POWER
LCM600
600 Watt Bulk Front End
Total Power: 600 W
# of Outputs: Single
Outputs: 12 to 60 V
Optional 5.0 V standby
SPECIAL FEATURES
600 W output power
Low Cost
2.4” x 4.5” x 7.5”
7.41 W/cu-in
Industrial/Medical safety
-40 °C to 70 °C with derating
Optional 5 V @ 2 A Housekeeping
High Efciency: 89% typical
Variable speed “Smart Fans”
DSP controlled front end
Conformal coat option
± 20% adjustment range
Margin programming
OR-ing FET
Terminal block input option
COMPLIANCE
EMI Class B
EN61000 Immunity
SAFETY
UL 60950-1
1598/1433
60601-1
CSA 60950-1
VDE 60950-1
60601
China CCC
CB Scheme Report/Cert
Electrical Specications
Input
Input ra nge: 85 - 264 Vac (Operating)
115/230 Vac (Nominal) Input through standard IEC connector/
TERMINAL BLOCK
Frequency: 47 - 440 Hz, Nominal 50/60
Input fusing: Internal 10 A fuses, both lines fused
Inrush current: ≤ 25 A peak, either hot or cold start
Power factor: 0.99 typical, meets EN61000-3-2
Harmonics: Meets IEC 1000-3-2 requirements
Input current: 8 A RMS max input current, at 100 Vac
Hold up time: 20 ms minimum for Main O/P, at full rated load
Efficiency: > 89% at full load
Leakage current: < 0.3 mA at 264 Vac
ON/OFF power switch: N/A
Power line transient: MOV directly after the fuse
Isolation: Isolation: PRI-Chassis 2500 Vdc Basic
PRI-SEC 4000 VAC Reinforced 2xMOPP
SEC-Chassis 500 Vdc
LCM600Q Efciency Without the 5 Vsb
76.00
78.00
80.00
82.00
84.00
86.00
88.00
90.00
92.00
25 50 75 100
Loading %
Efciency %
100 Vac
230 Vac
Data Sheet
LCM600 Data Sheet
Environmental Specications
Operating temperature: -40 °C to +70 °C, linear derating to 50% from 50 °C to 70 °C
Storage temperature: -40 °C to +85 °C
Humidity: 20 to 90%, non-condensing. Operating. Conformal coat option available
Fan noise: < 45 dBA, 80% load at 30 °C “-N” Low Noise Option < 35 dBA, 80% Load at 30 °C
Altitude: Operating - 16,404.2 feet
Storage - 30,000 feet
Shock: MIL-STD-810F 516.5, Procedure I, VI. Storage
Vibration: MIL-STD-810F 514.5, Cat. 4, 10. Storage
Electrical Specications
Output
Output rating: See ordering information table 85 - 264 Vac
Set point: ± 0.5% 85 - 264 Vac
Total regulation range: Main output ± 2%
5 Vsb ± 1%
Combined line/load/transient when measured at output
terminal
Rated load: 600 W maximum Derate linear to 50% from 50 °C to 70 °C
Minimum load: Main output @ 0.0 A
5 Vsb @ 0.0 A
No loss of regulation
Output noise (PARD): 1% max p-p
50 mV max p-p
Main output
5 Vsb output
Measured with a 0.1 μF Ceramic and 10 μF Tantalum
Capacitor on any output, 20 MHz
Output voltage overshoot: No overshoot/undershoot outside the regulation band during
on or off cycle
Transient response: < 300 µSec 50% load step @ 1 A/µs
Step load valid between 10% to 100% of output rating
Recovery time to within 1% of set point at onset of transient
Max units in parallel: Up to 10
Short circuit protection: Protected, no damage to occur Bounce mode
Remote sense: Compensation up to 500 mV
Output isolation: Standard per safety requirements
Forced load sharing: To within 10% of all shared outputs Analog sharing control
Overload protection (OCP): 105% to 125%
120% to 170%
Main output
5 Vsb output
Overvoltage protection (OVP): 125% to 145%
110% to 125%
12 V output
5 Vsb output
Overtemp protection: 10 - 15 °C above safe operating area Both PFC and output converter monitored
Fan Fault Protection: For-N option only. Will shutdown output and DC_OK
Ordering Information
Model
Number* Output
Nominal Output
Voltage Set Point
Set Point
Tolerance Adjustment Range
Current Output Ripple
P/P (0-50 ˚C)
Max Continuous
Power
Combined Line/
Load Regulation
Min Max
LCM600L 12 V 12 V ±0.5% 9.6 - 14.4 V 0 A 52 A 120 mV 600 W 2%
LCM600N 15 V 15 V ±0.5% 12.0 - 19.5 V 0 A 44 A 150 mV 600 W 2%
LCM600Q 24 V 24 V ±0.5% 19.2 - 28.8 V 0 A 27 A 240 mV 600 W 2%
LCM600U 36 V 36 V ±0.5% 28.8 - 43.2 V 0 A 16.7 A 240 mV 600 W 2%
LCM600W 48 V 48 V ±0.5% 38.4 - 57.6 V 0 A 14 A 280 mV 600 W 2%
*Note: Add “-T” for terminal block instead of IEC input
Add “-N” for low noise model on 12 V or 24 V models
Add “-4” for 5 V Standby output
Add “-A” will be automatically added to all orders to denote new Aesthetics style chassis unless otherwise specied
Example: a 24 V with terminal block, low noise and standby with new Aesthetics would be LCM600Q-T-N-4-A
LCM600 Data Sheet
Pin Assignment
Signals Name Description Pin Number(s)
+Vout Power rail SK4
GND Power GND SK5
Signals Name Description SK2 Pin Number
A2 EEPROM Address 1
-VPROG Return connection of external supply for Margin Programming 2
A1 EEPROM Address 3
-Vsense Remote Sense Return 4
ISHARE Load share voltage 5
A0 EEPROM Address 6
SDA1 Serial Data Signal (I2C) 7
+VPROG Positive connection of external supply for Margin Programming 8
SCL1 Serial Clock Signal (I2C) 9
+Vsense Remote Sense Positive 10
5VSB 5V standby 11
GND 5V standby Return 12
5VSB 5V standby 13
G_DCOK_C Global DCOK Collector 14
GPIOA6 EEPROM Write Protect 15
G_DCOK_E Global DCOK Emitter (GND) 16
GND Return Ground for output signal and I2C communication 17
G_ACOK_C Global ACOK Collector 18
INH_EN Turn Off Main Output 19
G_ACOK_E Global ACOK Emitter (GND) 20
Note: Mating connector for SK2 is LANDWIN CI0120P1HD0-LF
LED INDICATORS
2 provided are clearly visible up to a 45 degree offset from vertical with office environment ambient lighting. The status is reflected in the
indicator color.
The DC_OK LED LED is bicolor. It shall light green if the DC output is within specification, and amber if the output falls out of specification.
The AC_OK LED LED is green if the AC is within specification and off when out of specification. Note: With 5 V standby, Amber also
indicates that PSU is in standby mode/output off.
CONTROL SIGNALS
AC_OK Open collector 0.5 V maximum at 10 mA. Both emitter and collector access provided.
DC_OK Open collector 0.5 V maximum at 10 mA. Both emitter and collector access provided.
DC_OK will de-assert when output is loss due to OCP, OVP, OTP, or Fan Fault (for -N option).
PS_INHIBIT/ENABLE Signal 0.0 - 0.5 V contact closure, output OFF
Signal Output Signal Connectors (SK2)
SK2 Mating Connector: JST Part Number PHDR-20VS;
Contact Pins: JST Part Number SPHD-001T-P0.5
LCM600 Data Sheet
Ordering Information
LCMXXXXY - A - B - C - ###
Case Size Input Termination Acoustic Noise Option Codes Hardware Code
1-Phase input where XXXX =
600 = 2.4” x 4.5” x 7.5”, 600W Blank = IEC connector Blank = Standard Blank = No Options Factory Assigned for
Modiefied standards
T = Terminal Block N = Low Noise Fan 1 = Conformal Coat
Voltage Code Y = 4 = 5 V Standby
Code 5 = Opt 1 + 4
L 12
N 15
Q 24
U 36
W 48
41
(2X)22 0.5
(2X)47 0.5
62 1
(2X)6 0.5
(2X)182.5 0.5
(2X)10 0.5
(2X)177.5 0.5
11.150.5
17.65 0.5
(2X) 94.45 0.5
50(2X)10.6
114.3 0.5
(18.5) 190.5 0.5
50
(212.2 ref)
16.8
9.5
9.5
SCREW-MC PHILIP PAN
WITH WASHER M4x8
SEE DETAIL B
DETAIL B
AC INLET VERSION
INPUT TERMINAL BLOCK
SEE NOTE 8
LED (DC/OK FAIL)
LED (AC OK)
SK2 SIGNAL
CONNECTOR - 20WAY
SK4 & SK5
(8X) MOUNTING LOCATIONS
BOTH SIDES
M4X0.7P THREAD
SEE NOTE 7
BRAND LOGO
SEE DETAIL A
SEE DETAIL C (TRIMPOT LOCATION)
(4X) MOUNTING LOCATIONS
M4X0.7P THREAD
SEE NOTE 7
SCALE 1.500
DETAIL A
GROUND
NEUTRAL
LIVE
DETAIL C
(TRIMPOT LOCATION)
VOLTAGE ADJUSTMENT:
CLOCKWISE - INCREASE VOLTAGE
COUNTER CLOCKWISE - DECREASE VOLTAGE
Mechanical Drawings
NOTE: OPTIONAL BARRIER STRIP OUTPUT TERMINAL AVAILABLE
OPTIONAL MOLEX TYPE CONNECTOR OUTPUT AVAILABLE
New Mechanical Reference Drawing:
Weight: 2.84 lbs (1.29 Kg)
MOUNTING LOCATIONS SCREW
PENETRATION DEPTH IS 4.6 mm MAX.
RECOMMENDED SCREW TORQUE:
M3.5 x 0.6P = 6 - 8kgf-cm
M4.0 x 0.7P = 8 - 10kgf-cm
Note 7 RECOMMENDED SCREW TORQUE:
M3.5x0.6P = 6-8kgf-cm
M4.0x0.7P = 8-10kfg-cm
Note 8 INPUT: TERMINAL BLOCK TYPE.
M3.5 SCREW TORQUE VALUE OF 12kgf-cm
USING WIRE GAUGE 22-19 (9.5mm CENTERS)
LCM600 Data Sheet
Mechanical Drawings – Terminal Block Input
Old Mechanical Reference Drawing:
Weight: 2.84 lbs (1.29 Kg)
Note 7 RECOMMENDED SCREW TORQUE:
M3.5x0.6P = 6-8kgf-cm
M4.0x0.7P = 8-10kfg-cm
190,5
0,5
18,5 REF
16,8
9,5
9,5
12,8
32,8
114,3 0,5
50
(2X)10,6
15,75
(2X)22 0,5
40,2
(2X)47 0,5
61 0,5
(2X)6 0,5
(2X)182,5 0,5
17,65 0,5
(2X)94,45 0,5
11,15 0,5
(2X)10 0,5
(2X)177,5 0,5
LED (AC OK)
LED (DC/OK FAIL)
INPUT TERMINAL BLOCK
SEE NOTE 8
POS - SK4
NEG - SK5
SK2 SIGNAL CONNECTOR - 20WAY
SCREW-MC PHILIP PAN
WITH EXT-T WASHER
M3.5 x P0.6 x 6
(8X) MOUNTING LOCATIONS
BOTH SIDES
M4X0.7P THREAD
SEE NOTE 7
(4X) MOUNTING LOCATIONS
M4X0.7P THREAD
SEE NOTE 7
PROVISION FOR FUTURE
LABEL REQUIREMENTS
SEE DETAIL A
PRODUCT LABEL
SEE DETAIL B (TRIMPOT LOCATION)
SCALE 8:5
DETAIL A
GROUND
NUETRAL
LIVE
DETAIL B
(TRIMPOT LOCATION)
VOLTAGE ADJUSTMENT:
CLOCKWISE - INCREASE VOLTAGE
COUNTER CLOCKWISE - DECREASE VOLTAGE
LCM600 Data Sheet
Low Noise VS Non-Low Noise LCM600 Model
30.0
32.0
34.0
36.0
38.0
40.0
42.0
44.0
46.0
48.0
50.0
52.0
54.0
56.0
58.0
60.0
02.5 57.5 10 12.5 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 40 42.5 45 47.5 50
25 Deg Ambient
NON-Low noise version
Low noise version
LOAD (A)
NOISE (dBA
30.0
32.0
34.0
36.0
38.0
40.0
42.0
44.0
46.0
48.0
50.0
52.0
54.0
56.0
58.0
60.0
02.5 57.5 10 12.51517.52022.52527.53032.53537.54042.54547.
55
0
50 Deg Ambient
NON-Low noise version
Low noise version
LOAD (A)
NOISE (dBA
NON-Low noise version
LOAD (A)
25˚C ambient 50˚C ambient
fan (V) RPM noise (dbA) fan (V) RPM noise (dbA)
0 6.254 3558.0 40.9 6.228 3460.9 39.9
2.5 6.257 3559.8 41.0 6.228 3460.9 39.9
5 6.262 3562.0 41.0 6.230 3494.3 40.1
7.5 6.263 3562.0 41.0 6.242 3526.6 40.1
10 6.242 3528.9 40.5 6.242 3526.6 40.1
12.5 6.251 3530.9 40.6 6.237 3515.6 40.4
15 6.251 3538.3 40.7 6.229 3504.9 40.2
17.5 6.226 3538.2 40.7 6.205 3482.8 39.4
20 6.223 3541.0 40.7 6.217 3490.1 40.0
22.5 6.242 3545.1 40.8 6.227 3493.8 40.1
25 6.253 3553.9 40.9 6.234 3504.3 40.2
27.5 6.254 3564.1 41.0 6.212 3501.7 40.2
30 6.253 3552.2 40.9 6.642 3787.4 44.1
32.5 6.264 3559.7 41.0 7.893 4652.3 48.0
35 6.262 3559.6 41.0 9.153 5463.4 50.0
37.5 6.262 3560.8 41.0 11.035 6600.2 52.0
40 6.262 3559.8 41.0 11.605 6993.9 53.2
42.5 7.637 4521.2 47.8 11.608 6997.2 53.2
45 8.919 5362.2 49.3 11.608 6997.2 53.2
47.5 10.068 6139.5 51.0 11.608 6997.2 53.2
50 11.362 6893.4 52.8 11.608 6997.2 53.2
Low noise version
PWM
25˚C ambient 50˚C ambient
LOAD (A) RPM noise (dbA) LOAD (A) RPM noise (dbA)
0% 0 3028 35.2 0 3180 36.0
5% 2.5 3028 35.2 2.5 3300 36.7
10% 5 3028 35.2 5 3300 36.7
15% 7.5 3060 35.4 7.5 3360 37.0
20% 10 3028 35.2 10 3360 37.0
25% 12.5 3028 35.2 12.5 3360 37.0
30% 15 3060 35.4 15 3360 37.0
35% 17.5 3060 35.4 17.5 3388 37.2
40% 20 3028 35.2 20 3388 37.2
45% 22.5 3028 35.2 22.5 3540 38.0
50% 25 3060 35.4 25 3840 39.2
55% 27.5 3028 35.2 27.5 4104 40.2
60% 30 3028 35.2 30 4408 41.4
65% 32.5 3060 35.4 32.5 4736 42.7
70% 35 3060 35.4 35 5184 44.5
75% 37.5 3060 35.4 37.5 5728 46.4
80% 40 3060 35.4 40 6688 49.5
85% 42.5 3420 37.4 42.5 7560 51.8
90% 45 3868 39.3 45 7584 51.9
95% 47.5 4376 41.3 47.5 7584 51.9
100% 50 5040 43.9 50 7584 51.9
LCM600 Data Sheet
WORLDWIDE OFFICES
Americas
2900 S.Diablo Way
Tempe, AZ 85282
USA
+1 888 412 7832
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
+44 (0) 1384 842 211
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
+852 2176 3333
For more information: www.artesyn.com/power
For support: productsupport.ep@artesyn.com
www.artesyn.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Artesyn
Embedded Technologies assumes no responsibility, and disclaims all liability for damages resulting from use
of this information or for any errors or omissions. Artesyn Embedded Technologies, Artesyn and the Artesyn
Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies, Inc.
All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective
owners. © 2014 Artesyn Embedded Technologies, Inc. LCM600 DS Rev. 01-14-15
Accessories
Miscellaneous Specications
BURN-IN
100% Burn-in at 45 °C, at 80 - 90 % load. Duration of burn-in determined by Quality Assurance Procedures.
MTBF
The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specification @ 25 °C and 40 °C, ambient, at full
load. With the power supply installed in a system in a 25 °C ambient environment and operating at full load, capacitor life shall be 10 years,
minimum for ALL electrolytic capacitors contained within this power supply. The power supply shall demonstrate a MTBF level of
> 500,000 hours.
QUALITY ASSURANCE
Full QAV testing shall be conducted in accordance with Artesyn Embedded Technologies Standards with reports available upon request.
WARRANTY
Artesyn Embedded Technologies shall warrant the power supply to be free of defects in materials and workmanship for a minimum period
of three years from the date of shipment, when operated within specifications. The warranty shall be fully transferable to the end owner of
the equipment powered by the supply.
Order kit part number 73-788-001 for control connector interface with .3m wires attached
Order kit part number 73-788-002 for control connector interface with unloaded housing and 20 pins
PIN 20
PIN 2
PIN 19
PIN 1
PIN 3
300 ± 5 mm
PIN 20
PIN 2
PIN 19
PIN 1
PIN 3