L205-30-60_211605-211393-211394 (pdf) 0308 Rev. 05
Technical Assistance (800) 343-1391 www.aemc.com
1
of 4
ORDERING INFORMATION CATALOG NO.
Simple Logger® Model L205, Stray Voltage with Leads (0 to 25.5Va c Input) .............................. Cat. #2116.05
Simple Logger® Model L230, RMS Voltage with Leads (0 to 300Va c Input) .............................. Cat. #2113.93
Simple Logger® Model L260, RMS Voltage with Leads (0 to 600Va c Input) ............................... Cat. #2113.94
All AC Voltage Simple Loggers® are supplied with software (CD-ROM), 6 ft DB-9 RS-232 cable, 9V Alkaline battery, 5 ft lead set,
and user manual
Accessories
Safety Grip Probes, set of 2 .......................................................................Cat. #2111.31
110V US Outlet Adaptor with Banana Jacks (for Models L230 or L260) ...................................Cat. #2118.49
Voltage Leads, (2) with clips, 5 ft ...................................................................Cat. #2118.51
AC Voltage Simple Logger®
Models L205, L230 & L260
ELECTRICAL
Number of Channels: One
Measurement Range:
0 to 25Vrms (L205)
0 to 300Vrms (L230)
0 to 600Vrms (L260)
Input Connection:
Recessed safety 4mm banana jacks
Resolution: 8 Bit
L205: 12.5mV max
L230: 250mV max
L260: 500mV max
Accuracy*: ±1% of Reading + Resolution
Sample Rate: 4096/hr max, decreases by
50% each time memory is full
Storage Technique:
Time Extension Recording™ (TXR™)
Data Storage: 8192 readings
Power: 9V Alkaline battery
Battery Life:
Up to one yr of recording @ 25°C
Output: RS-232 via DB-9 connector
Indicators: Red LED double flashes in
LOGGING, single flashes in STANDBY,
and is off in OFF mode
Controls: One button used to start and
stop recording sessions and to turn the
data logger on and off
MECHANICAL
Size: 27/8 x 25/16 x 15/8"
(73 x 59 x 41mm)
Weight: (with battery) 5 oz (140g)
Mounting: Base plate mounting holes or
Velcro® pads
ENVIRONMENTAL
Operating Temperature:
-4° to +158°F (-20 to +70°C)
Storage Temperature:
-4° to +174°F (-20 to +80°C)
Relative Humidity:
5 to 95% non-condensing
• Three input types to choose from:
Model L205
0 to 25Vrms input (stray voltage)
Model L230
0 to 300Vrms input
Model L260
0 to 600Vrms input
• True RMS measurements
• Inputs via color coded safety
Banana Jacks
• Scale automatically selected
by software
• Includes test leads and
alligator clips
• Double Insulation
• CE Mark
• HVAC troubleshooting
• Line voltage monitoring
• Surge/Sag monitoring
• Stray voltage monitoring
• Dropout monitoring