https://www.phoenixcontact.com/us/products/2320335
07/15/2016Page2/5
Energy storage-UPS-BAT/VRLA/24DC/38AH-2320335
Technical data
Output data
Nominal output voltage 24 V DC
Output current Imax 45 A
Connection in series No
Output fuse 2x 25 A ATOF 32V
General
IQ technology Yes
Disposal
Used batteries must not be thrown away with household waste, they
should instead be disposed of in accordance with applicable national
regulations. They can also be returned to Phoenix Contact or the
manufacturer.
Net weight 26 kg
Memory medium Lead rechargeable battery module
Protection class III
Mounting position Horizontally, on a mounting plate
Standards and Regulations
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Connection in acc. with standard CUL
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
VdS approval G 100002
Vibration (operation) < 15 Hz, amplitude ±2.5 mm, 15 - 150 Hz, 2.3g/2.3g according to IEC
60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Drawings
Block diagram
DC 12V
DC 12V
Battery
DC 24V
J
m
C