Expansion module for safety relays KZE5
-
YS Part number 85102954
"Multiplication of contacts" function for safety relays
1- or 2-channel operation
Security with redundancy and feedback circuit
5 "NO" security contacts
Performance Level (PL) e, safety category 4 to EN ISO 13849-1
SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
Part numbers
Specifications
Supply frequency range (Hz)
Operating characteristics
Multiplication of the number of contacts for safety relays
Display of output state by LED
Output : OUT1 (relay K1)
Output : OUT2 (relay K2)
85 102 956 : 24 VAC/DC
85 102 954 : 110-115 VAC
85 102 955 : 230-240 VAC
Supply frequency range (Hz)
AC : -
15 / + 10 % U
DC :
±
10 % U (at 10 % residual ripple)
DC :
- 15 / + 10 % U (at 48 % residual ripple)
1,8 VA (24 VAC/DC)
3,0 VA (110, 230 VAC)
Maximum response time on emergency stop
Forcibly guided relays (positively driven)
Number of safety circuits
Max. thermal current I for each contact
According to AC15 (NO contacts) : 3 A / 230 VAC
According to AC15 (NC contacts) : 2 A / 230 VAC
According to DC13 (NO contacts) : 4 A / 24 VDC ; 0,5 A / 110 VDC
According to DC13 (NC contacts) : 4 A / 24 VDC
At 5 A, 230 VAC, cos φ
=
1 : > 1,5 x 105 switching cycles
At 8 A, 24 VDC, according to DC 13 (NO contacts) : > 25 x 103 switching cycles (ON : 0,4 s ; OFF : 9,6 s)
20 x 106 switching cycles
1200 switching cycles / h
Protection against short circuits
Max. fuse rating : 10 A gL
Line circuit breaker : B 6 A
Operating temperature (
o
C)
Climate resistance according to IEC/EN 60068
-1
Vibration resistance according to IEC/EN 60068
-2-6
Amplitude : 0,35 mm
Frequency:10→55Hz
Electromagnetic environment
Immunity to electrostatic discharges acc.
IEC/EN 61000
-4-
2
Immunity to radiated, radio
-frequency, electromagnetic
field acc. IEC/EN 61000
-4-3
Immunity to rapid transient bursts acc. to IEC/EN 61000
-4-
4
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com