Type 2 surge protection device-VAL-MS 800/30 VF/FM-2805402
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge arrester consisting of 2-channel base element with remote indication contact and protective plugs
connected in series with a varistor and a gas-filled spark gap.
Product Features
With or without floating remote indication contact
Disconnect device on each individual plug
Mechanical coding of all slots
Type 2 consistent plug-in surge arresters
Optical, mechanical status indication for the individual arresters
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 250.0 GRM
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 97 mm
Width 35.6 mm
Depth 58 mm
Horizontal pitch 2 Div.
Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
https://www.phoenixcontact.com/us/products/2805402
08/19/2014Page2/6
Type 2 surge protection device-VAL-MS 800/30 VF/FM-2805402
Technical data
Ambient conditions
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 25g
Vibration (operation) 5g
General
Standards/specifications IEC 61643-11 2011
EN 61643-11 2012
IEC test classification II
T2
EN type T2
IEC power supply system IT (please see note below)
Number of ports One
SPD design Combination type
Mode of protection L-PEN
L-PE
Mounting type DIN rail: 35 mm
Color black
Housing material PA 6.6
PBT
Pollution degree 2
Distance between live and grounded parts 8 mm
Inflammability class according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 2
Surge protection fault message Optical, remote indicator contact
Additional descriptions
Note
Usable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts
(bodies) of the equipment of the low-voltage installation is connected to
the earthing arrangement of the transformer substation. (interconnected
earthing arrangement of the HV-transformer substation with the bodies
of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE
0100-442 Fig. 44D / Example a)
Protective circuit
Nominal voltage UN400/690 V AC (TN-C)
690 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
https://www.phoenixcontact.com/us/products/2805402
08/19/2014Page3/6
Type 2 surge protection device-VAL-MS 800/30 VF/FM-2805402
Technical data
Protective circuit
Maximum continuous operating voltage UC (L-PE) 800 V AC
Maximum continuous operating voltage UC (L-PEN) 800 V AC
Rated load current IL80 A
Residual current IPE ≤ 3 µA
Standby power consumption PC≤ 3 mVA
Nominal discharge current In (8/20) µs (L-PE) 15 kA
Nominal discharge current In (8/20) µs (L-PEN) 15 kA
Maximum discharge current Imax (8/20) µs (L-PE) 30 kA
Maximum discharge current Imax (8/20) µs (L-PEN) 30 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up (L-PE) ≤ 5 kV
Voltage protection level Up (L-PEN) ≤ 5 kV
Residual voltage Ures (L-PE) ≤ 3 kV (at In)
≤ 2.6 kV (at 10 kA)
≤ 2.4 kV (at 5 kA)
≤ 2.3 kV (at 3 kA)
Residual voltage Ures (L-PEN) ≤ 3 kV (at In)
≤ 2.6 kV (at 10 kA)
≤ 2.4 kV (at 5 kA)
≤ 2.3 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PE) ≤ 5 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PEN) ≤ 5 kV
TOV behavior at UT (L-PEN) 1550 V AC (5 s / withstand mode)
Response time tA (L-PE) ≤ 100 ns
Response time tA (L-PEN) ≤ 100 ns
Max. backup fuse with branch wiring 100 A AC (gG)
Max. backup fuse with V-type through wiring 80 A AC (gG)
Indicator/remote signaling
Connection name Remote fault indicator contact
Switching function PDT contact
Operating voltage 5 V AC ... 250 V AC
30 V DC
Operating current 5 mA AC ... 1.5 A AC
1 A DC
Connection method Screw connection
Screw thread M2
https://www.phoenixcontact.com/us/products/2805402
08/19/2014Page4/6
Type 2 surge protection device-VAL-MS 800/30 VF/FM-2805402
Technical data
Indicator/remote signaling
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 1.5 mm²
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 1.5 mm²
AWG conductor cross section 28 ... 16
Connection data
Connection method Screw connection
Conductor cross section stranded min. 1.5 mm²
Conductor cross section stranded max. 25 mm²
Conductor cross section solid min. 1.5 mm²
Conductor cross section solid max. 35 mm²
AWG conductor cross section 15 ... 2
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 16 mm
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130805
eCl@ss 7.0 27130805
eCl@ss 8.0 27130805
ETIM
ETIM 2.0 EC000941
ETIM 3.0 EC000941
ETIM 4.0 EC000941
ETIM 5.0 EC000941
UNSPSC
UNSPSC 6.01 30212010
https://www.phoenixcontact.com/us/products/2805402
08/19/2014Page5/6
Type 2 surge protection device-VAL-MS 800/30 VF/FM-2805402
Classifications
UNSPSC
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
Approvals
KEMA-KEUR / ÖVE / GL / CCA / IECEE CB Scheme / KEMA-KEUR / ÖVE
Ex Approvals
Approvals submitted
Approval details
KEMA-KEUR
ÖVE
GL
CCA
IECEE CB Scheme
https://www.phoenixcontact.com/us/products/2805402
08/19/2014Page6/6
Type 2 surge protection device-VAL-MS 800/30 VF/FM-2805402
Approvals
KEMA-KEUR
ÖVE
Drawings
Dimensioned drawing
99
45 22,5
65,5
58
51,5
Circuit diagram
12 14
11
FM
L