5 hex nut (<=70A), 1/4-20 or M6 hex nut (>70A). Screw Stud Thread Dimension "A" Dimension "B" M6 .510 .045 [12.95 1.14] .652 .035 [16.56 0.89] 1/4 -20 .545 .045 [13.84 1.14] .687 .035 [17.45 0.89] M5 .510 .045 [12.95 1.14] .652 .035 [16.56 0.89] 10-32 .545 .045 [13.84 1.14] .687 .035 [17.45 0.89] Shunt and Dual Coil Dimension B (See Table) .278 [7.05] 1.26 [32.00] .660 .045 [16.76] 1.14] 1.940 [49.28] .795 [20.19] 2.640 MAX. [67.06] (SEE NOTE A) SHUNT DUAL COIL Spacing for VDE Switch 1.266 [32.16] .676 [17.17] 2.454 MAX. [64.52] (SEE NOTE A) .187 [4.75] .971 [24.66] .676 .971 [17.17] [24.66] .110 [2.79] .250 [6.35] 1.266 [32.16] -IREC5 .187 [4.75] 2.454 MAX. [64.52] (SEE NOTE A) .250 [6.35] Note: Each outer terminal is supplied with a flatwasher, -IREC5 tooth lockwasher and a hex nut. .110 [2.79] -IREC4, -IRE 2.438 MAX. [64.52] (SEE NOTE A) .260 [6.60] -IREC4, -IREG4 IAL Series - Configurations 154 FIG.1 CONFIGURATIONS (CONT.) Barriers Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, interlock and emergency/rapid shutdown circuitry. Trip may be accomplished by voltage or current, which must be removed after trip. .670 [17.02] Voltage Trip Sometimes called "dump circuits" or "panic trip circuits," these units make it possible to open main power contacts with lower power inputs from one or more sources. This configuration is becoming increasingly more important for sensitive circuitry and denser packaging in automation systems. Available in series, shunt or relay configurations. Relay and Dual Coil .281 [7.14] 1.098 [27.89] .122 [3.11] 1.378 [35.00] .952 [24.18] FIG.3 FIG.4 1.147 [29.13] 1.147 [29.13] .721 [18.31] .722 [18.34] .303 [7.69] 3.100 [78.74] 2.740 [69.60] .795 [20.19] .660.045 [16.761.14] 1.330 [33.78] FIG.2 2.560 [65.02] .033 [.84] .033 [.84] .721 [18.31] 2.560 [65.02] 1.940 [49.28] NOTE: THIS BARRIER CAN BE FLIPPED TO COVER EITHER POLE. PLEASE CONTACT FACTORY FOR SPECIFIC PART NUMBER 2.640 MAX [67.06] (SEE NOTE A) BARRIER OPTIONS Standard Barrier Optional Barrier Fig. 1 Fig. 2, 3 & 4 Fig. 2 Fig. 3 & 4 All multi-pole 50/60 Hz Fig. 2 Fig. 3 & 4 All multi-pole 80 VDC, if opposite polarity Fig. 2 Fig. 3 & 4 125VDC Fig. 2 Fig. 3 & 4 Rating Option RELAY RELAY DUAL DUAL COIL COIL IEL 240/415 VAC 415 VAC (VDE) Notes: Tolerance .015 [.39] unless noted. Dimensions in brackets [ ] are millimeters. ATerminal protrusion dimensions are referenced from back of mounting panel. BEach screw terminal is supplied with a 10-32x.312[7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher. CStud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A), 1/4 -20 or M6 hex nut (>70A). 277/480 VAC 1/4-20, M6 studs for AC 120/240 VAC multi-pole 125VDC LEL Note: Optional barrier available with factory assigned part number. Contact factory for assistance. 155 IAL Series - Configurations http://airpax.sensata.com IAL Series Mid-Trip Handle Positions Mid-Trip Indication Circuit protection, rapid fault location and alarm capability are blended together in the Airpax mid-trip indication option. This option is designed for automatic handle movement to a middle position upon electrical overload, allowing for easier detection of the fault circuitand minimizing downtime due to the overload condition. In the optional auxiliary switch configuration, the switch allows an alarm or signal to be forwarded when the breaker trips and the handle moves to the middle position. The alarm can be disengaged by the manual actuation of the handle to the OFF position. Once the fault has been corrected, the circuit breaker can be reset to the ON position. The mid-trip option is available in one, two or three pole toggle handle packages and in either standard panel screw or snap-in mounting. Please see specification tables of specific product for available ratings. Snap-In Mounting The snap-in mounting adapter allows for simplified mounting of most IEL/LEL toggle handle products. Prior to shipment, the adapter is attached to the circuit breaker during our final product assembly, allowing you to securely snap the unit into a rectangular panel cut-out. This eliminates the need for panel mounting hardware and associated assembly costs. Panel Mounting Detail C N NO ON ITIO S PO MID-TRIP POSITION NC BREAKER IN ONOR MANUALLY TURNED OFFPOSITION 2.938.007 [74.63 .18] C O PO FF SI TIO NO N NC BREAKER INMID-TRIP POSITION (ELECTRICALLY TRIPPED) DIM.iAi (SEE TABLE) .995 [25.27] 2.061 [52.35] 1.750 [44.45] 2.495 [63.37] 3.220 [81.79] .687 [17.45] 1.560 [39.62] Available for units up to three poles, with or without an option handle guard. PANEL MOUNTING OPTIONS # of Poles Dimension "A" Panel Thickness 1 pole Note: Tolerance .015 [.39] unless noted. Dimensions in brackets [ ] are millimeters. .760 .007 [19.30 .18] .062 .005 [1.57 .13] 2 pole 1.530 .007 [38.86 .18] .062 .005 [1.57 .13] Panel Mounting Detail Tolerance .005 [.13] unless noted. 3 pole 2.280 .007 [57.91 .18] .062 .005 [1.57 .13] IAL Series - Configurations 156 OPERATING CHARACTERISTICS NOMINAL DCR /IMPEDANCE Current Ratings (Amps) 0.20 Resistance (ohms) Impedance (ohms) DC Delays Impedance (ohms) AC, 50/60Hz Delays AC, 400Hz Delays 51, 52, 53, 59 61, 62, 63, 69 41, 42, 43, 49 45.8 28.5 71.94 1.0 1.38 1.10 2.85 2.0 0.371 0.29 0.76 5.0 0.055 0.051 0.12 10.0 0.017 0.016 0.032 20.0 0.006 0.006 0.010 30.0 0.003 0.004 0.006 50.0 0.0019 0.0018 0.0019 60.0 0.00157 0.00134 -- 70.0 0.00147 0.00133 -- 80.0 0.00146 0.00123 -- 90.0 0.00135 0.00114 -- 100.0 0.00135 0.00114 -- 125.0 0.0005 -- -- 150.0** 0.0005 -- -- 165.0** 0.0004 -- -- 175.0** 0.0004 -- -- 200.0** 0.0004 -- -- 250.0** 0.0004 -- -- 400** 0.0003 -- -- Notes: DCR and impedance based on 100% rated current applied and stablized a minimum of one hour. No 53 delay on 125 amp single pole or 400 amp four pole devices Tolerance: .02 amperes to 2.5 amperes, 20%; 2.6 amperes to 20 amperes, 25%; 21 amperes to 50 amperes, 50%. Consult factory for special values and for coil impedance of delays not shown ** Paralleled poles only, 400 amps only available on CELHP 149 157 IAL IAL/CEL/LEL Series - Operating Characteristics Series - Operating Characteristics http://airpax.sensata.com/ http://airpax.sensata.com IAL Series PERCENTAGE OF RATED CURRENT VS TRIP TIME IN SECONDS AT +25C Delay 100% 125%* 150% 200% 400% 600% 800% 1000% 41* No Trip May trip .5 to 8 .15 to 1.9 .02 to .4 .006 to .25 .004 to .1 .004 to .05 42* No Trip May trip 5 to 70 2.2 to 25 .40 to 5 .012 to 2 .006 to .2 .006 to .15 43* No Trip May trip 35 to 350 12 to 120 1.5 to 20 .012 to 2.2 .01 to .22 .01 to .1 49* No Trip May trip .100 max. .050 max. .020 max. .020 max. .020 max. .020 max. 51 No Trip .5 to 6.5 .3 to 3 .1 to 1.2 .031 to .5 .011 to .25 .004 to .1 .004 to .08 52 No Trip 2 to 60 1.8 to 30 1 to 10 .15 to 2 .04 to 1 .008 to .5 .006 to .1 53** No Trip 80 to 700 40 to 400 15 to 150 2 to 20 .23 to 9 .015 to .55 .012 to .2 59 No Trip .120 max. .100 max. .050 max. .022 max. .017 max. .017 max. .017 max. 61 No Trip .7 to 12 .35 to 7 .130 to 3 .030 to 1 .015 to .3 .01 to .15 .008 to .1 62 No Trip 10 to 120 6 to 60 2 to 20 .2 to 3 .02 to 2 .015 to .8 .01 to .25 63 No Trip 50 to 700 30 to 400 10 to 150 1.5 to 20 .4 to 10 .013 to .85 .013 to .5 69 No Trip .120 max .100 max. .050 max. .022 max. .017 max. .017 max. .017 max 71 No Trip .44 to 10 .3 to 7 .100 to 3 .030 to 1 .012 to .3 .004 to .15 .004 to .1 72 No Trip 1.8 to 100 1.7 to 60 1 to 20 .15 to 3 .015 to 2 .008 to .79 .006 to .28 73 No Trip 50 to 600 30 to 400 10 to 150 1.8 to 20 .015 to 10 .015 to .88 .011 to .5 79 No Trip .120 max .100 max. .050 max. .023 max. .016 max. .015 max. .015 max Notes: All trip curves and trip currents are specified with the protector mounted in the normal vertical position at ambient temperature of +25 C. Protectors do not carry current prior to application of overload. A: Ratings above 30 amps may deviate from the above limits by approximately 10% (130% for delay 49). * No 53 delay on 125 amp single pole or 400 amp four pole devices * 135% for delay 71, 72, 73 & 79 http://airpax.sensata.com/ IAL- Series - Operating Characteristics IAL/CEL/LEL Series Operating Characteristics 150 158 DELAY CURVES 400Hz, DC, 50/60Hz Delay Curves (typ) Inrush Pulse Tolerance A choice of delays is offered for DC, 50/60Hz, 400Hz, or combined DC/50/60Hz applications. Delays 49, 59, 69 and 79 provide fast-acting, instantaneous tripping and are often used to protect sensitive electronic equipment (not recommended where a known inrush exists). Delays 41, 51, 61 and 71 have a short delay for general purpose applications. Delays 42, 52, 62 and 72 are long enough for most transformers and capacitor loads. Delays 43, 53, 63 and 73 are extra long for special motor applications. Pulse tolerance is defined as a single pulse of half sine wave peak current amplitude of 8 milliseconds duration that will not trip the circuit breaker. 0 300 400 400 500 500 600 600 700 700 800 800 900 900 1000 1000 .001 MAY TRIP 10000 DELAY DELAY 63 63 10 10 1 1 .1 .1 .1 .01 .01 .01 800 900 9001000 1000 IAL IAL/CEL/LEL Series - DelaySeries Curves- Operating Characteristics 100 150 200 100 150 200 300 125 125 300 400 400 500 500 600 600 700 700 800 800 900 900 1000 1000 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT 100 10 1 .001 DELAY DELAY 69 69 1000 100 300 400 400 500 500 600 600 700 700 800 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT MAY TRIP MAY TRIP 0 10000 1000 100 .001 .001 0 100 150 100 200 150 200 300 0 125 125 .001 0 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS 100 150 200 100 150 200 300 125 125 MAY TRIP 1000 1000 149 159 .01 .01 1000010000 100 .1 .1 MAY TRIP .001 0 1 1 .01 .01 10 10 .1 .1 100 TIME IN SECONDS TIME IN SECONDS 1 1 DELAY DELAY 62 62 1000 100 10 10 10000 1000 MAY TRIP 100 100 TIME IN SECONDS DELAY DELAY 61 61 1000 1000 .001 10000 10 MAY TRIP 10000 MAY TRIP 10000 The table on page 171 provides a guide to determine if the inertia delay feature is required. Consult factory for further assistance. 1 .1 .01 .001 0 0 100 150 200 100 150 200 300 125 125 300 400 500 600 700 400 500 600 700 800 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT 800 900 900 1000 1000 http://airpax.sensata.com/ http://airpax.sensata.com IAL Series DC Delay Curves (typ) PULSE TOLERANCES 10000 61, 62, 63, 71, 72, 73 10 times (approx.) rated current 61F, 62F, 63F, 71F, 72F, 73F 12 times (approx.) rated current 64, 65, 66 (0 - 50A) 25 times (approx.) rated current 64, 65, 66 (>50 - 80A) 20 times (approx.) rated current 64, 65, 66 (>80 - 100A) 18 times (approx.) rated current MAY TRIP 1000 TIME IN SECONDS 1 10 1 .1 .1 .01 .01 0 100 150 200 125 300 400 500 600 700 800 900 1000 .001 0 PERCENT OF RATED CURRENT 10000 100 150 200 125 300 400 500 600 700 800 900 1000 900 1000 PERCENT OF RATED CURRENT 10000 DELAY 52 MAY TRIP 100 TIME IN SECONDS 100 10 1 10 1 .1 .1 .01 .01 0 100 150 200 125 DELAY 59 1000 300 400 500 600 700 PERCENT OF RATED CURRENT http://airpax.sensata.com/ 800 900 1000 MAY TRIP 1000 .001 DELAY 53 100 10 .001 MAY TRIP DELAY 51 100 TIME IN SECONDS Pulse Tolerance 10000 1000 TIME IN SECONDS Delay .001 0 100 150 200 125 300 400 500 600 700 800 PERCENT OF RATED CURRENT IAL Characteristics Series - Delay Curves IAL/CEL/LEL Series - Operating 150 160 400Hz Delay Curves (typ) *Available only in IAL/IUL/IEL; not available in LEL. 10000 DELAY 41 10 1 .01 .01 0 100 150 200 125 300 400 500 600 700 800 900 1000 .001 0 DELAY 42 MAY TRIP 300 400 500 600 700 800 900 1000 900 1000 PERCENT OF RATED CURRENT 1 10 1 .1 .1 .01 .01 100 150 200 125 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT IAL IAL/CEL/LEL Series - DelaySeries Curves- Operating Characteristics MAY TRIP 100 10 0 DELAY 49 1000 TIME IN SECONDS 100 .001 100 150 200 125 PERCENT OF RATED CURRENT 10000 1000 TIME IN SECONDS 1 .1 10000 149 161 10 .1 .001 DELAY 43 100 TIME IN SECONDS 100 TIME IN SECONDS 1000 MAY TRIP 1000 MAY TRIP 10000 .001 0 100 150 200 130 300 400 500 600 700 800 PERCENT OF RATED CURRENT http://airpax.sensata.com/ http://airpax.sensata.com IAL Series DC/50/60Hz Dual-frequency Delay Curves (typ) 10000 10000 100 10 1 1 .1 .01 .01 0 100 150 200 135 300 400 500 600 700 800 900 1000 .001 100 150 200 135 300 400 500 600 700 800 900 1000 900 1000 PERCENT OF RATED CURRENT 10000 DELAY 73 MAY TRIP 100 TIME IN SECONDS 100 10 1 10 1 .1 .1 .01 .01 0 100 150 200 135 DELAY 79 1000 300 400 500 600 700 PERCENT OF RATED CURRENT http://airpax.sensata.com/ 800 900 1000 MAY TRIP 1000 .001 0 PERCENT OF RATED CURRENT 10000 TIME IN SECONDS 10 .1 .001 DELAY 72 MAY TRIP 1000 TIME IN SECONDS 100 TIME IN SECONDS DELAY 71 MAY TRIP 1000 .001 0 100 150 200 135 300 400 500 600 700 800 PERCENT OF RATED CURRENT IAL Characteristics Series - Delay Curves IAL/CEL/LEL Series - Operating 150 162 IAL/IUL/IEL/IDL/LEL SPECIFICATIONS Trip Free Will trip open on overload even when forcibly held in the ON position. This prevents the operator from damaging the circuit by holding the breaker on. Trip Indication The operating handle moves positively to the OFF or mid-trip position on electrical overload. Ambient Operation IAL/IUL/IEL protectors operate in temperatures between -40C to +85C. Insulation Resistance Not less than 100 megohms at 500 volts DC. Dielectric Strength IAL/IUL/IEL protectors withstand 3750Vac (1250Vac for LEL), 60Hz for 60 seconds between all electrically isolated terminals except auxiliary switch terminals shall withstand 600Vac, 60Hz for REG and REC types. Four terminal dual coil and relay construction (not offered in the LEL) will withstand 1500Vac. Moisture Resistance Meet all the requirements of MIL-PRF-55629 when tested in accordance with Method 106 of MIL-STD-202. Shock Circuit protectors shall not trip when tested per MIL-STD-202, Method 213, Test Condition I with 100% rated current applied to delayed units and 80% rated current to instantaneous units. Vibration Circuit protectors shall not trip when vibrated per MILSTD-202, Method 204, Test Condition A with 100% rated current applied to delayed units and 80% rated current to instantaneous units. UL-1500 (Marine Ignition Protected) The IDL/IDLH is approved for Marine Ignition Protection (series configuration only), covering ignition protected circuit breakers. This specification requires devices to be used in accordance with the requirementsof U.S. Coast Guard and Fire Protection Standard for Pleasure and Commercial Motor Craft, ANSI/MFPA #302. Endurance Operating as a switch, the operating life exceeds 10,000 operations, 6000 at rated load, 4000 without load, at a rate of 6 per minute. Electrical Characteristics .050-100 amperes 80Vdc, 240Vac Max., 240/415Vac at 50 amperes Max., 50/60Hz and 400Hz. Consult factory for specific product ratings. Units rated for 240/415Vac and above 50 amperes are not suitable for across-the-line motor starting. APPROXIMATE WEIGHT PER POLE Ounces Grams 3.1 90 Poles One through six poles available. Construction Series, shunt, relay dual coil and series with auxiliary switch available in various delays and combinations. Auxiliary Switch When supplied shall be S.P.D.T. configuration. Non VDE approved switches have a maximum UL rating of 10.0 amperes, 250 volts, 60Hz; 3.0 amperes, 50 volts DC (REC type) or 0.1 amperes, 125 volts, 60Hz (REG type). VDE approved switches have a maximum UL rating of 10.0 amperes, 250 volts, 60Hz (REC type); or 0.1 amperes, 125 volts, 60Hz (REG; type). The maximum VDE ratings are 1.0 amperes, 125 volts, 60Hz (REC type); 0.1 amperes, 125 volts, 60Hz (REG type). Salt Spray (Corrosion) Meet the requirements of MIL-PRF-55629 when tested in accordance with Method 101 of MIL-STD-202. 149 163 IAL IAL/CEL/LEL Series - Specifications Series - Operating Characteristics RECOMMENDED TORQUE SPECIFICATIONS Component Torque (in-lbs) 6-32 Mounting Inserts 6 to 8 M3 Mounting Screws 4 to 5 10-32 Screw Terminals 14 to 15 M5 Terminal Screws 14 to 15 10-32 Stud Terminals 13 to 14 M5 Stud Terminals 13 to 14 1/4 - 20 Stud Terminals 40 to 45 M6 Stud Terminals 40 to 45 1/2 - 32 Mounting Bushing 30 to 35 Where applicable, mechanical support must be provide to the terminals when applying torque http://airpax.sensata.com/ http://airpax.sensata.com IAL Series IAL/IUL/IEL/IDL/LEL/LELHP SPECIFICATIONS AGENCY APPROVALS - IAL/IUL/IEL Voltage 65 65(4) 65(4) 65 80 80 80 80 125 250 300 125 125 125(5) 120/240 125/250(5) 240 240 250 250 250 250 250 250(5) 277 277 240/415 240/415 277/480 277/480 277/480 277480 480 480 250 Frequency (Hz) DC DC DC DC DC DC DC DC DC DC DC 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 400 Phase 1 1 1 1 1 1&3 3 3 3 1 3 3 3 1 1&3 3 1 3 3 3 1&3 1&3 3 1&3 Min. Poles 1 1 1 2** 1 1 2 3 2 2+ 3++ 1 1 1 2 2 only 1 2 1 1 1 2 1 3 only 1 1 2 2 2 2 2 2 2 2 1 TC 1 1 1 2 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 1 1 1 1 2 OL 1 1 1 1 1 1 1 0 0 0 0 0 1 1 1 1 0 1 1 1 1 0 0 1 1 1 0 0 1 1 1 0 1 0 1 UL/CSA .02-100 .02-100 .02-50 101-150 .02-70 70.1-100 101-150 251-300 .02-100 .02-50 .02-50 .02-70 .02-100 .02-100 .02-100 .02-100 .02-70 .02-100 .02-50 .02-50 .02-50 .02-80 .02-60 .02-100 .02-50 .02-50 .02-50 .02-50 .02-30 .02-50 .02-30 .02-50 .02-30 .02-50 .02-50 AGENCY APPROVALS - IDL/IDLP (MARINE) VDE (amps) .10-70 .10-50 .10-50 .10-100 .10-100 .10-100 .10-100 .10-100 .10-50 .10-50 - UL 1077 & CSA (AIC) U2, 7500 U2, 3000 U2, 5000 U2, 7500 U2, 7500 U2, 5000 U1, 10000 U2, 7500 U2, 5000 U1, 5000 U2, 1000 U2, 5000 U1, 3000 U3, 1500 U1, 2000 U3, 1500 U1, 2000 U2, 2000 U2, 3000 C2, 5000(1) C2, 5000(2) U1, 1000 U1, 5000 U3, 2000 U2, 2000 C2, 5000(1) U2, 2000 C2, 5000(1) U2, 2000 U2, 1200 C2, 5000(3) C2, 5000(3) C2, 5000(3) C2, 5000(3) U2, 1500 VDE (AIC) 4000 4000 5000 2000 2000 2000 2000 2000 2000 2000 - VDE (amps) .10-100 125-150 151-200 .05-70 .10-50 .10-50 - UL489 (AIC) 7500 50 000 50000 10000 50000 10000 10000 5000 5000 10000 5000 5000 5000 VDE (AIC) 2000 2000 2000 3000 2000 2000 - - 10000 AIC (UL489A) - Voltage 48 48 65 80 125 250 250 Frequency (Hz) DC DC DC DC 50/60 50/60 50/60 Phase 1 1 1&3 Min. Poles 1 2** 1 1 1 2 1 TC 1 1 1 1 1 1 1 OL 1 1 1 1 1 1 1 UL/CSA .02-100 101-150 .02-60 .02-100 .02-100 .02-100 .02-60 VDE (amps) - UL 1077 & CSA (AIC) U1, 5000 U1, 5000 U1, 1000 U2, 1500 U 1, 1500 U2, 1500 U1, 1000 VDE (AIC) - UL 1077 & CSA (AIC) C2, 5000(1) VDE (AIC) - UL 1077 & CSA (AIC) C2, 5000(3) C2, 5000(3) VDE (AIC) - AGENCY APPROVALS - IULQ (TAPPED COIL) Frequency Voltage (Hz) 125/250 50/60 Phase 1 Min. Poles 1 TC 1 OL 1 UL/CSA 2/1-30/15 VDE (amps) - AGENCY APPROVALS - IULD (DUST SEALED) Voltage 250 277 Frequency (Hz) 50/60 50/60 Phase 1&3 1 Min. Poles 1 1 TC 1 1 OL 1 1 UL/CSA .02-100 .02-30 VDE (amps) - Notes: ** Paralleled poles; + 2 poles in series; ++ 3 poles in series; (1) With 125 A max. series fuse; (2) Series combination with 209 or 229 series (100 A max.); (3) With 100 A max. series fuse; (4) With blocked vent construction (5) Non-standard construction. "Fit for further use" approval AGENCY APPROVALS - LEL/LELHP Voltage 65 65 65 80 80 80 80 125 125/250 125 125 120/240 240 Frequency (Hz) DC DC DC DC DC DC DC DC DC 50/60 50/60 50/60 50/60 Phase 1&3 1&3 1 1&3 Min. Poles 1 2** 3** 1 1 2** 3** 1 2 1 1 2 1 UL/CSA .05-50 101-150 175-200 .05-100 .05-100 125-150 175-200 .05-70 .05-50 .05-40 .05-50 .05-70 .05-20 AGENCY APPROVALS - CELHP 80 DC - 4 400 AGENCY APPROVALS - CEL/CELP (COMMUNICATIONS) Voltage 65 65 80 80 80 125 80 Frequency (Hz) DC DC DC DC DC DC DC Phase - Min. Poles 1 2** 1 2** 3** 1 1 http://airpax.sensata.com/ UL/CSA .05-50 101-150 .05-100 101-200 201-250 .05-70 15.1-125 VDE (amps) - UL 489A (AIC) 7500 50000 50000 10000 10000 5000 10000 VDE (AIC) - General notes: * All supplementary protectors are of the overcurrent (OC) type * The family of protectors has been evaluated for end use application for use groups (UG) A, B, C and D * The terminals (FW) are suitable for factory wiring only (0) * The maximum voltage ratings for which the protectors have been tested are shown in the chart * The current is the amperage range that the protectors have been tested * The tripping current (TC) for all of the protectors is either either "1" (in the range of 125% to 135% of ampere rating) or "2" (more than 135% of ampere rating) * The overload rating (OL) - designates whether the protector has been tested for general use or motor starting applications. 0 - tested at 1.5 times amp rating for general use 1 - tested at 6 times AC rating or 10 times DC rating for motor starting * The short circuit current rating (SC) - The short circuit rating in amperes following a letter and number designating the test conditions and any calibration following the short circuit test is defined below: C - Indicates short circuit test was conducted with series overcurrent protection U - Indicates short circuit test was conducted without series overcurrent protection 1 - Indicates a recalibration was not conducted as part of the short circuit testing 2 - Indicates a recalibration was performed as part of the short circuit testing 3 - Indicates recalibration was performed along with the dielectric and voltage withstand for "Suitable for Further Use" rating IAL Characteristics Series - Specifications IAL/CEL/LEL Series - Operating 150 164 IAL/IUL/IEL DECISION TABLES The ordering code for IAL/IUL/IEL/LEL circuit protectors may be determined by following the decision steps in the appropriate part number decision table subsequent to this page. The coding given permits a self-assigning part number but with certain limitations. Special applications may require a factory assigned part number. Typical examples are units with mixed ratings, combinations of styles, or constructions not listed in the third decision table, etc. With these, it is suggested that order entry be by description and/or drawings, and a part number will be established. Additionally, it is standard policy to establish a factoryassigned part number whenever a descriptive drawing exists to provide cross reference, traceability and manufacturing control. When specifying a circuit breaker for AC motor start or high inrush applications, the peak amplitude and surge duration should be specified for factory assistance in rating selection. 1 Select Type and Terminal Type To determine the ordering number for your particular IAL/IUL/IEL unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have. One handle per unit IALH **IULH ***IELH One handle per pole IALN ***IULN One handle per unit panel seal IALX **IULX ***IELX One handle per unit, rocker, bracket mounting IALZX **IULZX ***IELZX One handle per unit, rocker, integral mounting Terminal Standard screw terminal, no designation required K Stud terminals C Clip terminals B Bullet terminals One handle per unit UL 1500 One handle per pole UL 1500 * IDLH *** IML One handle per unit mid trip indication *** IMLH One handle per pole mid trip indication IALBX **IULBX ***IELBX One handle per unit, rocker, accidental-off protection **IMLBX One handle per unit, mid trip indication, rocker, accidental-off protection *UL Recognized **UL Recognized, CSA Certified ***UL Recognized, CSA Certified, VDE Approved Third Decision Internal Configuration -0 Switch only (50, 70 or 100 amp switch) -1 Series -1REC4 Series with auxiliary switch* .110 quick connect 1 Single pole 11 Two pole 111 Three pole 1111 Four pole* *Not available in toggle seal handle type. Consult factory for 5 and 6 pole IEL part number. Example: IEL 1 - 1REC4- 61- 20.0 - 01 - V 1 4 2 3 4 5 7 Fourth Decision SW Switch only -41 400Hz short delay -42 400Hz long delay -43 400Hz motor start -49 400Hz 150% instant trip -51 DC short delay -52 DC long delay -53 DC motor start -1REC5 Series with auxiliary switch* .187 quick connect -1REG4 Series with auxiliary switch .110 quick connect -59 DC 125% instant trip -61 50/60Hz short delay Series with alarm switch, electrical trip, .110 quick connect terminals -62 50/60Hz long delay -63 50/60Hz motor start Series with alarm switch, electrical trip, .110 quick connect terminals (mid-trip only) -69 50/60Hz 125% instant trip -71 DC/60Hz short delay -72 DC/60Hz long delay -73 DC/60Hz motor start -79 DC/60 Hz 135% instant trip -1RS4 -1RLS4 Series with alarm switch, electrical trip, .187 quick connect terminals -3 Shunt -4 Relay (not available in IEL/IELX) * Only one auxiliary switch is normally supplied on two or three pole units. Switch is located in the right-hand pole (viewed from terminal end) unless otherwise specified. C = CCC Approved Note: CCC Approval is pending. IAL Series - Decision Tables Second Decision Frequency & Delay This approval requires the addition of a C at the end of the part number. The unit will not be VDE Approved. 165 2 Poles * IDL -1RS5 Notes: IEL, IELH and IELX circuit protectors are designed to meet 8mm creepage clearance requirements for installation Category 111, Pollution Degree 3, Case A as measured in IEC 664. Intended for use in equipment to comply with IEC 950, 601 and VDE 0804 & 0805. Description IAL **IUL ***IEL 3 For example the code shown is the code for a single pole breaker with a series construction and auxiliary switch, designed for operation in a 50/60Hz circuit. It has a short time delay, rating of 20 amperes and a marked black handle, and is VDE approved. First Decision For addition of inertial delay, add an iFi to any delay numeral. V = VDE and CCC Approved The shaded areas denote VDE and CCC (if applicable) Approval options. This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE or CCC Approved, but other approvals still apply. Note: CCC Approval is pending. http://airpax.sensata.com Optional Optional ON I O OFF Standard hardware. No designation required. Standard hardware. No designation required. Use three numbers print required Use three numbers toto print required current value between .100 amps current value between .100 amps minimum and 100 amps maximum. minimum and 100 amps maximum. INDICATING COLOR ROCKER HANDLE COLOR ON I -A-A Metric thread mounting inserts and terminals Metric thread mounting inserts and terminals -B-B Barrier Barrier -C-C (See (See 277V (50/60Hz only) note 277V (50/60Hz only) note 3)3) -D-D 240/415V (50/60Hz only) 240/415V (50/60Hz only) O OFF INDICATING COLOR LINE The VDE (lth) will 95% the The VDE (lth) will bebe 95% ofof the UL/CSA rated current. UL/CSA rated current. LINE LOAD ON LINE ON O OFF FIG. 1 (See (See 277V/480V (50/60Hz only) note 277V/480V (50/60Hz only) note 4)4) -E-E INDICATION "OFF" Mounting/Indicator Code: F, G, H INDICATION "ON" Mounting/Indicator Code: A, B, C FIG. 2 O OFF LINE LOAD OFF FIG. 3 LINE LOAD ON FIG. 5 FIG. 4 LINE LOAD OFF O For example, use: For example, use: .100 2.00 10.0 .100 oror 2.00 oror 10.0 ON FIG. 6 MARKING DETAIL "A" (SEE TABLE) -G-G Handle Handle guard, (available ZX, BX and snap-in guard, (available inin ZX, BX and snap-in versions only) versions only) INDICATING COLOR OFF O Snap-in face plate adapter Snap-in face plate adapter INDICATION "ON" Mounting/Indicator Code: J, K, L -01 (STD) -01 (STD) Yellow Yellow -10 -10 -11 -11 Red Red -20 -20 -21 -21 Blue Blue -30 -30 -31 -31 Green Green -40 -40 -41 -41 Orange Orange -60 -60 -61 -61 White White -90 -90 -91 -91 -X-X Handle guard with actuation feature Handle guard with nono actuation feature (BX rocker only) (BX rocker only) -1-1 Silver 5/16" (.312") bullet Silver 5/16" (.312") bullet -2-2 Gold 5/16" (.312") bullet Gold 5/16" (.312") bullet LINE OFF LOAD O OFF O ON ON FIG. 2 FIG. 1 LOAD LINE LOAD LINE ON FIG. 3 O -W Wire -W Wire clamp supplied (VDE approved clamp supplied (VDE approved upup toto and including 16.0 amps) and including 16.0 amps) Marked* Marked* ON-OFF ON-OFF I-OI-O ROCKER HANDLE COLOR I ON OFF FIG. 5 FIG. 4 LOAD LINE ON OFF O -00 -00 Handle lock Handle lock LINE -U-U 120/240V 120/240V 50/60Hz 50/60Hz IAL, IUL, IEL, IALH, IAL, IUL, IEL, IALH, IULH, IELH - Toggle Handle IULH, IELH - Toggle Handle Black Black -L-L -P-P Handle Color and Marking Selection Handle Color and Marking Selection Unmarked Unmarked 1/4- 20 - 20 stud(M6 (M6 stud when option selected) 1/4 stud stud when -A-A option is is selected) (<=70A requires >70A not use -K) (<=70A requires -K,-K,if if >70A dodo not use -K) -M-M Handle Handle opposite pole inin opposite pole 7 7 Seventh Seventh Decision Decision Color Color -K-K FIG. 6 MARKING DETAIL "B" (SEE TABLE) Notes: Notes: 1. One more descriptions may used required. 1. One or or more descriptions may bebe used as as required. 2. When this is not used, table one may substituted and U.S. thread and 2. When this is not used, table one may bebe substituted and U.S. thread and two lockwashers will supplied. Unit will rated 250V (50/60Hz only.) two lockwashers will bebe supplied. Unit will bebe rated at at 250V (50/60Hz only.) 3. VDE approved 250Vac 3. VDE approved at at 250Vac 4. VDE approved 415Vac 4. VDE approved at at 415Vac LINE INDICATION "OFF" Mounting/Indicator Code: M, N, P, R LOAD LINE ON O O OFF FIG. 2 FIG. 3 LINE LOAD OFF O ON FIG. 6 MARKING DETAIL "C" (SEE TABLE) 7 7 Seventh Seventh Decision Decision Rocker Handle Color, Indicator Color and Marking Selection (See Notes) Rocker Handle Color, Indicator Color and Marking Selection (See Notes) IALX, IULX, IELX, IALZX, IULZX, IELZX Rocker Handle (Single Rocker Color) IALX, IULX, IELX, IALZX, IULZX, IELZX Rocker Handle (Single Rocker Color) Vertical Mounting Vertical Mounting Rocker Rocker Handle Handle Color Color Horizontal Mounting Horizontal Mounting On-Off On-Off Fig.4 Fig.4 I-OI-O Fig.5 Fig.5 On-Off On-Off I-OI-O Fig.6 Fig.6 Indicating Indicating Color Color Marking Marking Color Color Indicates: Indicates: Unmarked Unmarked On-Off On-Off Fig.1 Fig.1 I-OI-O Fig.2 Fig.2 On-Off On-Off I-OI-O Fig.3 Fig.3 Black Black N/A N/A White White N/A N/A -00 -00 -01-01 -02 -02 -03 -03 -04 -04 -05 -05 -06 -06 Red Red N/A N/A White White N/A N/A -20 -20 -21 -21 -22 -22 -23 -23 -24 -24 -25 -25 -26 -26 Grey Grey N/A N/A Black Black N/A N/A -40 -40 -41 -41 -42 -42 -43 -43 -44 -44 -45 -45 -46 -46 Orange Orange N/A N/A Black Black N/A N/A -50 -50 -51 -51 -52 -52 -53 -53 -54 -54 -55 -55 -56 -56 White White N/A N/A Black Black N/A N/A -90 -90 -91 -91 -92 -92 -93 -93 -94 -94 -95 -95 -96 -96 Marking Marking Detail Detail AA IALZX, IULZX, IELZX Rocker Handle (Dual Rocker Color) IALZX, IULZX, IELZX Rocker Handle (Dual Rocker Color) Black Black White White White White OnOn -A0 -A0 -A1 -A1 -A2 -A2 -A3 -A3 -A4 -A4 -A5 -A5 -A6 -A6 Black Black Red Red White White OnOn -B0 -B0 -B1 -B1 -B2 -B2 -B3 -B3 -B4 -B4 -B5 -B5 -B6 -B6 Black Black Green Green White White OnOn -C0 -C0 -C1 -C1 -C2 -C2 -C3 -C3 -C4 -C4 -C5 -C5 -C6 -C6 Black Black White White White White Off Off -F0 -F0 -F1 -F1 -F2 -F2 -F3 -F3 -F4 -F4 -F5 -F5 -F6 -F6 Black Black Red Red White White Off Off -G0 -G0 -G1 -G1 -G2 -G2 -G3 -G3 -G4 -G4 -G5 -G5 -G6 -G6 Black Black Green Green White White Off Off -H0 -H0 -H1 -H1 -H2 -H2 -H3 -H3 -H4 -H4 -H5 -H5 -H6 -H6 -J1 -J1 Black Black White White White White OnOn -J0 -J0 -J2 -J2 -J3 -J3 -J4 -J4 -J5 -J5 -J6 -J6 Black Black Red Red White White OnOn -K0 -K0 -K1 -K1 -K2 -K2 -K3 -K3 -K4 -K4 -K5 -K5 -K6 -K6 Black Black Green Green White White OnOn -L0 -L0 -L1 -L1 -L2 -L2 -L3 -L3 -L4 -L4 -L5 -L5 -L6 -L6 AA BB IALBX, IULBX, IELBX, LELBX Rocker Handle (Dual Rocker Color) IALBX, IULBX, IELBX, LELBX Rocker Handle (Dual Rocker Color) Black Black White White White White Off Off -M0 -M0 N/A N/A -M2 -M2 -M3 -M3 N/A N/A N/A N/A -M6 -M6 Black Black Red Red Red Red OffOff -N0 -N0 N/A N/A -N2 -N2 -N3 -N3 N/A N/A N/A N/A -N6 -N6 Black Black Green Green Green Green Off Off -P0 -P0 N/A N/A -P2 -P2 -P3 -P3 N/A N/A N/A N/A -P6 -P6 Black Black Yellow Yellow Yellow Yellow Off Off -R0 -R0 N/A N/A -R2 -R2 -R3 -R3 N/A N/A N/A N/A -R6 -R6 Notes: Bezels IALBX, IULBX, IELB, IELBX black. Notes: A. A. Bezels of of IALBX, IULBX, IELB, IELBX areare black. Consult factory other marking options. B. B. Consult factory forfor other marking options. CC ROCKER HANDLE COLOR IAL Series 6 6 Sixth Sixth Decision Decision Rated Current Rated Current O 5 5 Fifth Fifth Decision Decision LEL DECISION TABLES 1 First Decision 5 Select Type and Terminal Type Rated Current Terminal Description LEL One handle per unit LELH One handle per pole LML One handle per unit, mid-trip indication LMLH One handle per pole, mid-trip indication Use three numbers to print (.050 or 1.50 or 100) Value between .050 amps and 100 amps. Standard screw terminal, no designation required K Stud terminals C Clip terminals B Bullet terminals 6 One handle per unit, rocker, integral mounting LMLZX One handle per unit, rocker, mid-trip indication, integral mounting Example: LELBX One handle per unit, rocker, accidental-off protected LEL 1 - 1REC4 - 61 - 20.0 - 01 - V LMLBX One handle per unit, rocker, mid-trip indication, accidental-off protected 1 -A Metric thread mounting inserts and terminals -B Barrier -F 240V 50/60Hz -G Handle guard, (available in ZX, BX and snap-in versions only) -K 1/4 - 20 Stud (M6 Stud when -A -L Handle Lock -M Handle in opposite pole Fourth Decision -P Snap-in mounting plate adapter Frequency and Delay -U 120/240Vac, 5000 A.I.C., 70A max. 2 pole only with barrier (VDE 250Vac) 2 3 4 5 7 Note: Other options available, consult factory. 4 Second Decision Poles 1 Single pole 11 Two pole 111 Three pole 3 Third Decision Internal Configuration -1REC4 Series with auxiliary switch .110 quick connect -1REC5 Series with auxiliary switch .187 quick connect -1REG4 Series with auxiliary switch (gold contacts) .110 quick connect -1RS4 Series with alarm switch, electrical trip, .110 quick connect -1RLS4 Series with alarm switch, electrical trip, .110 quick connect* * Used only with mid-trip. option is selected) ( 50A requires -K, >50A do not use -K) -51 DC short delay -V 125VDC -52 DC long delay -X -53* DC motor start Handle guard with no actuate "off" feature (see detail C) -59 DC 125% instant trip -1 Silver 5/16" (.312") bullet -61 50/60Hz short delay -2 Gold 5/16" (.312") bullet -62 50/60Hz long delay -63 50/60Hz motor start -69 50/60Hz 125% instant trip Notes: 1. One or more descriptions may be used as required. 2. When this decision is not used, decision 7 may be substituted and U.S. thread will be supplied. 3.If (M5 or M6) studs are required, use "A" only on an LELK. For addition of inertial delay, add an "F" to any delay numeral. *Not available above 100 amps. 7 Series -1 Sixth Decision Optional LELZX 2 Fifth Decision V = VDE and CCC Approved The shaded areas denote VDE and CCC (if applicable) Approval options.This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE or CCC Approved, but other approvals still apply. C = CCC Approved The approval requires the addition of a C at the end of the part number. The unit will not be VDE Approved. Seventh Decision LEL Toggle Handle Color Selection -01 Black w/ white markings -11 Yellow w/ black markings -21 Red w/ white markings -31 Blue w/ white markings -41 Green w/ white markings -61 Orange w/ black markings -91 White w/ black markings See alternate 7th Decision for ZX and BX Rocker Handles. Notes: The LEL family of circuit breakers are designed to meet 8mm creepage and clearance requirements for installation Category 111, pollution degree 3, Case A as measured in IEC 664. Intended for use in equipment designed to comply with IEC 380, 435, 601 AND VDE 0730, 0804 & 0805. 149 167 LELIAL/CEL/LEL Series - Decision Tables Series - Operating Characteristics http://airpax.sensata.com/ http://airpax.sensata.com IAL Series 7 Seventh Decision Rocker Handle Color, Indicator Color and Marking Selection (See Notes) LELZX & LMLZX Rocker Handle (Single Rocker Color) Vertical Mounting Rocker Handle Color Horizontal Mounting Unmarked On-Off Fig.1 I-O Fig.2 On-Off I-O Fig.3 N/A -00 -01 -02 -03 N/A -20 -21 -22 -23 Indicating Color Marking Color Indicates: Black N/A White Red N/A White ON I On-Off Fig.4 I-O Fig.5 On-Off I-O Fig.6 -04 -05 -06 -24 ROCKER HANDLE -25 COLOR Grey N/A Black N/A -40 -41 -42 -43 -44 -45 Orange N/A Black N/A -50 -51 -52 -53 -54 INDICATING -55 White N/A Black N/A -90 -91 -92 -93 -94 O OFF COLOR -46 O OFF -56 INDICATION "OFF" Mounting/Indicator Code: F, G, H INDICATION "ON" Mounting/Indicator Code: A, B, C White On -A0 -A1 -A2 Black Red White On -B0 -B1 -B2 Black Green White On -C0 -C1 -C2 Black White White Off -F0 -F1 -F2 -F3MARKING -F4 -F5 DETAIL "A" (SEE TABLE) -F6 Black Red White Off -G0 -G1 -G2 -G3 -G4 -G5 -G6 Black Green White Off -H0 -H1 -H2 -H3 -H4 -H5 -H6 Black White White On -J0 -J1 -J2 -J3 -J5 -J6 Black Red White On -K0 -K1 -K2 -K3 -K4 -K5 -K6 Black Green White On -L0 -L1 -L2 -L3 -L4 -L5 -L6 N/A -M5 -M6 N/A -N5 -N6 N/A -P5 -P6 -B4LINE O OFF -C3 FIG. 1 FIG. 2 O OFF OFF -C4 FIG. 3 LINE ON OFF FIG. 5 FIG. 4 White White Off -M0 N/A -M2 -M3 Black Red Red Off -N0 N/A -N2 -N3 Black Green Green Off -P0 N/A -P2 -P3 -J4 OFF O N/A -R2 OFF O -R3 LOAD OFF O N/A ON ON FIG. 2 FIG. 1 LOAD LINE LOAD LINE ON FIG. 3 OFF LOAD LINE -R5 ON FIG. 5 FIG. 4 A -C6 ROCKER HANDLE COLOR INDICATION "ON" Mounting/Indicator Code: J, K, L -B6 ON INDICATING COLOR O -R0 Off LINE LOAD -C5FIG. 6 I ON Black Yellow LINE LOAD OFF O LINE -A6 LINE -B5 LOAD ON ON O -B3 LOAD -A5 -A4 O -A3 LELBX Rocker Handle (Dual Rocker Color) Yellow A -96 White Notes: A. Bezels of IALBX, IULBX, IELB, IELBX are black. B. Consult factory for other marking options. ROCKER HANDLE COLOR LINE Black Black INDICATING COLOR ON I -95 LINE LELZX & LMLZX Rocker Handle (Dual Rocker Color) -26 Marking Detail B C -R6 FIG. 6 MARKING DETAIL "B" (SEE TABLE) LINE INDICATING COLOR ROCKER HANDLE COLOR ON I INDICATING COLOR ON I O OFF O OFF ROCKER HANDLE COLOR OFF O INDICATING COLOR ROCKER HANDLE COLOR I ON LINE INDICATION "ON" Mounting/Indicator Code: A, B, C INDICATION "OFF" Mounting/Indicator Code: F, G, H LOAD ON LINE OFF FIG. 1 ON O FIG. 2 O OFF FIG. 3 LOAD LINE LINE OFF ON FIG. 4 LOAD LINE OFF O O FIG. 5 LOAD ON FIG. 6 MARKING DETAIL "A" (SEE TABLE) http://airpax.sensata.com/ Area reserved for amperage marking. HANDLE POSITION "OFF" INDICATION "OFF"INDICATION "OFF" WITH GUARD Mounting/IndicatorMounting/Indicator Code: M, N, P, R Code: M, N, P, R INDICATION "ON" Mounting/Indicator Code: J, K, L LINE OFF LOAD ON FIG. 1 O OFF O ON FIG. 2 FIG. 3 LOAD LINE ON OFF FIG. 4 LOAD LINE O LINE FIG. 5 LOAD LINE ON OFF O LINE FIG. 6 MARKING DETAIL "B" (SEE TABLE) LOAD LINE LINE LOAD LOAD ON O O OFF FIG. 2 FIG. 3 LINE OFF O ON O FIG. FIG.62 ON O OFF FIG. 3 NO ACTUATION ACCESS OPTIONAL HANDLE POSITION "ON" WITH GUARD LINE LOAD OFF O ON FIG. 6 MARKING DETAIL "C" (SEE TABLE) MARKING DETAIL "C" (SEE TABLE) LEL Series - Decision Tables IAL/CEL/LEL Series - Operating Characteristics 150 168 CEL DECISION TABLES 1 First Decision 5 Select Type and Terminal Rated Current Type Description Terminal CEL One handle per unit, UL489A Listed CELH One handle per pole, UL489A Listed Standard screw terminal, no designation required CML Single pole only, one handle per unit mid-trip construction, UL489A Listed CMLH One handle per pole mid-trip construction, UL489A Listed CMLZX Single pole only, one handle per unit, rocker handle w/ RLS aux switch, mid-trip construction, UL489A Listed One handle per unit, flat rocker handle, UL489A Listed CELBX CMLBX Single pole only, one handle per unit, flat rocker handle w/ RLS aux switch, mid-trip construction, UL489A Listed 2 Stud terminals C Clip terminals B Bullet terminals Required value between .050 amps minimum and 125 amps maximum. 6 Sixth Decision Optional Example: CEL 1 - 1REC4 - 51 - 20.0 - A - 01 - V 1 2 3 4 5 6 7 -A Metric thread mounting inserts and terminals -B Barrier -G Snap-in mounting plate adapter with handle guard (ZX, BX and snap-in only) -K 1/4-20 Stud (M6 stud when metric option -A selected) 50A requires -K, >50A do not use -K Snap-in mounting plate adapter -P -T 80VDC, 10000AIC, (required over 50A) -V 125VDC Second Decision -1 Silver 5/16" (.312") bullet Poles -2 Gold 5/16" (.312") bullet 1 Single pole 11 Two pole 111 Three pole 3 K Use three numbers in build (.050 or 1.50 or 100). One handle per unit, rocker handle, UL489A Listed CELZX Fifth Decision Notes: 1. One or more descriptions may be used as required. 2. When this decision is not used, decision 7 may be substituted and U.S. thread will be supplied. 7 Third Decision Internal Configuration -1 Series -1REC4 Series with auxiliary switch .110 quick connect -1RLS4 ** Series with auxiliary switch .110 quick connect, mid-trip only -1REC5 Series with auxiliary switch .187 quick connect -1RS4 ** Alarm switch, .110 quick connect * Only one auxiliary switch is normally supplied on two and three pole units switch is located in the right hand pole (viewed from terminal end). Note, aux switch followed by "R" indicates reverse mount option ** Not available for 125 amp single pole Seventh Decision LEL Toggle Handle Color Selection V = VDE and CCC Approved The shaded areas denote VDE and CCC (if applicable) approval options. This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE or CCC Approved, but other approvals still apply. -01 Black w/ white markings -11 Yellow w/ black markings -21 Red w/ white markings -31 Blue w/ white markings -41 Green w/ white markings -61 Orange w/ black markings -91 White w/ black markings See alternate 7th Decision for ZX and BX Rocker Handles. C = CCC Approved 4 Fourth Decision Frequency and Delay -51 DC short delay -52 DC long delay -53* DC motor start -59 DC 125% instant trip For addition of inertial delay, add an "F" to any delay numeral. Example: -51F *Not available above 100 amps. 149 169 The approval requires the addition of a C at the end of the part number. The unit will not be VDE Approved. T = TUV Approved The approval requires the addition of a T at the end of the part number. The unit will only be TUV EN60947-2 approved with a single pole, 125 amp rating configuration. CELIAL/CEL/LEL Series - Decision Tables Series - Operating Characteristics http://airpax.sensata.com/ http://airpax.sensata.com IAL Series 7 Seventh Decision Rocker Handle Color, Indicator Color and Marking Selection (See Notes) LELZX & LMLZX Rocker Handle (Single Rocker Color) Vertical Mounting Horizontal Mounting On-Off Fig.4 I-O Fig.5 On-Off I-O Fig.6 Unmarked On-Off Fig.1 I-O Fig.2 On-Off I-O Fig.3 N/A -00 -01 -02 -03 -04 -05 -06 N/A -20 -21 -22 -23 -24 -25 -26 Black N/A -40 -41 -42 -43 -44 -45 -46 N/A Black N/A -50 -51 -52 -53 -54 -55 -56 N/A Black N/A -90 -91 -92 -93 -94 -95 -96 Marking Color Indicates: Black N/A White Red N/A White Grey N/A Orange White LELZX & LMLZX Rocker Handle (Dual Rocker Color) ON I Black White White On -A0 -A1 -A2 -A3 -A4 Black Red White On -B0 -B1 -B2 -B3 -B4 Black Green White On -C0 -C1 -C2 -C3 -C4 Black White White Off -F0 -F1 -F2 INDICATION "ON" -F3 Mounting/Indicator -F4 Code: A, B, C Black Red White Off -G0 -G1 -G2 -G3 Black Green White Off -H0 -H1 -H2 -H3 LINE O OFF INDICATING COLOR FIG. 1 -H4 O FIG. 2 ON I -A5 -A6 -B5 -B6 -C5 -C6 O OFF -G5 O OFF OFF ROCKER HANDLE COLOR A INDICATION "OFF" -F5 -F6 Mounting/Indicator Code: F, G, H LINE LOAD ON ON OFF A LINE -G4 LOAD LINE Marking Detail INDICATING COLOR ROCKER HANDLE COLOR FIG. 3 -G6 LINE LOAD -H5 LINE LOAD OFF O Indicating Color ON FIG. 5 FIG. 4 ON O Rocker Handle Color -H6 FIG. 6 Black White White On -J0 -J1 -J2 -J3 Black Red White On -K0 -K1 -K2 -K3 -K4 -K5 -K6 Black Green White On -L0 -L1 -L2 -L3 -L4 -L5 -L6 MARKING (SEE TABLE) -J4 DETAIL "A" -J5 -J6 B LINE LELBX Rocker Handle (Dual Rocker Color) Black White White Off -M0 N/A -M2 -M3 N/A Black Red Red Off -N0 N/A -N2 -N3 N/A Black Green Green Off -P0 N/A -P2 -P3 Black Yellow Yellow Off -R0 N/A -R2 -R3 -M6 -M5 ROCKER -N5HANDLE COLOR -N6 N/A -P5 -P6 N/A -R5 -R6 I ON INDICATION "ON" Mounting/Indicator Code: J, K, L OFF LOAD O FIG. 1 O ON ON FIG. 2 LOAD LINE LOAD LINE OFF ON FIG. 3 LOAD LINE ON O LINE OFF FIG. 5 FIG. 4 C OFF O Notes: A. Bezels of IALBX, IULBX, IELB, IELBX are black. B. Consult factory for other marking options. INDICATING COLOR OFF O FIG. 6 MARKING DETAIL "B" (SEE TABLE) LINE INDICATING COLOR INDICATING COLOR ON I O OFF O OFF ROCKER HANDLE COLOR OFF O INDICATING COLOR LINE INDICATION "ON" Mounting/Indicator Code: A, B, C INDICATION "OFF" Mounting/Indicator Code: F, G, H LOAD ON OFF FIG. 1 ON O FIG. 2 O OFF FIG. 3 LOAD LINE LINE OFF ON FIG. 4 LOAD LINE OFF O O FIG. 5 LOAD ON FIG. 6 MARKING DETAIL "A" (SEE TABLE) http://airpax.sensata.com/ Area reserved for amperage marking. LINE HANDLE POSITION "OFF" INDICATION "OFF" WITH GUARD Mounting/Indicator Code: M, N, P, R INDICATION "OFF" Mounting/Indicator Code: M, N, P, R INDICATION "ON" Mounting/Indicator Code: J, K, L LINE OFF LOAD ON FIG. 1 O OFF O ON FIG. 2 FIG. 3 LOAD LINE ON OFF FIG. 4 LOAD LINE O LINE LINE ROCKER HANDLE COLOR I ON FIG. 5 LOAD LINE ON LOAD LOAD OFF O ROCKER HANDLE COLOR ON I FIG. 6 MARKING DETAIL "B" (SEE TABLE) LINE O LINE FIG. 2 ON LINE LOAD ON O OFF O FIG.FIG. 3 2 OFF O O ON OFF FIG. FIG. 6 3 NO ACTUATION ACCESS OPTIONAL HANDLE POSITION "ON" WITH GUARD LINE LOAD OFF O ON FIG. 6 MARKING "C" (SEE TABLE) MARKING DETAILDETAIL "C" (SEE TABLE) CEL Series - Decision Tables IAL/CEL/LEL Series - Operating Characteristics 150 170 LELHP DECISION TABLES V = VDE Approved First Decision Select Type with Stud Terminals LELPK One handle per unit LMLPK One handle per unit, mid-trip LELZXPK One ZX rocker handle per unit (integral mounting) LMLZXPK One ZX rocker handle per unit, mid-trip (integral mounting) LELBXPK LMLBXPK One BX rocker handle per unit (integral mounting) One BX rocker handle per unit, mid-trip (integral mounting) LELHPK One handle per pole LMLHPK One handle per pole, mid-trip The shaded areas denote VDE approval options. This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE approved, but other approvals still apply. Example: LELHPK 11 - 1REC4 - 51 - 125. - A - 01 - V 1. One toggle handle per unit on 125A to 150A units (2-parallel pole) 2. 175A to 200A (3-parallel pole) requires handle in each pole, "H" selection 1 2 3 4 5 6 7 Second Decision Poles 11 Two pole (up to 150 amps) 111 Three pole (160 to 200 amps) Third Decision Internal Configuration Fifth Decision Frequency and Delay Rated Current (Amps) -01 Black w/ white markings DC 135% short delay (160 to 200 amp) 130. -11 Yellow w/ black markings DC 125% long delay (125 to 150 amp) 135. -21 Red w/ white markings 150. -31 Blue w/ white markings DC 125% instant trip (125 to 150 amp) 175. -41 Green w/ white markings DC 135% instant trip (160 to 200 amp) 200. -61 Orange w/ black markings Additional ratings available. -91 White w/ black markings -1REC4 Series with auxiliary switch .110 quick connect -1REG4 Series, aux switch (gold contacts) .110 quick connect -59 Series with alarm aux switch .110 quick connect, mid-trip only For addition of intertial delay, add an "F" to any delay option. Example: - 59 becomes -59F -1RLSG4 Series, alarm aux switch (gold contacts), .110 quick connect, mid-trip only 6 DC 135% long delay (160 to 200 amp) Sixth Decision Series with alarm aux switch .110 quick connect -A Metric thread mounting inserts and terminals -1REC5 Series with aux switch .187 quick connect -G Snap-in mounting plate adapter with handle guard (ZX, BX & snap-in only) -X Handle guard with no actuate off feature (BX only, no mid-trip) Series with alarm aux switch .187 quick connect, mid-trip only -P Snap-in mounting plate adapter -1RS4 Series with alarm aux switch .187 quick connect -1RS5 Series with alarm aux switch .187 quick connect, mid-trip See LEL alternative 7th decision for ZX & BX rocker handles Optional (leave entry blank if none apply) -1RS4 -1RLS5 Toggle Handle Color 125. Series -52 7 Seventh Decision DC 125% short delay (125 to 150 amp) -1 -1RLS4 149 171 -51 Fourth Decision Notes: 1. One or more descriptions may be used as required. 2. When this decision is not used, decision 7 may be substituted and U.S. thread will be supplied. LELHP Series - Decision IAL/CEL/LEL Series Tables - Operating Characteristics http://airpax.sensata.com/ http://airpax.sensata.com IAL Series CELHP DECISION TABLES V = VDE Approved First Decision Terminal Select Type CELP One toggle handle per unit CELHP One toggle handle per pole CMLHP One toggle handle per pole, mid-trip construction CELZXP One rocker handle per unit CELBXP One flat rocker handle per unit The shaded areas denote VDE approval options. This approval requires the addition of a V at the end of the part number. The V will be added to any part number formed entirely from shaded decisions. If non-shaded areas are selected, the unit will not be VDE approved, but other approvals still apply. Standard screw terminal, no designation required K Stud terminals C Clip terminals B Bullet terminals Example: 1. One toggle handle per unit is available only on 101A to 200A (two parallel pole construction) 2. 201A to 250A (three parallel pole constructions) require handles in each pole, "H" version first decision 3. Unit supplied with bullet terminals will not have buss bar installed, unless requested, buss bar supplied standard to 150A only. 4. One handle per unit is available for 100A to 200A (two parallel pole constructions) and 201A to 250A (three pole constructions) (ZX & BX versions only) 5. 400 amps available with toggle handes only CELHPK 11 - 1REC4 - 51 - 125. - A - 01 - V 1 2 3 4 5 6 7 Second Decision Poles 11 Two pole (up to 150 amps) 111 Three pole (160 to 250 amps) 1111 Four pole (400 amps) 7 Seventh Decision Fourth Decision Fifth Decision Third Decision Frequency and Delay Rated Current (Amps) Internal Configuration DC 125% short delay (101 to 150 amp) 125. -01 Black w/ white markings DC 135% short delay (160 to 250 amp) 130. -11 Yellow w/ black markings DC 125% long delay (101 to 150 amp) 135. -21 Red w/ white markings DC 135% long delay (160 to 250 amp) 150. -31 Blue w/ white markings DC 125% motor start (101 to 150 amp) 175. -41 Green w/ white markings DC 135% motor start (160 to 250 amp) 200. -61 Orange w/ black markings DC 125% instant trip (101 to 150 amp) 400. -91 White w/ black markings DC 135% instant trip (160 to 250 amp) Additional ratings available. -0 Switch only -1 Series -1REC4 Series with auxiliary switch .110 quick connect -1RLS4 * Series with alarm aux. switch .110 quick connect, mid-trip only -1RS4 * -1REC5 Series with alarm aux. switch .110 quick connect Series with auxiliary switch .187 quick connect -51 -52 -53 -59 6 -1RLS5 * Series with alarm aux. switch .187 quick connect, mid-trip only -1RS4 * Series with alarm aux. switch .187 quick connect 1. Only one auxiliary switch is normally supplied on two and three pole units. Switch is located in the right hand pole (viewed from terminal end panel mount position). 2. When more than one aux. switch is required, change the 1 (of the 1REC4) to 2 or 3. If switches are mixed, then use "2R" or 3R". * Not available at 400 amps http://airpax.sensata.com/ Toggle Handle Color See LEL alternative 7th decision for ZX & BX rocker handles Sixth Decision Optional (leave entry blank if none apply) -A Metric thread mounting inserts and terminals -B Barrier -G Snap-in mounting plate adapter with handle guard (ZX, BX & snap-in only) -X Handle guard with no actuate off feature (BX only, no mid-trip) -1 Silver 5/16" (.312") bullet -2 Gold 5/16" (.312") bullet Notes: 1. One or more descriptions may be used as required. 2. When this decision is not used, decision 7 may be substituted and U.S. thread will be supplied. LELHP Series - Decision Tables IAL/CEL/LEL Series - Operating Characteristics 150 172