Industrial Power Supplies TIS SERIES 75-600 Watts CE Marked - LVD & EMC * DIN Rail Mounting * Rugged for Industrial Use * Regulated and Low Ripple * High Efficiency * Optional Built-In UPS Module * Wall Mount Bracket Available Specification (All specifications are typical at nominal input, full load and +25 C unless otherwise stated) Input Voltage * 93-132 V/187-264 V AC User selectable 187-264 V AC only TIS500 model Input Frequency * 47-63 Hz Inrush Current * See Table Input Current * See Table Earth Leakage Current * 300 A typ. 75 W, 150 W & 600 W units, 600 A typ. 300 W units Hold Up Time * 30 ms minimum Output Voltage * See Table Output Adjustment * 12 V models: 12-14 V DC, 24 V models: 24-28 V DC, 48 V models: 48-52 V DC Line Regulation * 0.2% Load Regulation * 1% 75 W and 150 W models, 0.5% 300 W and 600 W models for load variation between 10 and 90% Ripple & Noise * Overload Protection * <50 mV p-p 20 MHz band width 110% typically into constant current mode Overvoltage Protection * At 140% V out nominal Temperature Coefficient * 150 ppm max Efficiency * >85% Operating Temperature * -25 C to +70 C derate at 2%/C above +50 C Storage Temperature * -25 C to +85 C Relative Humidity * 95% Isolation * 3000 V AC input to output, 1 minute * 2000 V AC input to case, 1 minute * 500 V AC output to case, 1 minute Safety Class * Class 1 (IEC536) EMI/RFI * EN55022, EN555011 Class B conducted EMI Safety Approvals * EN60950, IEC950, UL1950 (File No. E181381) Immunity * To EN61000-4 sections -2, -3, -4, -6 and -8 MTBF * 75 W & 150 W >750,000hrs, 300 W & 600 W >370,000 hrs to MIL-HBK217F Switching Frequency * 67 kHz (100kHz TIS 75 W models) Tel: +44 (0)118 984 5515 UK Tel: +49 (0)700 9977 1000 D Output Voltage & Current Ratings Output Voltage nom. 12 V DC 24 V DC 48 V DC 24 V DC 48 V DC 24 V DC 48 V DC 24 V DC 24 V DC 48 V DC Output Current max. 6.0 A 3.0 A 1.5 A 6.0 A 3.0 A 12.0 A 6.0 A 20.0 A 24.0 A 12.0 A Input Current @ Full Load 115 V AC 230 V AC 1.2 A 0.6 A 1.2 A 0.6 A 1.2 A 0.6 A 2.4 A 1.2 A 2.4 A 1.2 A 4.6 A 2.4 A 4.6 A 2.4 A 2.4 A 9.5 A 4.7 A 9.5 A 4.7 A Inrush Current Max. 115 V AC 230 V AC 16.5 A 33.0 A 16.5 A 33.0 A 16.5 A 33.0 A 35.0 A 70.0 A 35.0 A 70.0 A 35.0 A 70.0 A 35.0 A 70.0 A 70.0 A 70.0 A 80.0 A 70.0 A 80.0 A Model Number TIS75-112 TIS75-124 TIS75-148 TIS150-124 TIS150-148 TIS300-124 TIS300-148 TIS500-124 TIS600-124 TIS600-148 Models With Built-In Redundancy Module - Option RED Output Power max. 300 W 300 W 600 W 600 W Output Voltage nom. 24 V DC 48 V DC 24 V DC 48 V DC Output Current max. 12 A 6A 24 A 12 A Input Current @ Full Load 115 V AC 230 V AC 4.6 A 2.4 A 4.6 A 2.4 A 9.5 A 4.7 A 9.5 A 4.7 A Inrush Current Max. 115 V AC 230 V AC 35.0 A 70.0 A 35.0 A 70.0 A 70.0 A 80.0 A 70.0 A 80.0 A Model Number TIS300-124RED TIS300-148RED TIS600-124RED TIS600-148RED DIN-Rail Power Output Power max. 75 W 75 W 75 W 150 W 150 W 300 W 300 W 500 W 600 W 600 W Models With Built-In DC UPS Module - Option UDS Output Voltage nom. 24 V DC 24 V DC Output Current max. 12 A 24 A Input Current @ Full Load 115 V AC 230 V AC 4.6 A 2.4 A 9.5 A 4.7 A Inrush Current Max. 115 V AC 230 V AC 35.0 A 70.0 A 70.0 A 80.0 A Model Number TIS300-124UDS TIS600-124UDS Models With Built-In Signals Module - Option SIG Output Power max. 150 W 150 W 300 W 300 W 600 W 600 W Output Voltage nom. 24 V DC 48 V DC 24 V DC 48 V DC 24 V DC 48 V DC Output Current max. 6A 3A 12 A 6A 24 A 12 A Input Current @ Full Load 115 V AC 230 V AC 2.4 A 1.2 A 2.4 A 1.2 A 4.6 A 2.4 A 4.6 A 2.4 A 9.5 A 4.7 A 9.5 A 4.7 A Inrush Current Max. 115 V AC 230 V AC 35.0 A 70.0 A 35.0 A 70.0 A 35.0 A 70.0 A 35.0 A 70.0 A 70.0 A 80.0 A 70.0 A 80.0 A Model Number TIS150-124SIG TIS150-148SIG TIS300-124SIG TIS300-148SIG TIS600-124SIG TIS600-148SIG NOTES: 1. DC Auxiliary rails available for TIS300 - maximum power 15 watts, and TIS600 - maximum power 25 watts. Call technical sales for details. Industrial Power Supplies 75-600 Watts TIS Series Output Power max. 300 W 600 W Redundancy Module - Option RED With this option a parallel operation of up to five units is possible. Decoupling diodes and current share lines allow to build true N + 1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure. This option is available as standard for TIS300 and TIS600 models. A combination with other options is not possible. For this option standard output connector is not used. www.xpplc.com Tel: +33 (0)820 801 401 F Tel: +41 (0)56 483 34 00 CH Uninterruptible DC-System - Option UDS Models TIS300124-UDS and TIS600124-UDS are equipped to build an uninterruptible DC-UPS system. Additional to the standard 24 V DC output power supplies they provide a professional battery management system to charge and monitor an external battery. In case of a power failure the battery is switched automatically and without any interruption to the DC-output. If mains power is available again the battery is switched off. The hold-up time is limited only by battery capacity and load. Charge current and voltage can be adjusted to values as required by battery type. Power fail and low battery alarm signals are available via two independent relay contacts. During normal operation the battery status is monitored by periodically loading the battery for short time. If a cell resistance is high there is a relay alarm available. The battery is fully protected under any operational conditions. The power supply is short circuit protected even with battery-backup operation, however for safety reasons the battery should be fused with a fast blow fuse. Battery mode can be activated by connection of Con1-Pin 7 and 8. Complete external battery modules (7 Ah standard) are available on request - Contact Technical Sales DC-UPS-module TECHNICAL DATA UDS TIS300-124UDS TIS600-124UDS Adjustment range of charging current 0.15 ... 1.5 A 0.25 ... 2.5 A Charging current (factory set) at 1.2 A 2.4 A Adjustment range charge voltage at charging current <50 mA 26.5 ... 28.5 V Holding current for charged battery at voltage 27.3 V (factory set) <50 mA Overload or short circuit during battery operation system switches off AC-Powerfail signal Vin <93 V AC and <187 V AC closed relay A Low battery signal battery voltage below 22 V 0.5 closed relay B During battery charge operation output current reduction by 1.4 x charge current Signal Module - Option SIG The option Signal module (SIG) provides three functions: * Remote ON/OFF * AC-Powerfail signal (PF) * DC-OK signal The power supply can be controlled by remote ON/OFF signal. If pin 1 and 2 are connected together unit is ON, with disconnection unit is OFF. AC-Powerfail and DC-OK signals are available via isolated relay contacts. Please note option SIG is not available for TIS75 models. Tel: +44 (0)118 984 5515 UK Tel: +49 (0)700 9977 1000 D Mechanical Details TIS150 TIS75 DIN-Rail Power Case Material: Internal Fuse: Weight: Case Material: Internal Fuse: Weight: Steel & to IP20 4 A Slow Blow 480g approx. TIS300 Steel & to IP20 4 A Slow Blow 800g approx. TIS500/600 Industrial Power Supplies 75-600 Watts TIS Series TIS500 Dimensions in brackets Case Material: Internal Fuse: Weight: Steel & to IP20 6.3 A Slow Blow 1400g approx. Case Material: Internal Fuse: Weight: Steel & to IP20 12 A Slow Blow 2000g approx. Wall Mounting Kit Tel: +33 (0)820 801 401 F A B C D E F G 25.0 - 135 150.6 4.6 7.5 TIS75 MK075 50.0 TIS150 MK150 145.0 20.0 105.0 135 150.6 4.6 7.5 TIS300 MK300 145.0 20.0 105.0 135 150.6 4.6 7.5 TIS500 MK500 145.0 20.5 105.0 150 160.0 4.6 7.5 TIS600 MK600 190.0 37.5 115.0 198 213.2 4.6 7.5 www.xpplc.com Models Order code Tel: +41 (0)56 483 34 00 CH Rev 1.0