9 SYSMAC Remote Master Modules C500-RM 01 Wired and Fiber-optic Remote I/O Systems Match Your Distance Needs 1 Wired remote I/O systems offer up to 200 m maximum distance using shielded twisted pair wire, Belden #9271 or equivalent 1 Fiber-optic remote I/O systems prevent electrical noise from fouling longdistance communication signals 1 Transmission distance with fiber-optic cables depends on core material: 20 m for all plastic; 200 m for plastic clad; 3 km for quartz crystal core 1 Master modules connect to slave racks or remote I/O relay or transistor blocks Ordering Information 3 WIRED REMOTE I/O SYSTEM Classification Description Specification Part number Remote master For CV/CVM1 controllers Use up to 8 masters per CPU C500-RM201 Transmission line Shielded twisted pair cable Belden #9271 or equivalent Commercially available 3 FIBER-OPTIC REMOTE I/O SYSTEM Classification Description Specification Use up to 8 masters per CPU Part number Remote master for CV/CVM1 controllers t ll Plastic core fibers Transmission media APF (all plastic) fiber-optic cable (user must assemble connectors) 20 m (65 ft), without connectors B500-PF212 Connectors, brown (includes 2) For cables 0 to 10 m length 3G5A2-CO001 Connectors, black (includes 2) For cables 8 to 20 m length 3G5A2-CO002 HPCF ((plastic clad)) fiber-optic cable,, i d / td indoor/outdoor use (user must assemble connectors) 50 m (164 ft) FCS-HCR-LB-501 100 m (328 ft) FCS-HCR-LB-102 500 m (1640 ft) FCS-HCR-LB-502 3G2A5-RM001-PEV1 3G2A5-RM001-EV1 Glass core fibers 1 km (3280 ft) FCS-HCR-LB-103 Zipcord style, orange, without connectors 50 m (164 ft) FCS-HCR-CO-501 Connectors for SYSMAC BUS Order two, one for each end S3200-COCH82 Termination kit for HPCF cable ------ FCS-CAK6230-US AGF (quartz crystal) fiber-optic cable ------ Commercially available 3 REMOTE SLAVE RACKS For part numbers and configuration information, refer to the CV/CVM1 Programmable Controller Catalog or C-Series Wired Remote I/O Manual (W120) or C-Series Fiber-optic Remote IO Manual (W136). C500-RM 01 C500-RM 01 Specifications 3 COMMUNICATIONS SPECIFICATIONS Omron PLC model CVM1-CPU01, CV500 Communications method Half-duplex Coding method Manchester coding method Connection method RS-485 Communications baud rate 187.5 kbps Max. masters per PLC 4 (fiber and wired) 8 (fiber and wired) Max. remote expansion racks per master 8 16 Max. I/O points (words) per master 512 (32 words) 512 (32 words) Max. points per PLC 512 1024 Communications cable C500-RM201: 2-conductor cable: Belden #9271 or VCTF (JIS L3306) 3G2A5-RM001-PEV1: Fiber-optic cable: all plastic or hard plastic clad fiber media 3G2A5-RM001-EV1: Fiber-optic cable: quartz glass core media Communications di t distance Wired Belden #9271 or VCTF cable: 200 m (656 ft) total distance Fiber-optic All plastic fiber (APF): 20 m (65.6 ft) Hard plastic fiber (HPCF): 200 m (656 ft) Quartz crystal fiber (AGF): 3 km (1.86 mile) 800 m (2640 ft) between nodes, 10 km (6.2 miles) total distance with repeaters Error control checks CVM1-CPU11, CV1000, CV2000 Manchester code check, frame length check, and parity check 3 MODULE SPECIFICATIONS Ports 1 port Current consumption C500-RM201 wired master: 0.3 A 3G2A5-RM001-(P)EV1 fiber-optic master: 0.7 A Module placement Install Remote I/O Master modules in the CPU Rack, CPU Expansion rack or a Local Expansion Rack Approved standards UL 508 (E95399), CSA C22.2 No. 142 (LR51460) Note: For detailed specifications on wired or fiber-optic SYSMAC BUS systems, refer to the following manuals: W120 C-Series Wired Remote I/O W136 C-Series Fiber-optic Remote I/O Dimensions Unit: mm (inch) 3G2A5-RM001-(P)EV1 C500-RM201 RM201 RM001 XFER ERR T/R ERR TEST OK TEST GOOD END RS CHK ENDSTA CHECK LINE ERROR TEST 250 (9.84) RS485 35 (1.38) 2 92 (3.62) 104 (4.09) Note: Refer to the CV/CVM1 Operation Manual for details on the dimensions when the Master Module is installed in the PLC Backplane. C500-RM 01 C500-RM 01 NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4. 9 OMRON ELECTRONICS, INC. OMRON CANADA, INC. One East Commerce Drive Schaumburg, IL 60173 885 Milner Avenue Scarborough, Ontario M1B 5V8 1-800-55-OMRON 416-286-6465 Cat. No. GC RIO-1 04/00 Specifications subject to change without notice. Printed in U.S.A.