International Products
169
www.littelfuse.com
International Products
© 2005 Littelfuse POWR-GARD Products Catalog
JJ
F
B
B
A
G
D
F
H
H
A
G
G
D
K
E
E
FIG. 1 FIG. 2
FIG. 3
British Dimension HRCII-C Fuses
600 Volts AC 2 600 Amperes
Specifications
Voltage Rating: 600 Volts AC, 250 Volts DC
Interrupting Rating: 200,000 amperes rms symmetrical AC
80,000 amperes rms symmetrical DC
Ampere Range: 2 600 amperes
Approvals: CSA Certified to Standard C22.2 No. 106-M90
(File No. LR90341)
Ampere ratings
2CO 2 10 25 50 80
4 15 30 60 100
6 20 40
2CC 125 200 300 400 500
150 250 350 450 600
2CM 80 125 200 300 400
100 150 250 350
Example part number (series & amperage): 2CM 150
Recommended Fuse Blocks
DF30 (F, B, FB) Fits 2 – 30 amps
DF60 (F, B, FB) Fits 40 – 60 amps
DF100 (F, B, FB) Fits 80 – 100 amps
For additional information on HRCII-C fuse holders, contact factory.
Cat. No. Old LF
Part No.
Refer To
Fig. No.
Dimensions in mm (inches in parentheses)
A B C D E F G H J K
2CO 2-30 FII 1 56 (2.2) 21 (0.83) 85 (3.3) 9 (0.35) 1 (0.04) 73 (2.87) 5.5 (0.21) 7.5 (0.29)
2CO 40-60 FII 1 57 (2.24) 26 (1.02) 88 (3.45) 13 (0.51) 1.6 (0.06) 73 (2.87) 5.5 (0.21) 7.5 (0.29)
2CO 80-100 FII 1 68 (2.88) 36 (1.42) 110 (4.33) 19 (0.75) 2.4 (0.09) 94 (3.7) 8.7 (0.34)
2CC 125-200 FIIC 2 76 (3) 41 (1.61) 137 (5.39) 19 (0.75) 3.6 (0.14) 111 (4.37) 8.7 (0.34) 16 (0.63)
2CC 250-400 FIIC 3 81 (3.19) 58 (2.28) 210 (8.27) 26 (1.02) 6.5 (0.26) 133 (5.24) 10.3 (0.4) 16 (0.63) 25.4 (1)
2CC 450-600 FIIC 3 83 (3.27) 74 (2.91) 210 (8.27) 26 (1.02) 6.5 (0.25) 133 (5.24) 10.3 (0.4) 16 (0.63) 25.4 (1)
2CM 80-100 FIIM 2 66 (2.6) 31 (1.22) 135 (5.31) 19 (0.75) 3.6 (0.14) 111 (4.37) 8.7 (0.34) 16 (0.63)
2CM 125-200 FIIM 1 77 (3.03) 41 (1.81) 110 (4.33) 19 (0.75) 2.4 (0.09) 94 (3.7) 8.7 (0.34) 10.3 (0.4)
2CM 250-400 FIIM 2 81 (3.19) 58 (2.25) 136 (5.35) 26 (1.02) 5.2 (0.2) 111 (4.37) 8.7 (0.34) 16 (0.63)
*Hole diameter to accept insulated stud (types C and D) mm min
HRCII-C fuses are stud-mounted fuses designed to British standard
dimensions. They are generally used for motor short-circuit protection in
dead-front holders, and are normally required to be used in conjunction
with a motor running overload device.