Timers GT5P Series GT5P Series -- ON Delay Timers Key features of the GT5P series include: * SPDT, 5A contacts * 8-pin, octal base * 9 time ranges * Repeat error 0.2% maximum * Control settings by hand or screwdriver * Power ON and timing out LED indicators * Uses the same sockets and hold down clips as IDEC's RR2P 8-pin relays Rated Operating Voltage 100 to 120V AC (50/60Hz) 200 to 240V AC (50/60Hz) 24V AC/DC 12V DC Voltage Tolerance AC type: 15% DC type: 10% (ripple 10% maximum) G Resistive load 120V AC/24V DC, 5A 240V AC, 3A Inductive load 240V AC, 0.8A 120V AC, 1.4A 24V DC, 1.7A Specifications Timers Contact Rating Allowable Contact Power (resistive load) 960VA AC 120W DC Contact Form SPDT UL Recognized CSA Certified File No. E55996 File No. LR66809 Voltage 250V AC, 150V DC Repeat Error 0.2% 10msec Voltage Error 0.5% 10msec Temperature Error 3% maximum (over -10 to 50C, reference temperature 20C) Setting Error 10% maximum Reset Time When turning power off after time up: 0.1 sec maximum When turning power off before time up: 1 sec maximum Insulation Resistance 100M minimum Dielectric Strength 2000V AC, 1 minute (except between contacts of the same pole) Vibration Resistance 100N (approximate 10G) Shock Resistance Operating extremes: 100N (approximate 10G) Damage limits: 500N (approximate 50G) Power Consumption 100V AC type: 1.5VA (at 50Hz) 200V AC type: 1.6VA (at 50Hz) 24V DC type: 0.9W Electrical Life 100,000 operations minimum (at rated load) Mechanical Life 20,000,000 operations minimum Operating Temperature -10 to +50C Operating Humidity 45 to 85% RH GT5P Table of Contents Specifications -- G-58 Part Numbering List -- G-59 Timing Diagrams / Schematics -- G-60 GT5P Accessories -- G-61 GT5P Dimensions -- G-62 Timing Diagrams Overview -- G-4 1.Inductive load (reference), cos =.3 to .4 or L/R=15msec. 2.Minimum applicable load: 5VDC/10mA (reference). G-58 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC Timers GT5P Series Part Numbering List Mode of Operation Contact Output Rated Voltage 100 to 120V AC 200 to 240V AC SPDT 240V AC, 3A 24V AC/DC 12V DC Complete Part No. 1S -- 3S GT5P-N3SA100 6S -- 10S GT5P-N10SA100 30S GT5P-N30SA100 60S GT5P-N60SA100 3M GT5P-N3MA100 6M GT5P-N6MA100 10M GT5P-N10MA100 1S GT5P-N1SA200 3S -- 6S GT5P-N6SA200 10S GT5P-N10SA200 30S GT5P-N30SA200 60S GT5P-N60SA200 3M GT5P-N3MA200 6M GT5P-N6MA200 10M GT5P-N10MA200 1S GT5P-N1SAD24 3S -- 6S GT5P-N6SAD24 10S GT5P-N10SAD24 30S -- 60S GT5P-N60SAD24 3M -- 6M GT5P-N6MAD24 10M GT5P-N10MAD24 1S -- 3S -- 6S -- 10S GT5P-N10SD12 30S GT5P-N30SD12 60S GT5P-N60SD12 3M -- 6M -- 10M GT5P-N10MD12 G Timers ON-Delay 24V DC/ 120V AC, 5A Time Range For sockets and accessories, see page G-61. www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-59 Timers GT5P Series Timing Diagram/Schematic/Electrical Life Curves SPDT 4 5 3 6 (-) 2 7 (+) 8 1 POWER Operation Mode Do not apply voltage to terminals 1, 3, and 4. Terminal No. Item Operation Set Time Power (Power) 2-7 Delayed Contact ON-Delay (NC) 5-8 (NO) 6-8 POWER Indicator OUT Timers G Life (x 10,000 operations) Electrical Life Curves 100 70 50 30 20 24V DC Resistance Load 120V AC Resistance Load 10 7 5 3 2 240V AC Resistance Load 24V DC Induction Load 120V AC Induction Load 240V AC Induction Load 1 0 G-60 www.idec.com 1 2 3 4 Load Current (A) 5 USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC Timers GT5P Series Accessories Mounting Accessories Style Part Numbers: Mounting Accessories and Sockets Appearance Use with Timers 8-Pin Screw Terminal (dual tier) GT5P Applicable Hold-Down Springs Appearance Part No. Part No. SR2P-05 SFA-203 8-Pin Fingersafe Socket GT5P SR2P-05C 8-Pin Screw Terminal GT5P SR2P-06 DIN Mounting Rail Length 1000mm -- BNDN1000 DIN Rail/ Surface Mounting Accessories SFA-202 G Mounting 8-Pin Solder Terminal Accessories Applicable Hold-Down Springs SFA-402 SR2P-51 Installation of Hold-Down Springs DIN Rail Mount Socket Panel Mount Socket Insert the springs into the outer slots with the projections facing inside. Hold-down Spring SFA-402 Insert the springs into the slots. Insert Socket SR3P-05 Socket SR2P-06 Hold-down Spring (sold separately) SFA-202 (use two springs) www.idec.com Hold-down Spring (sold separately) SFA-203 (use two springs) 8-pin Socket SR2P-511 USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-61 Timers Part Numbers: Mounting Accessories and Sockets Timers GT5P Series Dimensions Dimensions: GT5P Series " GT5P Timer, 8-Pin with SR2P-05 (When using DIN Rail) When using BAA/BAP: 102 maximum 52 33 DIN Rail (BAA/BAP/BADA) o25 36 98 maximum Hold-down spring 7.5 61 16.5 13 20 74 3 29 28.5 GT5P Timer, 8-Pin with SR2P-06 (When using DIN Rail) When using BAA/BAP: 95.5 maximum 36 60 31.7 1.7 91.5 maximum Hold-down Spring G 7.5 61 13 DIN Rail 18 74 1 29 Timers 22 G-62 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC Timers GT5Y Series GT5Y Series -- ON Delay Timers Key features of the GT5Y series include: * 4PDT, 3A or DPDT, 5A contacts * 4 time ranges * Repeat error 0.2% maximum * Control settings by hand or screwdriver * Power ON and timing out LED indicators * Uses the same sockets and hold-down clips as IDEC's RY4S and RU series relays UL, c-uL Listed File No. E55996 GT5Y-2 Contact Form DPDT 4PDT Resistive Load 220V AC, 5A 30V DC, 5A 220V AC, 3A 30V DC, 3A Inductive Load 220V AC, 2A 30V DC, 2.5A 220V AC, 0.8A 30V DC, 1.5A Resistive Load 1100VA AC 150W DC 660VA AC 90W DC Inductive Load Cos O = 0.3 L/r = 7msec 440VA AC 75W DC 176VA AC 45W DC Allowable Contact Power Allowable Voltage 250V AC, 125V DC Allowable Current 5A Temperature Error 3% maximum (over -10 to 50C, reference temperature 20C) Setting Error 10% maximum Reset Time When turning power off after time up: 0.1 second maximum When turning power off before time up: 1 second maximum Insulation Resistance 100M minimum Dielectric Strength 2,000V AC, 1 minute (except between contacts of the same pole) Vibration Resistance 100N (approximate 10G) Shock Resistance Operating extremes: 100N (approximate 10G) Damage limits: 500N (approximate 50G) Power Consumption 100V AC type: 1.5VA (at 50Hz) 200V AC type: 1.6VA (at 50Hz) 24V DC type: 0.9W Electrical Life 500,000 operations minimum (220V AC, 5A) 200,000 operations minimum (110V AC, 3A) Mechanical Life 50,000,000 operations minimum 50,000,000 operations minimum Operating Temperature -10 to +50C Operating Humidity 45 to 85% RH G Timers Rated Operating Voltage 100 to 120V AC (50/60Hz) 200 to 240V AC (50/60Hz) 24V DC 24V AC 12V DC Rated Load Specifications GT5Y-4 3A GT5Y Table of Contents Part Number List -- G-64 Timing Diagrams -- G-65 GT5Y Accessories -- G-66 GT5Y Dimensions -- G-67 1. Minimum applicable load: GT5Y-2: 5V DC, 20mA (reference value); GT5Y-4: 5V DC, 10mA (reference value). 2. Inductive load: cos =.3, L/R=7msec. www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-63 Timers GT5Y Series Part Numbering List Mode of Contact Operation Output Rated Voltage 100 to 120V AC 200 to 240V AC DPDT 220V AC/ 30V DC, 5A 12V DC 24V DC 24V AC ON-Delay 100 to 120V AC G Timers 200 to 240V AC 4PDT 220V AC/ 30V DC, 3A 12V DC 24V DC 24V AC Time Range 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M 1S/10S/1M/10M 3S/30S/3M/30M 6S/60S/6M/60M Complete Part No. GT5Y-2SN1A100 GT5Y-2SN3A100 GT5Y-2SN6A100 GT5Y-2SN1A200 GT5Y-2SN3A200 GT5Y-2SN6A200 GT5Y-2SN1D12 GT5Y-2SN3D12 GT5Y-2SN6D12 GT5Y-2SN1D24 GT5Y-2SN3D24 GT5Y-2SN6D24 GT5Y-2SN1A24 GT5Y-2SN3A24 GT5Y-2SN6A24 GT5Y-4SN1A100 GT5Y-4SN3A100 GT5Y-4SN6A100 GT5Y-4SN1A200 GT5Y-4SN3A200 GT5Y-4SN6A200 -- GT5Y-4SN3D12 -- GT5Y-4SN1D24 GT5Y-4SN3D24 GT5Y-4SN6D24 GT5Y-4SN1A24 GT5Y-4SN3A24 GT5Y-4SN6A24 1. For sockets and accessories, see page G-66. Timing Ranges Code Scale 1S 10S Time Range Indication x 0.1 S Time Range 0.1 second to 1 second x1 S 0.2 second to 10 seconds x 0.1 M 1.2 seconds to 1 minute 10M x1 M 12 seconds to 10 minutes 3S x1 S 0.1 second to 3 seconds x 10 S 0.5 second to 30 seconds x1 M 3 seconds to 3 minutes 30M x 10 M 30 seconds to 30 minutes 6S x1 S 0.1 second to 6 seconds x 10 S 1 second to 60 seconds x1 M 6 seconds to 6 minutes x 10 M 1 minute to 60 minutes 1M 30S 3M 60S 6M 60M G-64 0 to 10 0 to 3 0 to 6 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC Timers GT5Y Series Timing Diagram/Schematics/Electrical Life Curves GT5Y-2 GT5Y-4 DPDT 4PDT 1 5 1 5 4 8 2 6 3 7 4 8 Internal Connections (bottom view) 9 13 (-) 9 10 13 (-) 12 (+) 14 11 12 (+) 14 POWER POWER Item Terminal No. Operation Set Time Power (Power) 13-14 Delayed Contact Operation Mode: ON-Delay 1-9, 2-10, (NC) 3-11, 4-12 5-9, 6-10, (NO) 7-11, 8-12 POWER Indicator OUT G For an explanation of timing modes, see page E-4. Timers Electrical Life Curves Life (x 10,000 operations) 5000 AC Load 110V AC Resistance Load GT5Y-2 220V AC Resistance Load GT5Y-4 1000 500 110V AC Induction Load 100 220V AC Induction Load 50 1 2 3 4 5 Load Current (A) Life (x 10,000 operations) 5000 30V DC Resistance Load 1000 500 30V DC Induction Load 100V DC Resistance Load 100 100V DC Induction Load 50 1 www.idec.com DC Load GT5Y-2 GT5Y-4 2 3 4 5 Load Current (A) USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-65 Timers GT5Y Series Accessories DIN Rail Mounting Accessories Part Numbers: DIN Rail/Surface Mount Sockets and Hold-Down Springs DIN Rail Mount Socket Style Appearance Part No. 14-Blade Screw Terminal Applicable Hold-Down Springs Appearance Part No. SY4S-05 SFA-202 14-Blade Screw Terminal (fingersafe) SY4S-05C DIN Mounting Rail Length 1000mm BNDN1000 Timers G Panel Mounting Accessories Part Numbers: Panel Mount Socket and Hold-Down Springs Panel Mount Socket Style Appearance 14-Blade Solder Terminal Applicable Hold-Down Springs Part No. Appearance SY4S-51 Part No. SFA-302 PCB Mounting Accessories Part Numbers: PCB Mount Sockets with Applicable Hold-Down Springs PCB Mount Socket Style Appearance Part No. Applicable Hold-Down Springs Appearance Part No. 14 Blade, PCB Terminal SY4S-61 SFA-302 14 Blade, PCB Terminal SY4S-62 SY4S-02F1 G-66 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC Timers GT5Y Series Dimensions GT5Y Timer, Blade with SY4S-05 28.5 when When using DIN Rail When using BAA/BAP: 87.6 maximum using BAA 0.7 30 83.6 maximum 6 18 2-o4.2 Mounting Hole (M4 screw hole) 6.4 Holddown Spring DIN Rail 8 7 6 5 4 3 2 1 45 52.6 58.6 26 4.2 6 62 62 27.5 21 Terminal Arrangement DIN Rail (BAA) M3 Screw 3 18.5 4max. 25 4.8min. o3.2min. 3 18.5 26 25 14 13 12 11 10 9 (TOP VIEW) 5.9max. G Timers www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC G-67 Timers General Instructions General Instructions for All Timer Series Load Current With inductive, capacitive, and incandescent lamp loads, inrush current more than 10 times the rated current may cause welded contacts and other undesired effects. The inrush current and steady-state current must be taken into consideration when specifying a timer. Time Setting The time range is calibrated at its maximum time scale; so it is desirable to use the timer at a setting as close to its maximum time scale as possible. For a more accurate time delay, adjust the control knob by measuring the operating time with a watch before application. Contact Protection Switching an inductive load generates a counter-electromotive force (back EMF) in the coil. The back EMF will cause arcing, which may shorten the contact life and cause imperfect contact. Application of a protection circuit is recommended to safeguard the contacts. Input Contacts Use mechanical contact switch or relay to supply power to the timer. When driving the timer with a solid-state output device (such as a two-wire proximity switch, photoelectric switch, or solid-state relay), malfunction may be caused by leakage current from the solid-state device. Since AC types comprise a capacitive load, the SSR dielectric strength should be two or more times the power voltage when switching the timer power using an SSR. Temperature and Humidity Use the timer within the operating temperature and operating humidity ranges and prevent freezing or condensation. After the timer has been stored below its operating temperature, leave the timer at room temperature for a sufficient period of time to allow it to return to operating temperatures before use. Generally, it is desirable to use mechanical contacts whenever possible to apply power to a timer or its signal inputs. When using solid state devices, be cautious of inrushes and back-EMF that may exceed the ratings on such devices. Some timers are specially designed so that signal inputs switch at a lower voltage than is used to power the timer (models designated as "B" type). Environment Avoid contact between the timer and sulfurous or ammonia gases, organic solvents (alcohol, benzine, thinner, etc.), strong alkaline substances, or strong acids. Do not use the timer in an environment where such substances are prevalent. Do not allow water to run or splash on the timer. Timers G Vibration and Shock Excessive vibration or shocks can cause the output contacts to bounce, the timer should be used only within the operating extremes for vibration and shock resistance. In applications with significant vibration or shock, use of hold down springs or clips is recommended to secure a timer to its socket. Timing Accuracy Formulas Timing accuracies are calculated from the following formulas: Repeat Error Voltage Error = 1 x Maximum Measured Value - Minimum Measured Value x 100% 2 Maximum Scale Value = Tv - Tr x 100% Tr Tv: Average of measured values at voltage V Tr: Average of measured values at the rated voltage Temperature Error = Tt - T20 x 100% T20 Tt: Average of measured values at C T20: Average of measured values at 20C Setting Error G-68 = Average of Measured Values - Set Value x 100% Maximum Scale Value www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC